Superwatt Diesel Generator Specifications

The document provides specifications for the SUPERWATT diesel generator set, including models P200PB and P220EB, with power ratings of 160 kW (prime) and 176 kW (standby). It details features such as ISO compliance, assembly, control systems, and alternator ratings, along with engine specifications from Perkins. Additionally, it outlines standard features, optional accessories, and warranty information for the generator set.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
44 views4 pages

Superwatt Diesel Generator Specifications

The document provides specifications for the SUPERWATT diesel generator set, including models P200PB and P220EB, with power ratings of 160 kW (prime) and 176 kW (standby). It details features such as ISO compliance, assembly, control systems, and alternator ratings, along with engine specifications from Perkins. Additionally, it outlines standard features, optional accessories, and warranty information for the generator set.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

PrimeModel:P200PB

StandbyModel:P220EB

DIESELGENERATORSET 110-480V 3P4W


ISO9001:2000 StandardFeaturesandCharacteristics
SWTDIESELGENERATORSET QUALITYSTANDARDS
The SUPERWATT generator set compliance with all main
RatingRange standards, such as ISO8528 (GB/T2820-97), GB755,
1500RPM 50Hz BS5000, VDE0530, ISO3046, IEC34-1, CSA22-2,AS1359
ISO14001.
Standby: kW 176
DieselengineandalternatorOEMauthorizationcertificate
kVA 220 andtheirqualityassurance.
Prime: kW 160 Other standards and certifications can be considered on request.
kVA 200 ASSEMBLY
Theengineandalternatorareclosecoupledbymeansofan
[Link]
guaranteenoharmfulvibrationwilloccur.
Anti-vibration pads are placed between engine alternator feet.
and the baseframe. Thus ensuring complete vibration isolation
of the rotating assemblies and enabling the machine to be
placed on an uneven surface without any detrimental effects.
For durability and corrosion resistance, all iron and steel
surfaces of canopy fabrications have been treated for coating
by grit blast cleaning. Then covered by a polyester powder
paint which provides an excellent corrosion resistant surface.

CONTROLSYSTEMANDPROTECTION
[Link]
systemisusedtostartandstoptheengine,indicate
[Link]
featuresinside.
Therevolvingpartsarecoveredbyasafetynet,andtheplace
Thepictureisforreferenceonly.
whichiseasytoscaldandgotanelectricshockalltohavethe
Obviouswarningslogan.
warranty
ALTERNATORRATINGS SUPERWATT Company provides one-source responsibility for
the generator set and accessories.
AlternatorModel UCI274H(STAMFORD) SPG341H(SPARKS)
Each SUPERWATT generating set has gone through 2 hours
FrequencyandSpeed 50Hz 1500rpm 50Hz 1500rpm load test for running 0%, 25%, 50%, 75%, 100% and 110% load
all protective devices and control functions are stimulated and
PrimePowerData checked before dispatch.
Class-TEMPRise( ) Cont.H-125/40 Cont.H-125/40 All equipment is guaranteed for the period of 1000 hours or 12
Voltageseriesstar 380 400 415 440 380 400 415 440
mouths from the date of commissioning or 18 months from
Voltageparallelstar
shipping, whichever occurs first.
190 200 208 220 190 200 208 220
Voltageseriesdelta 220 230 240 254 220 230 240 254
Convenience for operation and maintenance, backed by
PERKINS, NEWAGE and LEROY SOMER global service
Ratingcapacity(kVA) 200 200 200 N/A 200 200 200 N/A network.
Ratingpower(kW) 160 160 160 N/A 160 160 160 N/A
Powerefficiency(%) 93.0 93.3 93.4 N/A 93.0 93.3 93.4 N/A
Inputpower(kW) 172.0 171.5 171.3 N/A 172.0 171.5 171.3 N/A

StandbyPowerData RATINGS:[Link]:Standby
ratings apply to installations served by a reliable utility [Link] standby rating is for
Class-TEMPRise( ) Standby.H-163/27 Standby.H-163/27 this rating. Ratings are in accordance with ISO-3046/1, BS 5514,AS 2789, and DIN 6271.
Voltageseriesstar 380 400 415 440 380 400 415 440 Prime Power Ratings: Prime power ratings apply to installations where utility power is
Voltageparallelstar unavailable or unreliable. At varying load, the number of generator set operating hours
190 200 208 220 190 200 208 220
is unlimited. A 10% overload capacity is available for one hour in twelve. Ratings are in
Voltageseriesdelta 220 230 240 254 220 230 240 254 in accordance with ISO-8528/1, overload capacity in accordance with ISO-3046/1, BS 5514
AS 2789, and DIN 6271. For limited running time and base load ratings, consult the
Ratingcapacity(kVA) 220 220 220 N/A 220 220 220 N/A factory. The generator set manufacturer reserves the right to change the design or
Ratingpower(kW) 176 176 176 N/A 176 176 176 N/A specifications without notice and without any obligation or liability whatsoever.
GENERAL GUIDELINES FOR DERATING: Altitude: Derate 2.0% per 300m (984 ft.)
% 92.7 93.0 93.2 N/A 92.7 93.0 93.2 N/A elevationabove1000m(3279ft.)uptoamaximumelevationof2450m(8000ft.).Morethan
Inputpower(kW) 189.9 189.2 188.8 N/A 189.9 189.2 188.8 N/A 2450m(8000)t,f pelasecona
tctusorourdeaelrforasssia
tnce.
Derate 6.0% per 11 (20 ) temperature above 40 (104 ).
Inlinewithourpolicyofcontinuousproductdevelopment,wereservetherightto
Changethespecificationwithoutnotice.

1
ALTERNATOR

Specification 1500RPM 50HZ AlternatorsmeettherequirementofBSEN60034andthe


relevantsectionofotherinternationalstandardssuchas
Type 4-Pole, Rotating Field BS5000,VDE0530,NEMAMG1-32,IEC34,CSAC22.2-100
Exciter type Brushless, Self excited As1359,andotherstandardsandcertificationscanbe
Voltage regulator (AS440) Solid State, Volts/Hz consideredonrequest.
Voltageregulation 1.5% The2/[Link]
Insulation Class H the2/3pitchandcarefullyselectedpoleandtoothdesigns,
ensuresverylowwaveformdistortion.
Protection IP23
Ratedpowerfactor Brushlessalternatorwithbrushlesspilotexciterforexcellent
0.8
loadresponse.
Statorwinding Doublelayerconcentric
TheinsulationsystemisclassH,easyparallelingwithmains
Windingpitch Twothirds orothergenerators,standard2/3pitchstatorwindingsavoid
Windingleads 12 excessiveneutralcurrents.
Maximumoverspeed 2250RPM Backedbyaworldwideservicenetwork.
Sustainedshortcircuit Self excited machines do not
sustain a short circuit current
Waveformdistortion Noload<1.5%
Non-distortingbalanced
linearload<5.0%
Altitude 1000m

DIESELENGINE

1106A-70TAG4 diesel engines are manufactured by Perkins EngineElectrical


Engines Company Limited (UK).
EngineElectricalSystem 1500RPM 50Hz
ApplicationData Batterychargingalternator:
Engine Specifications 1500RPM 50Hz negative/positive Negative
Manufacturer PERKINS Volts(DC) 12V
Numberofcylinders 6 Ampererating 85A
Cylinderarrangement Verticalin-line Startermotorratedvoltage(DC) 12V

Cycle 4stroke,compressionignition Startermotorratedcapability 4KW


Inductionsystem Turbocharged, Batteryvoltage 12V
Airtoairchargedcooled
Compressionratio 16:1 Fuel
Bore 105mm FuelSystem 1500RPM 50Hz
Stroke 135mm
Cubiccapacity 7.01 litres Typeofinjectionsystem Direct
Directionofrotation Anti-clockwiseviewedonflywheel Fuelfeedpump DP210G
Firingorder 1,5,3,6,2,4
Max. Power at rated rpm 191.3 kW
Estimatedtotalweight(dry) 788kg Fuelliftpump 1500RPM 50Hz
Frequency regulation steady state 0.5% Fuelliftpumpflow 180liters/hr
Meanpistonspeed 6.75 m/s Fuelliftpumpsuctiondepression 17kPa
Pressure 137.9kPa
Exhaust Maximumfuelpumpsuction 10 kPa
Exhaust System 1500RPM 50Hz Governortype Electronicgovernor
Maximumbackpressure 10.0kPa
Exhaustgasflow(max) 36.6m/min
3
FuelConsumption 1500RPM 50Hz
Exhaustgastemperature(max) 580
Standbypower 46.3 liters/hour
Lubrication
PrimePower 45.0 liters/hour
LubricationSystem 1500RPM 50Hz
At75%ofPrimePower 34.7 liter/hour
Totallubricationcapacity 16.5liters
At50%ofPrimePower 24.0 liter/hour

2
ApplicationData DSE704AMFCONTROLLER(Optional)
CoolingSystem
CoolantSystem 1500RPM 50Hz
Facearea 0.60 m2
ThecontrollermadeinUK
Pressurecapsetting 68.9kPa(9.90lb/in)2 )
DEEPSEAgensetcontroller
Maximumtoptanktemperature 103 (218 )
Total system capacity
Controlpanelforsoundproofing
withradiator 21liters
The DSE704 is an Automatic Mains Failure module with generator
Draindowncapacity 1.3liters(2.3UKpints)
monitoring, protection and start facilities. It utilises advanced surface
Coolingfanairflow 375m/min
3
mount construction techniques to provide a compact yet highly
Minimumtemperaturetoengine 79 (175 ) specified module. This model can start the generator automatically when
Temperatureriseacrossengine the MAINS failure and then control the ATS turn to the genset side.
5
Operation of the module is via three pushbuttons mounted on the
Maxpermissibleexternal
front panel with STOP, MANUAL and AUTO positions.
systemresistance 35kPa (5.1 lbf/in)2 )
Panelintroduction:
Thermostatoperationrange 82-95
Indicatortypefrequency,voltmeterandammeter
todisplayunit'selectricalparameter.
NOTE: Thevoltageselectorandthecurrentselectorareusedfor
Alldataisbasedon: Choosethedifferentphasevoltageandcurrenttodisplay.
AlldatabasedonoperationtoBSAU141A1971;BS5514;ISO3046/11982;DIN6271.
Theoilpressuregauge,coolanttemperaturegaugeandthe
[Link].2-DperASTMD975.
batteryvoltagegauge.
3.ISO3046,Part1,StandardReferenceConditionsof:
101.3kPa(29.53inHg) Thecontroller.
AirTemperature:25 (77 ) Preheatingbutton.
110m(361ft)
30% Protection:
254mmH2O(10inH2O)
51mmHg(2inHg) Over Speed Shutdown.
Low Oil Pressure Shutdown.
ToBeDetermined High Engine Temp Shutdown.
Charger failure alarm.
Mains failure alarm.
Optional Under speed Protection.
DCSupply:8to35VContinuous.

CONTROLLERS
COMAPAMF25NTCONTROLLER(Optional)
DSE702ASCONTROLLER(Standard)

ThecontrollermadeinCzech

Comapgensetcontroller
ThecontrollermadeinUK

DEEPSEAgensetcontroller Controlpanelforsoundproof

The AMF25NT is an Automatic Mains Failure module with generator


monitoring, protection and start facilities. The controller has a large
Controlpanelforopen LCD screen, display the generator's each parameter, running and
The Model 702 is an Auto Start Engine Control Module designed to alarm information. The off/replacement button, mode switch button,
control the engine via a remote input signal or a key switch. The start/stop button and the LED indicator light make it easy for the user to
The module is used to start and stop the engine and indicate fault operate and maintain the generator.
conditions, automatically shutting down the engine and indicating the
Panelintroduction:
engine failure by LED, giving true, first up fault annunciation.
Indicator or digital type frequency, voltmeter and ampere meter
Panelintroduction: to display unit's electrical parameter.
Indicatortypefrequency,voltmeterandammeter Thebigredbuttonisusedbytheoperatortostopthegenset.
todisplayunit'selectricalparameter. emergently.
Thevoltageselectorandthecurrentselectorareusedfor Thecontroller.
choosethedifferentphasevoltageandcurrenttodisplay.
Function:
Thebigredbuttonisusedbytheoperatortostopthegenset.
emergently. Communication:RS232connection,usestheindustryrank
MODBUSprotocolcaneasilycommunicatewithothers
Theoilpressuregauge,coolanttemperaturegaugeandthe intelligencecontrolsystem.
batteryvoltagegauge.
[Link]-tamperLCDhoursrun Displayfunction:LCDscreencandisplaythegenerator's
counterisalsoprovided. parameterandthecontrolsystem'srunninginformation.
Ifthecustomerneedstousethepreheatingfunction,wewillbe Set up parameter: Engineer can set up the controller parameter
abletoincreasethepreheatingbutton. from the control panel or through the PC, 6 programmable
Protection: Fan-out may meet the user's every kind of demand.
LowOilPressure Protection: The control system can protect the generator set
HighEngineTemperature manage each kind of electrical failure.
AuxiliaryShutdown ControlFunctionofATS.
Overspeed DC Supply: 8 to 35 V Continuous.
DC Supply: 8 to 35 V Continuous.

3
StandardFeaturesandOptionalAccessories
StandardFeatures ParallelingSystem
Battery, Battery Rack and Battery Cables ReactiveDroopCompensator

Integral Vibration Isolation VoltageAdjustControl

Oil Drain Extension VoltageRegulatorRelocationKit


Air cleaner, Heavy Duty ControllerSystem
3PoleCircuitBreaker CommonFailureRelayKit
Heavy duty industrial type exhaust silencer CustomerConnectionKit(ExceptOpenStyle)
with flexible pipe(supplied loose).
CommunicationsProductsandPCSoftware
MaintenanceandLiterature
EnginePre-alarmSenderKit
GeneralMaintenanceLiteratureKit RemoteAnnunciatorPanel
TestCertificateanddesignpaper
RemoteAudiovisualAlarmPanel
QualitycertificateandMaintenancecard
RemoteEmergencyStopKit
PCRCseriescontrolsystem,withRS232orRS485communication
Accessories connectionandcommunicationagreement.
Enclosed Unit
MiscellaneousAccessories
Sound Enclosure
Weather Enclosure (with enclosed critical silencer)

WeatherHousing(withroof-mountedcriticalsilencer)
Trailer(Causesthegenseteasilytomove)
Open Unit
Exhaust Silencer, Critical Kit
Flexible Exhaust Connector, Stainless Steel DimensionsandWeights
CoolingSystem OpenStyle
Block Heater OverallSize,L W H 2645 730 1630
(recommended for ambient temperatures below 0) )
Weight(radiatormodel),net,Kg 1680
Radiator Duct Flange
Remote Radiator Cooling

Fuel System
Auxiliary Fuel Pump
Flexible Fuel Lines H
Mechanical dipstick or fuel level sensor

BaseFuelTankwithDayTank

Fuelfillcapwithbreather w L
10 hours running tank Soundproof Style
Automatic fuel-providing device L W H mm 3430 1110 2060

Handprimerpump Weight(radiatormodel),net,Kg 2530

ElectricalSystem
Battery Charger, Equalize/Float Type

EngineandAlternator
3or4PoleCircuitBreakerwithShuntTrip

Fuel/Water Separator

Oil Preheater

Air Preheater
NOTE: This drawing is provided for reference only and should not be used for planning.
Anti-Condensation Heater [Link].

MaintenanceandLiterature DISTRIBUTEDBY:
MaintenanceKit(includesair,oil,andfuelfilters)
OverhaulLiteratureKit