UPower Inverter/Charger User Manual

The UPower Series Inverter/Charger User Manual provides essential safety instructions, installation guidelines, and operational details for models UP1500-M3222, UP2000-M3322, UP3000-M3322, and UP3000-M2142. It highlights the importance of proper installation, maintenance, and the use of recommended wiring and circuit breakers to ensure safe operation. The manual also describes the features of the inverter/charger, including advanced MPPT technology, pure sine wave output, and various charging modes.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
115 views28 pages

UPower Inverter/Charger User Manual

The UPower Series Inverter/Charger User Manual provides essential safety instructions, installation guidelines, and operational details for models UP1500-M3222, UP2000-M3322, UP3000-M3322, and UP3000-M2142. It highlights the importance of proper installation, maintenance, and the use of recommended wiring and circuit breakers to ensure safe operation. The manual also describes the features of the inverter/charger, including advanced MPPT technology, pure sine wave output, and various charging modes.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

UPower Series

——Inverter/changer

User Manual

Models:
UP1500-M3222
UP2000-M3322
UP3000-M3322
UP3000-M2142

Downloaded from [Link] manuals search engine


Downloaded from [Link] manuals search engine
Important Safety Instructions

Please reserve this manual for future review.

Please reserve this manual for future review. This manual contains all instructions of safety,
installation and operation for the inverter/charger.

 Read carefully all the instructions and warnings in the manual before installation.

 Non-safety voltage exists inside the inverter/charger, users must not dismantle it by itself
in order to avoid personal injury, contact professional maintenance personnel of our
company in need of maintenance.

 Keep the inverter/charger beyond the reach of children.

 Do not place the inverter/charger in a damp, oily, inflammable and explosive or a severe
environment with a large amount of dust accumulation.

 The utility input and AC output are of high voltage, don’t touch wire connecting locations.

 Install the inverter/charger in well ventilated places, it’s shell may become very hot
during operation.

 It is suggested to install appropriate external fuses/breakers.

 Make sure switching off all connections with PV array and the fuse/breakers close to
battery before inverter/charger installation and adjustment.

 Power connections must remain tight to avoid excessive heating from a loose
connection.

 It’s an off-grid inverter/charger, if connect to the grid, it may be damaged.

 This inverter/charger can only be used singly, parallel connection or in series will
damage the inverters.

Downloaded from [Link] manuals search engine


Downloaded from [Link] manuals search engine
CONTENTS

1. General Information ................................................................................... 1


1.1 Overview ....................................................................................1
1.2 Characteristics ..........................................................................2
1.3 Designations of models ...........................................................3
1.4 Schematic Diagram for Connections .....................................3
2. Installation Instructions ............................................................................ 4
2.1 General Installation Notes .......................................................4
2.2 Wire Size& breaker...................................................................4
2.3 Mounting ....................................................................................6
3. Interface Instruction .................................................................................. 9
3.1 Indicator......................................................................................9
3.2 Buttons .....................................................................................10
3.3 Real-time interface .................................................................10
3.4 Setting interface ......................................................................13
3.5 Other function ..........................................................................15
4. Protection ................................................................................................. 17
5. Troubleshooting ....................................................................................... 18
5.1 Fault ..........................................................................................18
5.2 Troubleshooting ......................................................................18
6. Maintenance ............................................................................................. 19
7. Technical Specifications ......................................................................... 20

Downloaded from [Link] manuals search engine


Downloaded from [Link] manuals search engine
1. General Information

1.1 Overview
The UPower series is a new type of the inverter/charger combining with solar & utility charging
and AC output, which adopts a multi-core processor design and advanced MPPT control
algorithm, and has the features of high response speed, high reliability and high
industrialization standard. It offers four charging modes to Solar priority, Utility priority, Solar
and Utility & Solar; two output modes for Battery and Utility, meeting the various application
demands.

The up-to-date optimized MPPT tracking technology is adopted for the PV charging modules.
It can quickly track the maximum power point of the PV array in any environment and acquire
the maximum energy of solar panel in real time;

The advanced control algorithm is adopted for AC-DC charging modules that realize fully
digitalized double closed-loop control for voltage and current, with high control precision, small
volume. The input range of AC voltage is wide, the output DC charging voltage/current is
continuously adjustable in a certain range, and the complete input/output protection functions
can offer stable and reliable charging and protection to the battery.

The DC-AC inverter modules are based on full digital and intelligent design. It adopts the
advanced SPWM technology, outputs the pure sine wave and converts 24/48VDC to
220/230VAC suitable for AC loads of household appliances, electric tools, commercial units,
electronic audio and video devices etc.

The product adopts 4.2 inch LCD display design, which real-time displays the operational data
and running state of the system. The comprehensive electronic protection function guarantees
more safe and more stable operation of the system.

Features:
 Adoption of the advanced SPWM technology, with pure sine wave output
 Fully digitalized voltage and current double closed-loop control
 Advanced MPPT technology, with efficiency no less than 99.5%.
 Four charging mode: Solar priority, Utility priority, Utility & solar and Solar
 Two OUTPUT mode: Battery and Utility
 LCD design that enables dynamic display of system running data and operating state
 Provided with common interface and advanced interface
 Multiple LED indicators that instantly indicate the operating state of the system
 2P circuit breaker provided at the utility input end
 Independent control of AC output with AC OUT button
 Battery temperature compensation function.
 Extensive Electronic protection

Downloaded from [Link] manuals search engine


1.2 Characteristics

Figure 1 Product appearance



① Mounting Hole ⑦ RTS interface

② Captive screw (2) ⑧ Relay interface

③ AC output terminal ⑨ Remote interface

④ Utility input terminal ⑩ Reserved communication interface

⑤ Ground terminal ⑪ Inverter/charger switch

⑥ Battery input terminal ⑫ PV input terminal

★The temperature sensor short-circuited or damaged, the controller will be charging or


discharging at the default temperature 25 ºC.

Downloaded from [Link] manuals search engine


1.3 Designations of models

1.4 Schematic Diagram for Connections

Warning:Confirm the AC equipment according to the power of the inverter/charger


selected, the maximum power value that exceeds its power, therefore is prohibited.

Downloaded from [Link] manuals search engine


2. Installation Instructions
2.1 General Installation Notes
 Please read the entire installation instructions to get familiar with the installation steps before
installation.

 Be very careful when installing the batteries, especially flooded lead-acid battery. Please
wear eye protection, and have fresh water available to wash and clean any contact with
battery acid.

 Keep the battery away from any metal objects, which may cause short circuit of the battery.

 Explosive battery gases may come out from the battery during charging, so make sure
ventilation condition is good.

 Ventilation is highly recommended if mounted in an enclosure. Never install the controller in


a sealed enclosure with flooded batteries! Battery fumes from vented batteries will corrode
and destroy the controller circuits.

 Lead-acid battery is recommended, other kinds please refer to the battery manufacturer.

 Loose power connections and corroded wires may result in high heat that can melt wire
insulation, burn surrounding materials, or even cause fire. Ensure tight connections and use
cable clamps to secure cables and prevent them from swaying in mobile applications.

 Battery connection may be wired to one battery or a bank of batteries. The following
instructions refer to a singular battery, but it is implied that the battery connection can be
made to either one battery or a group of batteries in a battery bank.
 Select the system cables according to 5A/mm2 or less current density in accordance with
Article 690 of the National Electrical Code, NFPA 70.

 For outdoor installation, keep out of the direct sunshine and rainwater infiltration.

 High voltage still exists inside the inverter/charger after switching off the power switch, do
not turn on or touch the internal units, conduct the associated operation only after
discharging the electric capacity.

 Do not place the inverter/charger in a damp, oily, inflammable and explosive or a severe
environment with a large amount of dust accumulation.

 Prohibit reverse connection at DC input end otherwise it may damage the equipment or
unpredictable danger will occur.

 The utility input and AC output are of high voltage, do not touch the wire connecting
locations.

2.2 Wire Size& breaker


The wiring and installation methods must conform to all national and local electrical code
requirements.

Downloaded from [Link] manuals search engine


 Recommended wire and circuit breaker of PV
Model PV wire size Breaker
UP1500-M3222 10mm2/8AWG 2P—63A
UP2000-M3322 10mm2/8AWG 2P—63A
UP3000-M3322 10mm2/8AWG 2P—63A
UP3000-M2142 6mm2/10AWG 2P—32A
NOTE: When the PV modules connect in series, the open circuit voltage of the PV array must
not exceed 92Vor 138V at 25℃ environment temperature.
 Recommended wire of Utility
Model Utility wire size
UP1500-M3222 2.5mm2/14AWG
UP2000-M3322 4mm2/12AWG
UP3000-M3322 6mm2/10AWG
UP3000-M2142 6mm2/10AWG
NOTE: The utility input has the circuit breaker already and there is no need to add any more.
 Recommended wire and circuit breaker of battery
Model Battery wire size Breaker
UP1500-M3222 16mm2/6AWG 2P—100A
UP2000-M3322 25mm2/4AWG 2P—125A
UP3000-M3322 35mm2/2AWG 2P—200A
UP3000-M2142 16mm2/6AWG 2P—100A
NOTE: Type of circuit breaker is selected based on non-independent connection of inverter at
the battery end.
 Recommended wire and circuit breaker for AC output
Model AC wire size Breaker
UP1500-M3222 2.5mm2/14AWG 2P—10A
UP2000-M3322 2.5mm2/14AWG 2P—16A
UP3000-M3322 4mm2/12AWG 2P—16A
UP3000-M2142 4mm2/12AWG 2P—16A
NOTE: The wire used for connection is for reference only, use thicker wires to lower
the voltage drop and improve the system performance when the distance between
the components is far.
NOTE: The above wire and the circuit breaker are for recommended use only,
please choose the suitable wire and circuit breaker according to the practical
situation.

Downloaded from [Link] manuals search engine


2.3 Mounting

Figure2-1 Mounting

Installation steps:

Step1:Determination of Installation Location and Heat-dissipation Space


Determination of installation location: The inverter/charger shall be installed in a place with
sufficient air flow through the radiators of the controller and a minimum clearance of 150 mm
from the upper and lower edges of the controller to ensure natural thermal convection. Please
see Figure 2-1: Mounting.

WARNING: Risk of explosion!


Never install the controller with flooded batteries in a sealed enclosure! Do not
install the battery in a confined area where battery gas can accumulate.

Step 2:Take down the terminal protective cover

※Screw off the screws and


take down the terminal
protective cover of the
inverter/charger before
wiring.

Downloaded from [Link] manuals search engine


Step 3:Wiring

Figure 2-2 Wring Diagram


Connect the system in an order of battery  load  PV array Utility
in accordance with Figure 2-2: Wiring Diagram and disconnect the system in the
reverse order.

Warning: Danger, High-voltage! Utility input, AC output and PV array will produce
very high voltage, make sure to disconnect the circuit breaker/ fuse before wiring.

Warning: Do not turn on the circuit breaker/ fuse in course of wiring, and at the
same time, ensure that the wires of “+”, “-” are correctly connected.

Warning: A circuit breaker must be installed at the battery end, for selection, refer
to Section 2.3 "Wire and Circuit Breaker".

NOTE: If the inverter/charger is to be used in an area with frequent lightning strikes, it is


recommended to install an external surge arrester.

Step 4:Grounding
Grounding connection must be made when utility is connected to the inverter/charger. The
inverter/charger has dedicated grounding terminal as shown in Fig. 2-2⑤, the grounding must
be reliable, the grounding wire shall be the thicker wire (wire is not less than 4mm2), the
grounding point shall be as close as possible to the inverter/charger, the grounding wire shall
be the shorter, the better.
Step 5: Install the terminal protective cover
Step 6:Connect accessory
 Connect the remote temperature sensor cable (model: RTS300R47K3.81A)
Connect one end of the remote temperature sensor cable to the interface⑦

Downloaded from [Link] manuals search engine


and place the other end close to the battery.
NOTE: The temperature sensor short-circuited or damaged, the inverter/charger will
be charging or discharging at the default temperature 25℃.

Step 7:Recheck if the wire connection is correct


Step 8:Powered on the inverter/charger

①Turn on the circuit breaker at the battery end.


②Switch on the switch then the inverter indicator is on.
③Turn on the breaker of PV array and Utility.
④Turn on the AC load when the AC output is normal.
NOTE: In case the power is supplied to the different AC loads, it is suggested to turn
the loads with larger surge current, wait till the load operation is stable, then turn on
the loads with smaller surge current.
NOTE: In case the inverter/charger is not in normal operation, or LCD or indicator
displays abnormal, refer to Section 5 to clear the fault or contact the after-sale
service personnel of our company.

Downloaded from [Link] manuals search engine


3. Interface Instruction
3.1 Indicator

Indicator Color Status Instruction


OFF No utility
Utility connection normal but no
On Solid charging
Green
Slowly Flashing Utility charging
Fast Flashing Utility charge module fault
OFF No PV
On Solid PV connection normal but no charging
Green
Slowly Flashing PV charging
Fast Flashing PV charge module fault
OFF Inverter turn off
On Solid Inverter turn on
Green
Slowly Flashing Inverter output
Fast Flashing Inverter fault
OFF Load no output
Green
On Solid Load output
OFF Relay turn off
Green
On Solid Relay turn on
OFF Input voltage(3.3~12VDC)
Green
On Solid No Input voltage
OFF Inverter output
Green
On Solid Utility output
OFF Device normal
Red
On Solid Device fault

Downloaded from [Link] manuals search engine


3.2 Buttons

Operation Instruction
Exit the current interface
Press the button
Clear the faults
Press the button and hold on 5s
Browse interface:Up/Down
Press the / button Setting interface:Up/Down
Switch to "Browse Parameter Column"
Press the button Determine the setting parameters
Switch the" Real Time Interface" over to "Set
Browse Interface"
Press the button and hold on 5s Switch the "Set Browse Interface" over to
"Parameter Setting Interface"
Inverter ON/OFF
Press the button and hold on 5s

3.3 Real-time interface

Icon:
Icon instruction Icon instruction

Utility connecting PV connecting

Utility no connecting PV no connecting

Load ON Load OFF

10

Downloaded from [Link] manuals search engine


Battery capacity level Battery capacity level
8~25% 25~50%

Battery capacity level Battery capacity level


50~75% 75~100%

Item Setting Content


Solar priority
Utility priority
① INPUT
Utility & solar
Solar
Battery
② OUTPUT
Utility
AC output voltage
AC output current
③ Load
AC output power
AC output frequency
Battery voltage
Max. charging current
④ Battery (PV charging current+ Utility charging current)
Battery temperature
Battery SOC
PV input voltage
PV charging current
PV
PV charging power
PV charge energy
⑤ Utility input voltage
Utility charging current
Utility
Utility charging power
Utility charge energy
AGW
GEL
⑥ Battery Type
FLD
USER

11

Downloaded from [Link] manuals search engine


① INPUT

 Solar priority
The battery is charged in solar priority mode and when the battery voltage is lower than
“Restore Auxiliary Module Charging Voltage(VAON)”, the utility starts charging. When the
battery voltage reaches to “Stop Auxiliary Module Charging Voltage(VAOF)”, the utility stops
charging.

VBAT<VAON

VBAT<VAOF

 Utility priority
The battery is charged in utility priority mode and when the battery voltage is lower than
“Restore Auxiliary Module Charging Voltage (VAON)”, the solar starts charging. When the
battery voltage reaches to “Stop Auxiliary Module Charging Voltage(VAOF)”, the solar stops
charging.

VBAT<VAON

VBAT<VAOF

② OUTPUT

 Battery

 Utility

12

Downloaded from [Link] manuals search engine


3.4 Setting interface

1) Common interface
Operation:

Step1: Press the button and hold on 5s under the real-time interface.

Step2: Press the button and hold on 5s under the setting parameter interface.

Step3: Press the button to enter the parameter.

Step4: Press the button to exit the setting interface.

Setting:
Item LCD Instruction Default Range
AGM
GEL
1 BTP Battery type AGM
FLD
USER
Solar priority
Solar
2 CSP Charge source priority Utility priority Utility & solar
priority
Solar
Battery
3 OSP Output source priority Battery
Utility
4 TMU Temperature unit ℃ ℃/℉
5 BLT Backlight time 30S 30S/60S/100S
6 BAS Buzzer alarm switch ON ON/ OFF

★ User 21.0~22.6V
7 LVD Low voltage disconnect voltage 21.6V ★
step size 0.2V

★ User 24.0~26.0V
8 LVR Low voltage reconnect voltage 25.0V ★
step size 0.2V
★The voltage parameter are referred to 25℃, and twice in 48V system.
NOTE: When Output source priority is Battery and the battery voltage less than the
Low Voltage Disconnect Voltage(LVD adjustable), the system will switch utility to
supply power for load.

13

Downloaded from [Link] manuals search engine


2) Advanced interface
Operation:

Step1: Press the + button and hold on 5s under the real-time interface.

Step2: Press the button and hold on 5s under the setting parameter interface.

Step3: Press the button to enter the parameter.

Step4: Press the button to exit the setting interface.


Setting:
Item LCD Instruction Default Range
9 BCT Boost Charging Time 30M 30M/60M/120M/180M

AGM:28.8V
★ ★
GEL:28.4V User 25.0~29.6V
10 BCV Boost Charging Voltage ★ ★
FLD:29.2V Step size 0.2V

USER:28.8V

★ User: 25.0~28.0V
11 BVR Boost Voltage Reconnect 26.4V ★
Step size 0.2V

★ User: 26.0~28.0V
12 FCV Float Charging Voltage 27.6V ★
Step size 0.2V

★ User: 29.0~31.0V
13 OVR Over Voltage Reconnect Voltage 30.0V ★
Step size 0.2V

★ User: 31.0~32.2V
14 OVD Over Voltage Disconnect Voltage 32.0V ★
Step size 0.2V
Stop auxiliary module charging ★
15 AOF voltage 28.0V ★
User: 24.0~29.6V

Restore auxiliary module charging ★
Step size 0.2V
16 AON voltage 24.0V

★ User: 21.6~24.0V
17 DON Day connect ON voltage 22.2V ★
Step size 0.2V

★ User: 24.0~26.5V
18 DOF Day connect OFF voltage 24.0V ★
Step size 0.2V
◆ ◆
19 MCC Max. charging current 60.0A 15.0~60.0A
20 PSM Power saving mode OFF ON/OFF
21 CFA Clear fault OFF ON/OFF
22 QCL Clear the accumulated energy OFF ON/OFF
23 VER Software version U-1.0 —
★The voltage parameter are referred to 25℃, and twice in 48V system.
◆For the inverter/charger of different power, the current setting range is not the same,
see Table of Technical Parameters for details.

14

Downloaded from [Link] manuals search engine


NOTE:
15/16:Stop/restore auxiliary module charging voltage
Only when the charging mode is Solar priority or Utility priority will the auxiliary module
charging voltage be effective.
20:Power saving mode
When the power saving mode switch is in ON state, and when the load is less than 40W, the
cycles of AC output for 5s, and no-output for 10s are excuted.

21:Clear the faults


In occurrence of short circuit or overload caused to AC output, the fault can be cleared out.

3.5 Other function


1) Output voltage & frequency switch

 When Switch 1 is in "ON" side, the output voltage is selected as 230VAC, and on the
contrary as 220VAC;
 When Switch 2 is in "ON" side, the output frequency is selected as 60Hz, and on the
contrary as 50Hz.

NOTE:If the output frequency or voltage of the inverter/charger is to be reset, it is


required to turn off the inverter/charger and start up the unit after setting.

2)Relay interface
Working principle: When the battery voltage reaches the Low Voltage Disconnect Voltage
(LVD), the coil of relay is energized, and the switch is turned on. The dry contact can drive
resistive loads 125VAC /1A, 30VDC/1A.

15

Downloaded from [Link] manuals search engine


NOTE: When the utility input is abnormal, this dry contact can control the oil engine
switch to charge the battery.

1) Remote interface

2) Remote interface input voltage( 3.3~ 12V )


(1)The input voltage Vi is within 2.5~ 10s, the AC output state is reversed (when the AC is
formerly in output state, now it is in no-output state ; when the AC is formerly in no-output state,
now it is in output state;)
(2) The input voltage Vi is greater than 10s, the AC is in output state all the time till the input
voltage Vi disappears.

NOTE: If it is to change the range of input voltage, it can be realized by changing the
resistance value of R.

16

Downloaded from [Link] manuals search engine


4. Protection
Protection Instruction
When the charging current of the PV array exceeds its rated current, it will be charged at the rated current.

PV Over Current NOTE: When the PV modules are in series, ensure that the open-circuit voltage of the PV array does not exceed the "maximum PV
open-circuit voltage". Otherwise the inverter/charger may be damaged.

PV short circuit When PV is not charging and short circuit, the inverter/charger is not damaged.
Fully protection against PV reverse polarity, correct the wire connection to resume normal operation.
PV Reverse Polarity NOTE: The inverter/charger will be damaged when the PV array straight polarity and the actual operation power of the
PV array is 1.5 times greater than the rated charge power!
Night Reverse Charging Prevent the battery discharging through the PV module in the night.
Utility input overvoltage When the utility voltage exceeds 280V, it will stop utility charging/discharging.
Utility input under voltage When the utility voltage less than 160V, it will stop utility charging/discharging.
When the battery voltage reaches to the set point of Over Voltage Disconnect Voltage, the inverter/charger will stop charging the
Battery overvoltage battery to protect the battery from being over charged to break down.
When the battery voltage reaches to the set point of Low Voltage Disconnect Voltage, the controller will stop discharging the
Battery Over Discharge battery to protect the battery from being over discharged to break down.
It will immediately close the output in occurrence of short-circuit and hereafter the output is automatically
Load Short Circuit recovered in time delay (the first time delay for 5s, the second time delay for 10s, the third time delay for 15s); if
the short-circuit remains after 3 times of delay, restart the inverter/charger only after clearing the fault.
Overload 105% 131% 160% 183%
Load Overload Continuance 15min. 30S 10S 5S
Recover 3 times The first time delay for 5s, the second time delay for 10s, the third time delay for 15s
The inverter/charger will stop charging/discharging when the internal temperature is too high, and will restore
Device overheating charging/discharging when the temperature is recovered to normal.

17

Downloaded from [Link] manuals search engine


5. Troubleshooting

5.1 Fault
battery
Fault
Module Code Fault frame indicator Buzzer
indicator
blink
BLV Battery over voltage — —
BOV Battery low voltage
Battery BOD Battery over discharge Flashing —
NVE Nominal voltage error
LTP Low temperature
over temperature
PV OTP
charging
(PV charge module) PV charge
Communication Fault Fast Flashing
module CFA Alarm
IOV Input over voltage
Utility ILV Input low voltage
over temperature Utility Alarm On Solid
charging OTP
module (Utility charge module) Fast Flashing
CFA
Communication Fault —
Alarm
OVA Input over voltage
IOS Input low voltage
Inverter Output voltage
output OOL inverter
abnormal
module Fast Flashing
Inverter output short
OTP circuit
CFA Output overload

5.2 Troubleshooting
Fault Troubleshooting
Battery over voltage Check if battery voltage too high, and disconnect solar modules.
Battery over When the battery voltage is restored to or above LVR point (low
discharge voltage reconnect voltage), the AC load will recover
The inverter/charger will automatically turn the system off. But while
Battery overheating the battery temperature declines to be below overheating recover
temperature value, the inverter/charger will working.
The inverter/charger will automatically turn the system off. But while
Device overheating the device temperature declines to be below overheating recover
temperature value, the inverter/charger will working.
①Please reduce the number of electric equipments.
Output overload
②Restart the controller or CFA of setting interface change to ON .
①Check carefully loads connection, clear the fault.
Output short circuit
②Restart the controller CFA of setting interface change to ON ..

Downloaded from [Link] manuals search engine


6. Maintenance
1)The following inspections and maintenance tasks are recommended at least two
times per year for best performance.
 Make sure inverter/charger firmly installed in a clean and dry ambient.
 Make sure no block on air-flow around the inverter/charger. Clear up any dirt and fragments
on radiator.
 Check all the naked wires to make sure insulation is not damaged for serious solarization,
frictional wear, dryness, insects or rats etc. Repair or replace some wires if necessary.
 Tighten all the terminals. Inspect for loose, broken, or burnt wire connections.
 Check and confirm that LED is consistent with required. Pay attention to any troubleshooting
or error indication .Take corrective action if necessary.
 Confirm that all the system components are ground connected tightly and correctly.
 Confirm that all the terminals have no corrosion, insulation damaged, high temperature or
burnt/discolored sign, tighten terminal screws to the suggested torque.
 Check for dirt, nesting insects and corrosion. If so, clear up in time.
 Check and confirm that lightning arrester is in good condition. Replace a new one in time to
avoid damaging of the inverter/charger and even other equipments.

WARNING:Risk of electric shock!


Make sure that all the power is turned off before above operations, and then
follow the corresponding inspections and operations.

2)This warranty does not apply under the following conditions:

 Damage from improper use or use in an unsuitable environment.


 PV or load current, voltage or power exceeding the rated value of controller.
 The inverter/charger is working temperature exceed the limit working environment
temperature.
 User disassembly or attempted repair the inverter/charger without permission.
 The inverter/charger is damaged due to natural elements such as lighting.
 The inverter/charger is damaged during transportation and shipment.

Downloaded from [Link] manuals search engine


7. Technical Specifications
Item UP1500-M3222 UP2000-M3322 UP3000-M3322 UP3000-M2142
System battery
24VDC 48VDC
voltage
Battery input voltage
21.6~31.9VDC 43.2~63.9VDC
range
Inverter output
Output rated power 1200W 1600W 2400W 2400W
Output power (15min.) 1500W 2000W 3000W 3000W
Overload power(5s) 2400W 3200W 4800W 4800W
Max. surge power 3000W 4000W 6000W 6000W
Output voltage
220VAC±3%
range
Output frequency 50HZ/60HZ
Output wave Pure Sine Wave
Power factor 0.8
Distortion THD ≤3%(24V or 48V resistive load)
Inverter efficiency ≤95%
Utility input
Utility input voltage
170VAC~275VAC
range
Utility charge current 20A 30A 30A 15A
Transfer time 20mS
Solar charging
★ ★
Max. PV open circuit 100V 150V
◆ ◆
voltage 92V 138V
Max. PV input power 780W 780W 780W 1040W
PV charging current 30A 30A 30A 20A
Equalization voltage 29.2V 58.4V
Boost voltage 28.8V 57.6V
Float voltage 27.6V 55.2V
Tracking efficiency ≤99.5%
Charging conversion
≤98%
efficiency
Temperature
compensate -3mV/℃/2V (Default)
coefficient
Others
Self-consumption ≤0.6A ≤0.8A ≤0.8A ≤0.6A
Enclosure IP30
Relative humidity < 95%(N.C.)
Working
environment -20℃~50℃(100% input and output)
temperature
Mechanical Parameters
Dimension 386×300×126mm 444×300×126mm
Mounting dimension 230mm
Mounting hole size Φ8mm
Weight 7kg 8.5kg 9kg 9kg
★At minimum operating environment temperature
◆At 25℃ environment temperature

Any changes without prior notice! Version number: V1.0