Calculation For Exit PDF

The document outlines the calculations for determining exit widths in various building scenarios according to specific by-laws. It includes step-by-step processes for calculating occupancy loads, unit capacities, and exit widths for different purpose groups such as offices, hotels, and restaurants. The calculations are based on floor areas and occupancy factors, ensuring compliance with safety regulations.

Uploaded by

Grimoireweisee
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
209 views29 pages

Calculation For Exit PDF

The document outlines the calculations for determining exit widths in various building scenarios according to specific by-laws. It includes step-by-step processes for calculating occupancy loads, unit capacities, and exit widths for different purpose groups such as offices, hotels, and restaurants. The calculations are based on floor areas and occupancy factors, ensuring compliance with safety regulations.

Uploaded by

Grimoireweisee
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

“MASA ITU

PEDANG,
JIKA TUAN
TIDAK
MEMOTONG,
MAKA TUAN
AKAN
DIPOTONG”
BOMBA CALCULATION DAY
CALCULATION FOR EXIT
STEP 1 : DETERMINE PURPOSE GROUP
STEP 2 : DETERMINE FLOOR AREA
STEP 3 : CALCULATE OCCUPANCY LOAD
STEP 4 : CALCULATE UNIT CAPACITY EXIT
STEP 5 : CALCULATE EXIT WITDH
CALCULATION FOR EXIT
STEP 1 : DETERMINE PURPOSE GROUP : By-Law 134
PG IV : PEJABAT

STEP 2 : DETERMINE FLOOR AREA : By-Law 176(a)


LUAS KASAR (GROSS FLOOR AREA)

STEP 3 : CALCULATE OCCUPANCY LOAD : By-Law 176(b)(c)


LUAS / OCCUPANCY LOAD FACTOR (Jadual 7)

STEP 4 : CALCULATE UNIT CAPACITY EXIT : 7th Schedule


OCCUPANCY LOAD / CAPACITY EXIT (Jadual 7)

STEP 5 : CALCULATE EXIT WITDH : By-Law 181


UNIT X 550mm (UNIT LEBAR TEMPAT KELUAR)
CALCULATION FOR EXIT
STEP 1 : DETERMINE PURPOSE GROUP : By-Law 134
PEJABAT
STEP 2 : DETERMINE FLOOR AREA : By-Law 176(a)
1000 m2
STEP 3 : CALCULATE OCCUPANCY LOAD : By-Law 176(b)(c)
1000/10 = 100 OL
STEP 4 : CALCULATE UNIT CAPACITY EXIT (STAIR) 7th Schedule
100/60 = 1.67 unit
STEP 5 : CALCULATE EXIT WITDH : By-Law 181
2 X 550 = 1100mm
CALCULATION FOR EXIT
STEP 1 : DETERMINE PURPOSE GROUP : By-Law 134
PEJABAT
STEP 2 : DETERMINE FLOOR AREA : By-Law 176(a)
1500 m2
STEP 3 : CALCULATE OCCUPANCY LOAD : By-Law 176(b)(c)
1500/10 = 150 OL
STEP 4 : CALCULATE UNIT CAPACITY EXIT (STAIR) 7th Schedule
150/60 = 2.5 unit
STEP 5 : CALCULATE EXIT WITDH : By-Law 181
3 X 550 = 1650mm
CALCULATION FOR EXIT
STEP 1 : DETERMINE PURPOSE GROUP : By-Law 134
PEJABAT
STEP 2 : DETERMINE FLOOR AREA : By-Law 176(a)
1990 m2
STEP 3 : CALCULATE OCCUPANCY LOAD : By-Law 176(b)(c)
1990/10 = 199 OL
STEP 4 : CALCULATE UNIT CAPACITY EXIT (STAIR) : 7th Schedule
199/60 = 3.32 unit
STEP 5 : CALCULATE EXIT WITDH : By-Law 181
3 X 550 = 1650mm + 300mm = 1950mm
CALCULATION FOR EXIT
STEP 1 : DETERMINE PURPOSE GROUP : By-Law 134
PEJABAT
STEP 2 : DETERMINE FLOOR AREA : By-Law 176(a)
2500 m2
STEP 3 : CALCULATE OCCUPANCY LOAD : By-Law 176(b)(c)
2500/10 = 250 OL
STEP 4 : CALCULATE UNIT CAPACITY EXIT (STAIR) : 7th Schedule
250/60 = 4.17 unit
STEP 5 : CALCULATE EXIT WITDH : By-Law 181
4 X 550 = 2200 + 300 = 2500mm
CALCULATION FOR EXIT
STEP 1 : DETERMINE PURPOSE GROUP : By-Law 134
PEJABAT
STEP 2 : DETERMINE FLOOR AREA : By-Law 176(a)
3650 m2
STEP 3 : CALCULATE OCCUPANCY LOAD : By-Law 176(b)(c)
3650/10 = 365 OL
STEP 4 : CALCULATE UNIT CAPACITY EXIT (STAIR) : 7th Schedule
365/60 = 6.09 unit
STEP 5 : CALCULATE EXIT WITDH : By-Law 181
6 X 550 = 3300 + 300 = 3600mm
CALCULATION FOR EXIT
STEP 1 : DETERMINE PURPOSE GROUP : By-Law 134
PEJABAT
STEP 2 : DETERMINE FLOOR AREA : By-Law 176(a)
8958 m2
STEP 3 : CALCULATE OCCUPANCY LOAD : By-Law 176(b)(c)
8958/10 = 896 OL
STEP 4 : CALCULATE UNIT CAPACITY EXIT (STAIR) : 7th Schedule
896/60 = 14.93 unit
STEP 5 : CALCULATE EXIT WITDH : By-Law 181
15 X 550 = 8250mm
CALCULATION FOR EXIT
STEP 1 : DETERMINE PURPOSE GROUP : By-Law 134
HOTEL
STEP 2 : DETERMINE NUMBER OF ROOM/FLOOR
40 ROOMS
STEP 3 : CALCULATE OCCUPANCY LOAD : By-Law 176(b)(c)
40 X 2 pax = 80 OL
STEP 4 : CALCULATE UNIT CAPACITY EXIT (STAIR) 7th Schedule
80/45 = 1.78 unit (say 2 unit)
STEP 5 : CALCULATE EXIT WITDH : By-Law 181
2 X 550 = 1100mm
CALCULATION FOR EXIT
STEP 1 : DETERMINE PURPOSE GROUP : By-Law 134
HOTEL
STEP 2 : DETERMINE NUMBER OF ROOM/FLOOR
326 ROOMS
STEP 3 : CALCULATE OCCUPANCY LOAD : By-Law 176(b)(c)
326 X 2 pax = 652 OL
STEP 4 : CALCULATE UNIT CAPACITY EXIT (STAIR) 7th Schedule
652/45 = 14.48 unit (say 14 unit)
STEP 5 : CALCULATE EXIT WITDH : By-Law 181
14 X 550 = 7700mm + 300mm = 8000mm
CALCULATION FOR EXIT
STEP 1 : DETERMINE PURPOSE GROUP : By-Law 134
RUMAH PANGSA
STEP 2 : DETERMINE FLOOR AREA
1900m2
STEP 3 : CALCULATE OCCUPANCY LOAD : By-Law 176(b)(c)
1900/24 pax = 79.2 OL
STEP 4 : CALCULATE UNIT CAPACITY EXIT (STAIR) 7th Schedule
80/45 = 1.78 unit (say 2 unit)
STEP 5 : CALCULATE EXIT WITDH : By-Law 181
2 X 550 = 1100mm
CALCULATION FOR EXIT
STEP 1 : DETERMINE PURPOSE GROUP : By-Law 134
RESTAURANT
STEP 2 : DETERMINE FLOOR AREA
1500m2 gross
700m2 nett
STEP 3 : CALCULATE OCCUPANCY LOAD : By-Law 176(b)(c)
700/1.35 pax = 518.5 OL
STEP 4 : CALCULATE UNIT CAPACITY EXIT (STAIR) 7th Schedule
518.5/75 = 6.91 unit (say 7 unit)
STEP 5 : CALCULATE EXIT WITDH : By-Law 181
7 X 550 = 3850mm
CALCULATION FOR EXIT
STEP 1 : DETERMINE PURPOSE GROUP : By-Law 134
PEJABAT
STEP 2 : DETERMINE FLOOR AREA : By-Law 176(a)
1000 m2
STEP 3 : CALCULATE OCCUPANCY LOAD : By-Law 176(b)(c)
1000/10 = 100 OL
STEP 4 : CALCULATE UNIT CAPACITY EXIT (STAIR) 7th Schedule
100/60 = 1.67 unit
STEP 5 : CALCULATE EXIT WITDH : By-Law 181
2 X 550 = 1100mm

1100mm (MINIMUM WIDTH REQUIRED)


= Proposed 2 stair
Used 2-1 formula
1100/2-1 = 1100 for 1 stair
CALCULATION FOR EXIT
STEP 1 : DETERMINE PURPOSE GROUP : By-Law 134
PEJABAT
STEP 2 : DETERMINE FLOOR AREA : By-Law 176(a)
1500 m2
STEP 3 : CALCULATE OCCUPANCY LOAD : By-Law 176(b)(c)
1500/10 = 150 OL
STEP 4 : CALCULATE UNIT CAPACITY EXIT (STAIR) 7th Schedule
150/60 = 2.5 unit
STEP 5 : CALCULATE EXIT WITDH : By-Law 181
3 X 550 = 1650mm

1650mm (MINIMUM WIDTH REQUIRED)


= Proposed 3 stair
Used -1 formula
1650/3-1 = 825 for 1 stair
Therefore 1 stair = 1100mm (2 exit unit)
CALCULATION FOR EXIT
STEP 1 : DETERMINE PURPOSE GROUP : By-Law 134
PEJABAT
STEP 2 : DETERMINE FLOOR AREA : By-Law 176(a)
8958 m2
STEP 3 : CALCULATE OCCUPANCY LOAD : By-Law 176(b)(c)
8958/10 = 896 OL
STEP 4 : CALCULATE UNIT CAPACITY EXIT (STAIR) : 7th Schedule
896/60 = 14.93 unit
STEP 5 : CALCULATE EXIT WITDH : By-Law 181
15 X 550 = 8250mm

8250mm (MINIMUM WIDTH REQUIRED)


= Proposed 4 stair
Used -1 formula
8250/4-1 = 2750mm for 1 stair
CALCULATION FOR EXIT
STEP 1 : DETERMINE PURPOSE GROUP : By-Law 134
HOTEL
STEP 2 : DETERMINE NUMBER OF ROOM/FLOOR
40 ROOMS
STEP 3 : CALCULATE OCCUPANCY LOAD : By-Law 176(b)(c)
40 X 2 pax = 80 OL
STEP 4 : CALCULATE UNIT CAPACITY EXIT (STAIR) 7th Schedule
80/45 = 1.78 unit (say 2 unit)
STEP 5 : CALCULATE EXIT WITDH : By-Law 181
2 X 550 = 1100mm

1100mm (MINIMUM WIDTH REQUIRED)


= Proposed 2 stair
Used 2-1 formula
1100/2-1 = 1100 for 1 stair
CALCULATION FOR EXIT
STEP 1 : DETERMINE PURPOSE GROUP : By-Law 134
HOTEL
STEP 2 : DETERMINE NUMBER OF ROOM/FLOOR
326 ROOMS
STEP 3 : CALCULATE OCCUPANCY LOAD : By-Law 176(b)(c)
326 X 2 pax = 652 OL
STEP 4 : CALCULATE UNIT CAPACITY EXIT (STAIR) 7th Schedule
652/45 = 14.48 unit (say 14 unit)
STEP 5 : CALCULATE EXIT WITDH : By-Law 181
14 X 550 = 7700mm + 300mm = 8000mm

8000mm (MINIMUM WIDTH REQUIRED)


= Proposed 6 stair
Used -1 formula
8000/6-1 = 1600mm for 1 stair
CALCULATION FOR EXIT
STEP 1 : DETERMINE PURPOSE GROUP : By-Law 134
RESTAURANT
STEP 2 : DETERMINE FLOOR AREA
1500m2 gross
700m2 nett
STEP 3 : CALCULATE OCCUPANCY LOAD : By-Law 176(b)(c)
700/1.35 pax = 518.5 OL
STEP 4 : CALCULATE UNIT CAPACITY EXIT (STAIR) 7th Schedule
518.5/75 = 6.91 unit (say 7 unit)
STEP 5 : CALCULATE EXIT WITDH : By-Law 181
7 X 550 = 3850mm

3850mm (MINIMUM WIDTH REQUIRED)


= Proposed 4 stair
Used -1 formula
3850/4-1 = 1284mm for 1 stair
CALCULATION FOR EXIT
Scenario: Upper floor exhibition area in an Institutional Building
Calculate Stair A, Stair B and Lobby C minimum width
Occupant Load
(UBBL 180(b)) = 1.35m2 / pax
Stair 1000m2 / 1.35m2 = 741 persons Stair
A 50 m B

In case of fire 1nos of exit inaccessible,


Therefore 2 other exit must accommodate total occupancy
741 / 2 exit = 371 person / exit

PG VII person per unit for stair = 75


371 pax / 75 = 4.95, say 5 20 m
5 x 0.55m = 2.75 m width each stair

C = horizontal exit, person per unit for stair = 100


371 pax / 100 = 3.71, say 4
4 x 0.55m = 2.20 m width for lobby C

Lobby C
CALCULATION FOR EXIT
Scenario: Upper floor exhibition area in an Institutional Building
Calculate minimum exit width for Door D and Stair B

Stair Stair
A 15 m 35 m B
Door
D

20 m

Door
E

Lobby C
Answer : Assume Lobby C is inaccessible, either B or D must accommodate

Occupant Load
(UBBL 180(b)) = 1.35m2 / pax
700m2 / 1.35m2 = 519 persons
Stair 519 pax / 2 exits = 260 persons
Stair
A 15 m 35 m B
Door Stair B = 75 pax per unit
D
260 pax / 75 = 3.47, say 3
3.0 x 0.55m = 1.65 + 0.3 = 1.95m width
222 persons
Door D (Horizontal exit) =100 pax per unit 20 m
260 pax / 100 = 2.6, say 3
3.0 x 0.55m = 1.65m width

Door
E

Lobby C
Question : Assume Stair A is inaccessible, Calculate width of Door E

Occupant Load
(UBBL 180(b)) = 1.35m2 / pax
300m2 / 1.35m2 = 222 persons
Stair 222 pax / 2 exits = 111 persons
Stair
A 15 m 35 m B
Door Stair B = 75 pax per unit
D
260 pax / 75 = 3.47, say 3
3.0 x 0.55m = 1.65 + 0.3 = 1.95m width
222 persons
Door E (Horizontal exit) =100 pax per unit 20 m
111 pax / 10 = 1.11, say 1
1.0 x 0.55m0 = 0.55 + 0.3 = 0.850mm width
*ByLaw 177(e) minimum exit width 2 unit,
Door minimum Door E width 1100mm
E

Lobby C
CALCULATION FOR EXIT
STEP 1 : DETERMINE PURPOSE GROUP - By-Law 134
KEDAI
STEP 2 : DETERMINE FLOOR AREA - By-Law 176(a)
4000 m2
STEP 3 : CALCULATE OCCUPANCY LOAD - By-Law 176(c)
4000/6 = 365 OL
STEP 4 : CALCULATE UNIT CAPACITY EXIT (STAIR) – 7th Schedule
666.66/60 = 11.1111 unit
STEP 5 : CALCULATE EXIT WITDH - By-Law 181
11 X 550 = 6050mm + 300mm = 6350mm

6350 (MINIMUM WIDTH REQUIRED)


= Proposed 4 stair
Used -1 formula
6350mm/4-1 = 2117mm for 1 stair
CALCULATION for exit door width at UPPER LEVEL
STEP 1 : DETERMINE PURPOSE GROUP - By-Law 134
KEDAI
STEP 2 : DETERMINE FLOOR AREA - By-Law 176(a)
4000 m2
STEP 3 : CALCULATE OCCUPANCY LOAD - By-Law 176(c)
4000/6 = 365 OL
STEP 4 : CALCULATE UNIT CAPACITY EXIT (DOOR) – 7th Schedule
666.66/100 = 6.66 unit
STEP 5 : CALCULATE EXIT WITDH - By-Law 181
7 X 550 = 3850mm

3850mm (MINIMUM WIDTH REQUIRED)


= Proposed 4 Door
Used -1 formula
3850mm/4-1 = 1284mm for 1 door
*By-Law 163 : fire door minimum 900x2100 or 1800x2100
Use double door 1800
CALCULATION exit width for Main Door at STREET LEVEL

STEP 1 : DETERMINE PURPOSE GROUP - By-Law 134


KEDAI
STEP 2 : DETERMINE FLOOR AREA - By-Law 176(a)
4000 m2
STEP 3 : CALCULATE OCCUPANCY LOAD - By-Law 176(c)
4000/3 = 1333.33 OL
STEP 4 : CALCULATE UNIT CAPACITY EXIT (DOOR) – 7th Schedule
133.33/100 = 13.33 unit
STEP 5 : CALCULATE EXIT WITDH - By-Law 181
13 X 550 = 7150mm + 300mm = 7450mm
*Main exit must be 50% of total exit width : 7.45m X 50% = 3.725m
Nos main door provided : 2 numbers
Exit width per door : 1863mm

Exit provision from upper to street level :-


Exit staircase provided : 4 doors @ 1284mm
Exit door at Street Level provided : 2 doors @ 1863mm
Thank You