SENSORTEC - CONVENTIONAL
IONISATION SMOKE DETECTOR MODEL: ST-I
The ST-I conventional ionisation detector utilises the dual chamber, single source principle to provide optimum
response to smoke.
The Radioactive source is only 33.3kBq., (0.9µci), Americium 241, therefore conforming to OECD
recommendations. The detector's design provides strong immunity to air velocities, contamination and RF
interference.
Variants:
ST-I-IS c/w STB-4IS Intrinsically Safe version.
VdS
ST-I-DA With Service Alarm facility. EXPECTED 041c/05
NOV. 2002
ST-IB Black Detector.
Both the ST-P and ST-I have a chemically etched screen for protection against insect ingress.
Variants:
ST-P-DA With Service Alarm facility.
ST-P-LV 12V Version.
VdS
ST-PB Black Detector G 298064 041c/06
BASE COMPATIBILITY
The NFD-68-P is supplied as standard with a B4-F base, however the NFD-68-P is also compatible with our
STB-4 and RB-3/4/6 bases. NOTE: Please refer to the NFD-68P instruction manual for correct wiring details.
The housing has a threaded cover to enable ease of access for installation and includes internal and
external earth terminals suitable for up to 4mm cable.
STANDARDS:-
CENELEC STANDARDS EN50014/50018
NBMC23.001/103
ISSeP APPOVED (Formerly INIEX)
EEXd IIC T6
BASES
Standard Bases:-
STB-4 - - Standard 4 terminal base.
STB-4 (B) - - Standard 4 terminal base (Black).
STB-4R - - Standard base inclusive of 220 or 330 or 470 Ohm resistor (Short circuit monitor resistor).
STB-4SDR - - Standard base inclusive of 470 Ohm resistor (Short circuit monitor resistor) & Diode.
STB-4IS - - Standard base for use with ST-I-IS Intrinsically Safe smoke detector.
STB-5DA - - Standard base for use with ST-I/ST-P-DA Service Alarm detector.
Deep Bases:-
STB-4SE - Standard 4 terminal deep base
STB-4SER - Standard deep base inclusive of 220 or 330 or 470 Ohm resistor (Short circuit monitor resistor).
STB-4SE-TW - Standard deep base, Two-Wire system.
STB-4SE-TW SAVWIRE - Standard deep base, SAV-Wire system.
STB-4SE-12VR - Standard deep base inclusive of a VFCO relay, 12V operation.
STB-4SE-12VRL - Standard deep base inclusive of a VFCO relay, 12V operation as above but latching.
STB-4SE-24VR - Standard deep base inclusive of a VFCO relay, 24V operation.
15mm
15mm
35mm 24mm
NFD-FPH
M6
104mm 100mm
160mm M6
27mm 137mm
146mm
TECHNICAL SPECIFICATION
Model: NFD-68-P Model: NFD-FPH Housing
Detector Type: - Conventional, ULTRAVIOLET Part No: - 63540
Part No: - 60043 Body & Cover - Copper free
Voltage: - 10V to 30V d.c. aluminium
Quiescent Current: - 120µA (max.). @ 24V d.c. (Powder coated)
(through terminals L & C) Locking Screw - Steel zinc plated
Alarm Current: - 65 mA. max. Window - Quartz Glass
OperatingTemperature - -10 deg.C to +50 deg.C. (Heat resistant)
Remote LED Output: - 'P' terminal = 30V - 100mA IP Rating - IP54 (no gasket)
(through terminals P & C via - IP67 (c/w gasket)
3rd wire) Cable Entries - 2 x M20
Mass: - 110g, excluding base (1.5mm pitch)
Relative Humidity: - 95% Classifcation - EExd IIC T6.
Compatible Base - STB series and RB-3/6
Detector Acceptance Angle- 100 Degrees.
The NHD Heat detector is non-mechanical and uses a thermister of low thermal mass as the
sensing element giving a fast response. Four different response grades are available to BS
5445/EN54 part 5, grades 1, 2, 3 plus a high temperature version to BS 5445/EN54 Part 8.
Although these detectors operate on the principle of a fixed threshold only, their fast
response make them generally suitable where combined rate-of-rise heat detectors would
normally be required.
The NHD heat detectors are unobtrusive and attractive in appearance. A very low
monitoring current is used and a red fire LED indicator is incorporated, which latches in
alarm. All NHD heat detectors have four terminals, as standard, allowing a transistor
switching facility capable of ‘sinking’ 100mA, ideally suitable for switching remote LED
indicators.
SPECIFICATION
24V d.c. Versions:
Sensitivity:-
Model No. BS 5445/EN54 Nominal Alarm Temp. Label Colour
NHD-G1 Grade 1 (Part 5) 58 Deg.C Green NHD-G1 NHD-G2
NHD-G2 Grade 2 (Part 5) 66 Deg.C Yellow 041a/01 041a/02
NHD-G3 Grade 3 (Part 5) 74 Deg.C Red
NHD-GH1 Range 1 (Part 8) 80 Deg.C Blue NHD-GH1 NHD-G3
041b/01 041a/03
12V d.c. Versions:
Sensitivity:-
Model No. BS 5445/EN54 Nominal Alarm Temp. Label Colour
NHD-G1-LV
NHD-GH1-LV
Grade 1 (Part 5)
Range 1 (Part 8)
58 Deg.C
80 Deg.C
Green
Blue
VdS
Operating Voltage Range:-
NHD-G1, G2, G3
16 - 30V d.c.. (Standard models) G 295027
11 - 24V d.c.. (12V d.c. versions) NHD-GH1
G 295028
Monitoring Current:-
20µA (typ) @ 24V d.c. @ 25Deg.C..
Operating Current:-
65mA (max. allowable).
Storage Temperature:-
-25 to +90Deg.C..
Base Types:-
SENSORTEC STB-4 Series (See below) and RB-3, RB-6 Series.
Mass:-
115g (Head only).
BASES
Standard Bases:-
STB-4 - - Standard 4 terminal base.
STB-4 (B) - - Standard 4 terminal base (Black).
STB-4R - - Standard base inclusive of 220 or 330 or 470 Ohm resistor (Short circuit monitor resistor).
STB-4SDR - - Standard base inclusive of 470 Ohm resistor (Short circuit monitor resistor) & Diode.
STB-4IS - - Standard base for use with ST-I-IS Intrinsically Safe smoke detector.
STB-5DA - - Standard base for use with ST-I/ST-P-DA Service Alarm detector.
Deep Bases:-
STB-4SE - Standard 4 terminal deep base
STB-4SER - Standard deep base inclusive of 220 or 330 or 470 Ohm resistor (Short circuit monitor resistor).
STB-4SE-TW - Standard deep base, Two-Wire system.
STB-4SE-TW SAVWIRE - Standard deep base, SAV-Wire system.
STB-4SE-12VR - Standard deep base inclusive of a VFCO relay, 12V operation.
STB-4SE-12VRL - Standard deep base inclusive of a VFCO relay, 12V operation as above but latching.
STB-4SE-24VR - Standard deep base inclusive of a VFCO relay, 24V operation.
15mm
63mm 104mm
WIRING CONNECTIONS
6 6 6 6
_
Max. current through
C
5 = 100mA @ 24V d.c.
The ST-I-IS utilises the dual chamber, single source principle to provide optimum response to smoke. The
radioactive source is only 33.3 kBq (0.9µCi) Americium 241, therefore conforming to OECD
recommendations. The sensors design provides strong immunity to air velocities, contamination and RF
interference. (Please refer to ST-I-IS Instruction manual for installation information).
The glass element is pre-scored to break easily under thumb pressure and thus no striker is required.
The NCPK-IS is suitable for a Zone 2 environment, classification Ex N IIC T6. The NCPK-IS call point has
an IP rating of IP54.
The beacon is available in 12V d.c. and 24V d.c. versions for gas groups IIB or IIC.
PART NUMBERS/ORDER CODES:-
Zone 0, 1 and 2 use XB8/1/C = 12V d.c., Gas Group IIB, Lens Clear.
EEx ia IIB/IIC T4 XB8/2/C = 12V d.c., Gas Group IIC, Lens Clear.
Baseefa Certified and Cenelec Approved XB8/4/C = 24V d.c., Gas Group IIB, Lens Clear.
IP66
XB8/5/C = 24V d.c., Gas Group IIC, Lens Clear.
The ST-FPHD-XXX is available as 60, 71, 88, 99, 107, 135, 163, 180, 230, 260, 316 and 385 Deg.C.
temperature settings.
Output: 1 Watt
The NBM-06 is designed specifically for applications where low current consumption is required.
The NBM-08 is weatherproof and comes complete with it's own mounting box, I.P. rating I.P.65.
Measuring only six centimetres deep this Low Profile Banshee Sounder blends unobtrusively into back-
ground in to most installations. The LFB24 features Buzz, Fast Sweep, Slow Sweep and Continuous tones.
Supply Voltage: 8-35V d.c., Current: <12mA, Sound Output: 103dB @ 1 metre, IP65 rated.
The NCP-K470 is fitted with a 470 Ohm short circuit series monitor resistor. Each call point is
supplied with a test key which, when inserted, simulates breaking the glass by allowing it to drop,
causing actual operation of the micro-switch.
The NCP-K470-WP is fitted with a 470 Ohm short circuit series monitor resistor. Each call point is
supplied with a test key which, when inserted, simulates breaking the glass by allowing it to drop,
causing actual operation of the micro-switch.
Also available are the ST-P-DA Photoelectric and ST-I-DA Ionisation smoke detectors which include a
special service alarm facility. The detector's indicating LED illuminates green when the smoke chamber
requires cleaning and red for fire alarm, also the service alarm signal can be shown at the control panel.
The STA-D5 has a revolutionary 'one pipe system', the Venturi Principle is achieved by the use of a single
pipe with two built-in channels which direct's the airflow smoothly through the detector's chamber and
return's the air back into the duct.
The VCT-03-NT sounder base gives systems designers a new low profile design, while giving the installers reduced installation time with it’s
wide cable access and rising clamp terminals.
Wiring from the fire alarm control panel’s sounder circuit may wired directly into the VCT-03-NT base mounted sounder and then on to the next
sounder.
Please note the VCT-03-NT is not supplied with a base, the base has to ordered separately.
The VRS-1 sounder is small in size but big on sound output. With it’s low current consumption and high sound output the ST-VMS gives
systems designers increased flexibility where a sounder with minimum visual impact is required.
Wiring from the fire alarm control panel’s sounder circuit may wired directly into the VRS-1 bedhead mounted sounder and then on the next
sounder.
Current: <12mA
The ST-I-AS has a chemically etched screen to improve smoke entry whilst reducing the
ingress of insects and airborne contaminants.
Variant: ST-I-AS Ionisation Sensor, Black. 041c/10
As the smoke enters the sensor, the amount of scattered light increases. This change is detected
by the photo-diode and is amplified before being converted into a digital signal and transmitted to
the control equipment.
Variant: ST-P-AS Photoelectric Sensor, Black. 041c/09
5 bit analogue data plus 1 range selector bit are used to give greater definition over a wide temperature
sensing range.
041a/04
Inside both the ST-NCP-AS and ST-NCP-AS-WP call points there is a miniature, innovative and
unobtrusive 'electronic component housing' which will allow the call point to be mounted in a variety of
surface and flush mounting back boxes.
Both call points include a LED indicator on the front cover. This LED flashes to indicate correct
ST-NCP-AS
communication with the control equipment, the LED will remain constantly illuminated when the call
point is in fire condition.
The ST-NCP-AS and ST-NCP-AS-WP call points operate on a reliable and well proven design, by
releasing a concealed microswitch when the glass is broken. The glass element is pre-scored to break
easily under thumb pressure and thus no striker is required. A plastic film which covers the surface of
the glass prevents the possibility of injury caused by the release of glass fragments.
Each manual call point is supplied with a test key which, when inserted, simulates breaking the glass
by allowing it to drop, causing actual operation of the microswitch.
The ST-NCP-AS and ST-NCP-AS-WP forms part of NITTAN (UK) LTD “AS” range of
SENSORTEC-ANALOGUE addressable equipment and should only be used on suitable and
compatible control panels. If in doubt, refer to panel manufacturer for advice. ST-NCP-AS-WP
35mm 63mm
104mm 104mm
30mm
Back Box
ST-NCP-AS
FIRE
86mm
86mm
BREAK GLASS
PRESS HERE
86mm
20mm 32mm
Key switch location here
60mm
ST-NCP-ASWP
M20
124mm
Considerable cost savings will be achieved as there is no need to provide additional power supply cabling.
Please refer to Instruction Manual NISM/NAM2/01 for further information on the NAM-AS2.
As per the NAM-AS2 this module operates on two wires, the Sig+ and -S loop cable and does not require
an external power supply.
Please refer to Instruction Manual NISM/OCM2/01 for further information on the OCM-AS2.
The MCM-AS3 may be used for a variety of purposes such as monitoring a zone of conventional detec-
tors and at the same time controlling fire doors, plant or smoke ventilators via the on board VFCO relay.
Please refer to Instruction Manual NISM/MCM3/01 for further information on the MCM-AS3.
The sounder circuit is monitored with an end of line resistor, just as a conventional sounder circuit, and can
drive up to 500mA of sounder load. Polarised sounders are required, or a blocking diode should be used.
Please refer to Instruction Manual NISM/SCM3/01 for further information on the SCM-AS3.
By using short circuit isolators on the loop, the section of wiring containing the short may be isolated
from the remainder of the loop therfore limiting the extent of the disablement to only the cable between
two adjacent short circuit isolators. The remainder of the loop will still continue to function as normal.
Ideally short circuit isolators should be fitted wherever the loop crosses a fire compartment zonal
boundary, also on either side of critical devices such as sounder control modules and at the beginning
and at the end of the loop.
In addition to the IP55 housing the SCI-4 incorporates two yellow LED indicators which are visible
through the enclosure and indicate the direction of the short circuit fault condition.
A new version of the SCI-4 called SCI-6, will be available at the end of 2001. The new short circuit
isolator will be mountable on a single gang, standard electrical, surface mounting type box.
VCT-03-NT-AS VCT-NTAS-CP
c/w STB-4 Base c/w VCT-03-CP-W
The addressable sounder base gives systems designers a new low profile design, while giving the installers reduced installation time with it’s
wide cable access and rising clamp terminals.
Supply Voltage: 24V d.c., Current: c. 10mA, Sound Output: 90dB @ 1m, IP43 rated.
WALL MOUNTED ADDRESSABLE SOUNDER MODEL: VCT-NTAS-CP c/w RED OR WHITE CAP
The VCT-NTAS-CP is a loop powered sounder and is compatible with Nittan ‘AS’ protocol control panels.
The addressable wall sounder c/w cap gives systems designers a new low profile design, while giving the installers reduced installation time
with it’s wide cable access and rising clamp terminals.
The VCT-NTAS-CP can be supplied with either a white or red cap depending on your fire system requirments.
VPR-SA2-NTAS(R)
VPR-SA2-NTAS(W)
The VPR-SA2-NTAS addressable 'AS' protocol sounder has been designed for applications where low current consumption relative to
high sound output is required.
With an operating frequency of 800-1000Hz each sounder provides sound within the frequency range specified in BS5839. The sounder
also has a wide operating voltage range of 8-35V d.c..
Different tones are available by selecting either Warble, Sweep, or Continuous via the jumper fitted to the PCB.
A second stage alarm may be switched, via the control panel, so the Pips tone will override the tone selected.
The sounder casing material is ABS and is supplied in either red or white colours. (Note white special order).
The sounder is supplied complete with its own mounting base which comes with marker points for drilling two M20 cable gland entries.
Supply Voltage: 24V d.c., Current: <12mA, Sound Output: 103dB @ 1 metre, IP65 rated.
The control panel conforms to prEN54 parts 2 and 4 and the main circuit board is built almost entirely using SMT
components. The circuitry is housed in a strong metal casing, there are clear indication status functions and
simplified labelling for connection of the cables to the main circuit PCB.
1-10 ZONE CONVENTIONAL CONTROL PANEL MODEL: CF/210 & 11-20 ZONE
CONVENTIONAL CONTROL PANEL MODEL: C/CF210
The CF/210 fire detection panel is a 1-10 and/or 1-20 detection zone suitable for connection of 24V Nittan
conventional detectors. The CF/210 1-10 zone panel is supplied as standard with a CF/EXP210 double zone
expansion zone card, the CF/210 may supplied as double enclosure and together with a C/CF210 11-20
zone expansion card allows an additional 10 zones allowing a maximum of 20 zones.
The control panel conforms to prEN54 parts 2 and 4 and the main circuit board is built almost entirely using
SMT components. The circuitry is housed in a strong metal casing, there are clear indication/status
functions and simplified labelling for connection of the cables to the main motherboard.
FEATURES:-
Indications for FAULT, ALARM and ZONES ISOLATED.
Indications for: Mains power, battery
disconnection, battery low, general fault, siren fault,
common isolate, common fire alarm, pre-alarm and day/night Internal Buzzer indicating fire and faults.
function status of the panel
Relay outputs for ALARM, FAULT and PRE-ALARM
RESET, SILENCE, EVACUATE and DAY/NIGHT functions with NO/NC volt free contacts
Engineer Entry Codes Levels 1 and 2 Monitored output for connecting a 24V Sounder or Bells etc.
Internal connection to a CP8/REL relay card (optional) for installing 24V d.c. output for auxiliary power supply
UNIREL/24 circuits (max. 8) to repeat conditions of the following:-
ALARM zone 1, ALARM zone 2, FAULT zone 1, FAULT zone 2, Zonal Isolation of a single zone
Isolate zone 1, Isolate zone 2, AND function activated, OR function
activatation. AND function and OR functions
Features:
VFCO contacts for Fire and Fault
3 Amp power supply
2 x Sounder circuits
Coded Access Part Numbers:
One man walk test facility EN-2 - 2 Zone Panel
Class change input EN-4 - 4 Zone Panel
Evacute input EN-8 - 8 Zone Panel
ACCEPT COMMON FAULT ZONAL FAULT ZONAL FAULT ACCEPT COMMON FAULT ZONAL FAULT ZONAL FAULT
1 2 3 4 1 2 3 4
304
DAY/NIGHTEVACUATION SILENCE RESET DAY/NIGHTEVACUATIONSILENCE RESET
ISOLATED ISOLATED ISOLATED ISOLATED
98000534 98000534
3
13
CF210 1-10 ZONE & C/CF210 11-20 ZONE EXPANDABLE CONVENTIONAL CONTROL PANEL
Note: The CF210 C/CF210
CF210 includes
CF210 c/w C/CF210
1 x CF/EXP210 as
standard
! !
303
303
1 2 3 1
4 2 3 4
5 6 7 8 5 6
9 7 8
10 9 10
! ! ! ! ! ! ! ! ! !
! ! ! ! ! ! ! ! ! !
132 132
225mm
285mm
285mm
355mm
80mm
80mm
NOTE:
2, 4 & 8 Zone panels are all
identical dimensions.
The advantage of the Two-Wire system makes the installation easier therefore greatly
reducing installation costs. All control panels incorporate a tactile membrane display with
facilities for both the end user and Engineer. A simple code provides the end user with
restricted access but allows an Engineer entry to the operator and engineering functions.
All the Two-Wire control panels can be utilised as a standard conventional panel in addition to
the Two-Wire configuration. This enables a mixture of zones to be configured as Two-Wire
and other zones can be configured as standard conventional type.
8 Zone Panel
TWO-WIRE WALL MOUNTING SOUNDER MODEL: VCT-03-NT-TW c/w RED OR WHITE CAP
This sounder together with the base sounder have been designed to compliment
our other products in the Two-Wire system range.
Specification:
Voltage: - - 24V d.c. nominal.
dB @1m - - 93dB @ 1m.
Start Current - - 30mA
Current Consumption - - <12mA
Tones - - Sweeping, Continuous & Alternating
IP Rating - - IP43
Cap - - Red or White VCT-03-NT-TW VCT-03-NT-TW
c/w STB-4 Base c/w VCT-03-CP Cap
ZONE
+
2-Wire Module
470R
Call ZONE OUT
ZONE IN Point
ZONE ZONE
- -
+
ZONE OUT
ZONE IN
Z+
+ ZONE OUT
ZONE IN -
Z-
-
Z-
Note:
Localvoltage free contact output is
Note: Note: Note: active when local detector remote
Use remote -IN only if local Switched 24V supply output is Global voltage free contact output -IN is active to clear this output a
voltage free contacts required active only when the zones alarms is active only when the zone panel reset condition must occur.
are active. alarms are active.
Fully compliant with EN54 Parts 2 and 4, it's wide range of features
include 16 zonal alarm LEDs (expandable to 32), four separate inde-
pendently programmable sounder circuits and an integral 24V 3amp
switch mode power supply. The AFP can be programmed on-site via
tactile switches on the panel front or via an easy to use, low-cost upload/
download PC programme.
Other features include a 999 event memory, delay timer and phased
evacuation facilities, sophisticated test and maintenance facilities and
a comprehensive ‘auto-learn' facility allowing the panel to self-configure
to devices connected to the loop.
* 16 Zonal LEDs
* Back lit, high resolution, LCD display * Fire, fault, and remote VFCO contacts
These panels are designed to be aesthetically pleasing with a contrasting membrane facia incorporating a tactile
alpha numeric keypad making it fully on-site programmable. The high quality steel enclosure may be fitted with an
optional glass window and flush mounting bezel. The main display is via an 80 character, back lit LCD with 20
zonal LED fire and fault indicators. There is also a 2 x 7 segment LED display for easy identification of Fire zone.
The ZXe panel designed to be aesthetically pleasing with a contrasting membrane facia incorporating a non-
tactile alpha numeric keypad making it fully on-site programmable. The high quality steel enclosure may be
fitted with an optional glass door or flush mounting kit as required.
The main display is via an 80 character, back lit LCD with 20 zonal LED fire and fault indicators expandable to
a maximum of 80 fire and fault LEDs.
ALSO AVAILABLE....
The ZX-R4b features a LCD only plus 6 dual status LED’s. The ZX-R5b is as per
ZX-R4b with the additional following two-way features: Accept, Silence/Resound,
Reset & Evacuate control keys and there is also a keyswitch which is provided to
enable/disable the two-way features/controls.
OPTIONAL EQUIPMENT:-
EXC-014: Flush mounting bezel for ZX-R4b/R5b
3A PSU