pH / ORP / ISE Process Control Systems Application Spotlight
Product Focus # 1 – Cost Effective pH & ORP-(Rev July 2008) Page 1 of 2
Advanced Sensor Technologies, Inc.
Superior pH / ORP / ISE Industrial Sensors Orange, California USA
Features Product Focus No. 1 – Cost Effective pH & ORP Measurement
Guaranteed Longest Lasting
Sensors Available with
performance guarantee *
Sensors are compatible with most
existing pH/ORP Meters,
Transmitters & Analyzers **
Application Specific Engineering
results in optimum Lifetime &
Performance ***
Integrated Temperature Cost-effective pH & ORP sensors can retrofit to your existing Transmitter
Compensation, Preamplifiers & Solid-state conductive polymer reference system reduces cleaning requirements,
Solution Ground Elements allows for aggressive chemical & mechanical cleaning to elongate sensor life
Proven in heavy industry slurries, thick-wall pH glass elements are nearly
impossible to break during normal process operation, cleaning and calibration
Solid State Reference System Flat pH Elements offer excellent “self-cleaning” operation for slurries
offers superior resistance to Chemically & thermally resistant RYTON® thermoplastic sensor body housing
Fouling & Dehydration and High Density Poly-Ethylene (HDPE) reference junction matrix
Support for embedded temperature compensation elements, stainless steel
Applications such as solution grounds (liquid earth), and conventional & differential preamplifiers
Acid/Fluoride, Hi-Temp, Saturated allows for connection to almost any existing pH/ORP transmitter or controller
Sodium and Sulfide Resistant are
available as standard options Cost-effective 4-Wire 4TX and 2-Wire 2TX pH & ORP Transmitters
True 2-wire 2TX meter simplifies installation and reduces power requirements
2TX & 4TX support external preamplifiers for installation up to 500 feet away
Custom Applications are available, Excellent input impedance support (> 1013 ) for sensors without preamplifiers
often at no additional charge ¼ DIN pH/ORP Transmitter & Controller in Watertight IP65 Case
Four (4) each Programmable 5 Amp Relays & One (1) each 5 Amp Wash Relay
Most Installation Styles are Automatic & Manual Temperature Compensation from -10 to +120 Celsius with
Supported Including: 3K Balco or 100 & 1000 Ohm Platinum TC Elements
Immersion, Twist Lock, RS 485 Digital Output, 4-digit security password
Valve Retractable & Sanitary Fully Isolated, Reversible & Programmable single 4-20 mA output for pH or
ORP signal with linear or proportional output
Available in a wide range of
plastics, from inexpensive PVC &
CPVC to thermally & chemically
resilient RYTON® thermoplastic
High Pressure Applications up to
100 psi for Valve Retractable &
150 psi for Inline Installations can
be supported for continuous use
Operating Temperatures from
-
30 to +150 ºC (-22 to +302 ºF) can
be supported for continuous use
pH / ORP / ISE Process Control Systems Application Spotlight
Product Focus #1 – Cost Effective pH & ORP Page 2 of 2
Advanced Sensor Technologies
Superior pH / ORP / ISE Industrial Sensors Orange, California USA
Features Low Cost pH Sensor WITHOUT preamplifier for 4TX or 2TX meters
Guaranteed Longest Lasting Model: PNZ 2012-1000-15 Low Cost General Purpose pH Sensor
Sensors Available with Description: ¾”- ¾” MNPT Immersion CPVC Bodied Low Cost pH Sensor with thick-wall
performance guarantee * break resistant Low Impedance Fast Response 9 millimeter MUGG pH glass and solid-state
conductive polymer double junction HDPE reference; Integrated 1000 Ohm Platinum
Temperature Compensator; 15 feet of cable to connect directly to 4TX & 2TX pH Transmitters
Sensors are compatible with most
existing pH/ORP Meters, Rugged pH Sensor WITH preamplifier for 4TX or 2TX meters
Transmitters & Analyzers ** Model: PN 6952-4TX-100 Rugged Saturated Sodium Purpose pH Sensor
Description: ¾”- 1” MNPT Immersion RYTON Bodied Saturated Sodium Resistant pH Sensor
Application Specific Engineering with thick-wall break resistant CH-III pH glass & solid-state conductive polymer double junction
results in optimum Lifetime & HDPE reference; Integrated 1000 Ohm Platinum Temperature Compensator & 6311 compatible
Performance *** preamplifier; 100 feet cable with tinned lead wires to connect directly to 4TX & 2TX pH
Transmitters
Integrated Temperature
Rugged ORP Sensor WITHOUT preamplifier for 4TX or 2TX meters
Compensation, Preamplifiers &
Model: PN 6852-1000-15 Rugged General Purpose ORP Sensor
Solution Ground Elements Description: ¾”- 1” MNPT Immersion RYTON Bodied General Purpose ORP sensor with
thick-band platinum (ORP) sensing element and solid-state conductive polymer double junction
Solid State Reference System HDPE reference; Integrated 1000 Ohm Platinum Temperature Measurement Element; 15 feet of
offers superior resistance to cable with tinned lead wires to connect directly to 4TX & 2TX ORP Transmitters
Fouling & Dehydration
Applications such as
Acid/Fluoride, Hi-Temp, Saturated
Sodium and Sulfide Resistant are
available as standard options
Custom Applications are available,
often at no additional charge
Most Installation Styles are
Supported Including:
Immersion, Twist Lock,
Valve Retractable & Sanitary
Available in a wide range of Choosing the Correct pH/ORP Sensor
plastics, from inexpensive PVC & 1. Choose a sensor body type that suits the physical parameters of the installation (refer to the
CPVC to thermally & chemically Configurations Portion of pH/ORP and Ion Selective webpages).
2. Choose a sensor that suits the process application, temperature, chemistry, and physical parameters of the
resilient RYTON® thermoplastic
installation (refer to Sensor Selection Guides and call factory or local sales agent for support)
3. Choose a sensor housing material that is compatible with the process chemistry, temperature & pressure
High Pressure Applications up to (refer to Chemical Resistance Charts as posted under the Technical Documents portion of the website).
100 psi for Valve Retractable & 4. Select suitable temperature compensation element, solution ground & integrated preamplifier based upon
the mating pH/ORP Instrument (refer to Electrochemical Instrumentation Page & ask for factory support).
150 psi for Inline Installations can
5. Specify the required cable length based upon installation location (refer to Part Numbering Guide).
be supported for continuous use
* Subject to application qualification and review by an approved ASTI sales agent and/or factory.
Operating Temperatures from Performance guarantee is posted on the ASTI online application questionnaire page.
-
30 to +150 ºC (-22 to +302 ºF) can ** See list of supported pH/ORP/ISE Instruments webpages as posted on the ASTI website.
*** Completion of Application Questionnaire form is required. Other restrictions may apply.
be supported for continuous use