UPower Inverter/Charger User Manual
UPower Inverter/Charger User Manual
——Inverter/changer
User Manual
Models:
UP1500-M3222
UP2000-M3322
UP3000-M3322
UP3000-M2142
Please reserve this manual for future review. This manual contains all instructions of safety,
installation and operation for the inverter/charger.
Read carefully all the instructions and warnings in the manual before installation.
Non-safety voltage exists inside the inverter/charger, users must not dismantle it by itself
in order to avoid personal injury, contact professional maintenance personnel of our
company in need of maintenance.
Do not place the inverter/charger in a damp, oily, inflammable and explosive or a severe
environment with a large amount of dust accumulation.
The utility input and AC output are of high voltage, don’t touch wire connecting locations.
Install the inverter/charger in well ventilated places, it’s shell may become very hot
during operation.
Make sure switching off all connections with PV array and the fuse/breakers close to
battery before inverter/charger installation and adjustment.
Power connections must remain tight to avoid excessive heating from a loose
connection.
This inverter/charger can only be used singly, parallel connection or in series will
damage the inverters.
1.1 Overview
The UPower series is a new type of the inverter/charger combining with solar & utility charging
and AC output, which adopts a multi-core processor design and advanced MPPT control
algorithm, and has the features of high response speed, high reliability and high
industrialization standard. It offers four charging modes to Solar priority, Utility priority, Solar
and Utility & Solar; two output modes for Battery and Utility, meeting the various application
demands.
The up-to-date optimized MPPT tracking technology is adopted for the PV charging modules.
It can quickly track the maximum power point of the PV array in any environment and acquire
the maximum energy of solar panel in real time;
The advanced control algorithm is adopted for AC-DC charging modules that realize fully
digitalized double closed-loop control for voltage and current, with high control precision, small
volume. The input range of AC voltage is wide, the output DC charging voltage/current is
continuously adjustable in a certain range, and the complete input/output protection functions
can offer stable and reliable charging and protection to the battery.
The DC-AC inverter modules are based on full digital and intelligent design. It adopts the
advanced SPWM technology, outputs the pure sine wave and converts 24/48VDC to
220/230VAC suitable for AC loads of household appliances, electric tools, commercial units,
electronic audio and video devices etc.
The product adopts 4.2 inch LCD display design, which real-time displays the operational data
and running state of the system. The comprehensive electronic protection function guarantees
more safe and more stable operation of the system.
Features:
Adoption of the advanced SPWM technology, with pure sine wave output
Fully digitalized voltage and current double closed-loop control
Advanced MPPT technology, with efficiency no less than 99.5%.
Four charging mode: Solar priority, Utility priority, Utility & solar and Solar
Two OUTPUT mode: Battery and Utility
LCD design that enables dynamic display of system running data and operating state
Provided with common interface and advanced interface
Multiple LED indicators that instantly indicate the operating state of the system
2P circuit breaker provided at the utility input end
Independent control of AC output with AC OUT button
Battery temperature compensation function.
Extensive Electronic protection
Be very careful when installing the batteries, especially flooded lead-acid battery. Please
wear eye protection, and have fresh water available to wash and clean any contact with
battery acid.
Keep the battery away from any metal objects, which may cause short circuit of the battery.
Explosive battery gases may come out from the battery during charging, so make sure
ventilation condition is good.
Lead-acid battery is recommended, other kinds please refer to the battery manufacturer.
Loose power connections and corroded wires may result in high heat that can melt wire
insulation, burn surrounding materials, or even cause fire. Ensure tight connections and use
cable clamps to secure cables and prevent them from swaying in mobile applications.
Battery connection may be wired to one battery or a bank of batteries. The following
instructions refer to a singular battery, but it is implied that the battery connection can be
made to either one battery or a group of batteries in a battery bank.
Select the system cables according to 5A/mm2 or less current density in accordance with
Article 690 of the National Electrical Code, NFPA 70.
For outdoor installation, keep out of the direct sunshine and rainwater infiltration.
High voltage still exists inside the inverter/charger after switching off the power switch, do
not turn on or touch the internal units, conduct the associated operation only after
discharging the electric capacity.
Do not place the inverter/charger in a damp, oily, inflammable and explosive or a severe
environment with a large amount of dust accumulation.
Prohibit reverse connection at DC input end otherwise it may damage the equipment or
unpredictable danger will occur.
The utility input and AC output are of high voltage, do not touch the wire connecting
locations.
Figure2-1 Mounting
Installation steps:
Warning: Danger, High-voltage! Utility input, AC output and PV array will produce
very high voltage, make sure to disconnect the circuit breaker/ fuse before wiring.
Warning: Do not turn on the circuit breaker/ fuse in course of wiring, and at the
same time, ensure that the wires of “+”, “-” are correctly connected.
Warning: A circuit breaker must be installed at the battery end, for selection, refer
to Section 2.3 "Wire and Circuit Breaker".
Step 4:Grounding
Grounding connection must be made when utility is connected to the inverter/charger. The
inverter/charger has dedicated grounding terminal as shown in Fig. 2-2⑤, the grounding must
be reliable, the grounding wire shall be the thicker wire (wire is not less than 4mm2), the
grounding point shall be as close as possible to the inverter/charger, the grounding wire shall
be the shorter, the better.
Step 5: Install the terminal protective cover
Step 6:Connect accessory
Connect the remote temperature sensor cable (model: RTS300R47K3.81A)
Connect one end of the remote temperature sensor cable to the interface⑦
Operation Instruction
Exit the current interface
Press the button
Clear the faults
Press the button and hold on 5s
Browse interface:Up/Down
Press the / button Setting interface:Up/Down
Switch to "Browse Parameter Column"
Press the button Determine the setting parameters
Switch the" Real Time Interface" over to "Set
Browse Interface"
Press the button and hold on 5s Switch the "Set Browse Interface" over to
"Parameter Setting Interface"
Inverter ON/OFF
Press the button and hold on 5s
Icon:
Icon instruction Icon instruction
10
11
Solar priority
The battery is charged in solar priority mode and when the battery voltage is lower than
“Restore Auxiliary Module Charging Voltage(VAON)”, the utility starts charging. When the
battery voltage reaches to “Stop Auxiliary Module Charging Voltage(VAOF)”, the utility stops
charging.
VBAT<VAON
VBAT<VAOF
Utility priority
The battery is charged in utility priority mode and when the battery voltage is lower than
“Restore Auxiliary Module Charging Voltage (VAON)”, the solar starts charging. When the
battery voltage reaches to “Stop Auxiliary Module Charging Voltage(VAOF)”, the solar stops
charging.
VBAT<VAON
VBAT<VAOF
② OUTPUT
Battery
Utility
12
1) Common interface
Operation:
Step1: Press the button and hold on 5s under the real-time interface.
Step2: Press the button and hold on 5s under the setting parameter interface.
Setting:
Item LCD Instruction Default Range
AGM
GEL
1 BTP Battery type AGM
FLD
USER
Solar priority
Solar
2 CSP Charge source priority Utility priority Utility & solar
priority
Solar
Battery
3 OSP Output source priority Battery
Utility
4 TMU Temperature unit ℃ ℃/℉
5 BLT Backlight time 30S 30S/60S/100S
6 BAS Buzzer alarm switch ON ON/ OFF
★
★ User 21.0~22.6V
7 LVD Low voltage disconnect voltage 21.6V ★
step size 0.2V
★
★ User 24.0~26.0V
8 LVR Low voltage reconnect voltage 25.0V ★
step size 0.2V
★The voltage parameter are referred to 25℃, and twice in 48V system.
NOTE: When Output source priority is Battery and the battery voltage less than the
Low Voltage Disconnect Voltage(LVD adjustable), the system will switch utility to
supply power for load.
13
Step1: Press the + button and hold on 5s under the real-time interface.
Step2: Press the button and hold on 5s under the setting parameter interface.
14
When Switch 1 is in "ON" side, the output voltage is selected as 230VAC, and on the
contrary as 220VAC;
When Switch 2 is in "ON" side, the output frequency is selected as 60Hz, and on the
contrary as 50Hz.
2)Relay interface
Working principle: When the battery voltage reaches the Low Voltage Disconnect Voltage
(LVD), the coil of relay is energized, and the switch is turned on. The dry contact can drive
resistive loads 125VAC /1A, 30VDC/1A.
15
1) Remote interface
NOTE: If it is to change the range of input voltage, it can be realized by changing the
resistance value of R.
16
PV Over Current NOTE: When the PV modules are in series, ensure that the open-circuit voltage of the PV array does not exceed the "maximum PV
open-circuit voltage". Otherwise the inverter/charger may be damaged.
PV short circuit When PV is not charging and short circuit, the inverter/charger is not damaged.
Fully protection against PV reverse polarity, correct the wire connection to resume normal operation.
PV Reverse Polarity NOTE: The inverter/charger will be damaged when the PV array straight polarity and the actual operation power of the
PV array is 1.5 times greater than the rated charge power!
Night Reverse Charging Prevent the battery discharging through the PV module in the night.
Utility input overvoltage When the utility voltage exceeds 280V, it will stop utility charging/discharging.
Utility input under voltage When the utility voltage less than 160V, it will stop utility charging/discharging.
When the battery voltage reaches to the set point of Over Voltage Disconnect Voltage, the inverter/charger will stop charging the
Battery overvoltage battery to protect the battery from being over charged to break down.
When the battery voltage reaches to the set point of Low Voltage Disconnect Voltage, the controller will stop discharging the
Battery Over Discharge battery to protect the battery from being over discharged to break down.
It will immediately close the output in occurrence of short-circuit and hereafter the output is automatically
Load Short Circuit recovered in time delay (the first time delay for 5s, the second time delay for 10s, the third time delay for 15s); if
the short-circuit remains after 3 times of delay, restart the inverter/charger only after clearing the fault.
Overload 105% 131% 160% 183%
Load Overload Continuance 15min. 30S 10S 5S
Recover 3 times The first time delay for 5s, the second time delay for 10s, the third time delay for 15s
The inverter/charger will stop charging/discharging when the internal temperature is too high, and will restore
Device overheating charging/discharging when the temperature is recovered to normal.
17
5.1 Fault
battery
Fault
Module Code Fault frame indicator Buzzer
indicator
blink
BLV Battery over voltage — —
BOV Battery low voltage
Battery BOD Battery over discharge Flashing —
NVE Nominal voltage error
LTP Low temperature
over temperature
PV OTP
charging
(PV charge module) PV charge
Communication Fault Fast Flashing
module CFA Alarm
IOV Input over voltage
Utility ILV Input low voltage
over temperature Utility Alarm On Solid
charging OTP
module (Utility charge module) Fast Flashing
CFA
Communication Fault —
Alarm
OVA Input over voltage
IOS Input low voltage
Inverter Output voltage
output OOL inverter
abnormal
module Fast Flashing
Inverter output short
OTP circuit
CFA Output overload
5.2 Troubleshooting
Fault Troubleshooting
Battery over voltage Check if battery voltage too high, and disconnect solar modules.
Battery over When the battery voltage is restored to or above LVR point (low
discharge voltage reconnect voltage), the AC load will recover
The inverter/charger will automatically turn the system off. But while
Battery overheating the battery temperature declines to be below overheating recover
temperature value, the inverter/charger will working.
The inverter/charger will automatically turn the system off. But while
Device overheating the device temperature declines to be below overheating recover
temperature value, the inverter/charger will working.
①Please reduce the number of electric equipments.
Output overload
②Restart the controller or CFA of setting interface change to ON .
①Check carefully loads connection, clear the fault.
Output short circuit
②Restart the controller CFA of setting interface change to ON ..