NITTAN (UK) LTD offers a range of fire detection devices including the ST-I ionisation smoke detector, ST-P photoelectric smoke detector, and NFD-68P ultraviolet flame detector, each designed for optimal smoke response and equipped with various features and variants. The ST-I-IS model is specifically designed for hazardous areas, while the NFD-FPH is a flameproof version for environments with flammable substances. All devices comply with relevant safety standards and specifications, ensuring reliable performance in fire detection systems.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
43 views20 pages

Sensortec - Conventional: Nittan (Uk) LTD

NITTAN (UK) LTD offers a range of fire detection devices including the ST-I ionisation smoke detector, ST-P photoelectric smoke detector, and NFD-68P ultraviolet flame detector, each designed for optimal smoke response and equipped with various features and variants. The ST-I-IS model is specifically designed for hazardous areas, while the NFD-FPH is a flameproof version for environments with flammable substances. All devices comply with relevant safety standards and specifications, ensuring reliable performance in fire detection systems.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

NITTAN (UK) LTD

SENSORTEC - CONVENTIONAL
IONISATION SMOKE DETECTOR MODEL: ST-I
The ST-I conventional ionisation detector utilises the dual chamber, single source principle to provide optimum
response to smoke.

The Radioactive source is only 33.3kBq., (0.9µci), Americium 241, therefore conforming to OECD
recommendations. The detector's design provides strong immunity to air velocities, contamination and RF
interference.
Variants:
ST-I-IS c/w STB-4IS Intrinsically Safe version.
VdS
ST-I-DA With Service Alarm facility. EXPECTED 041c/05
NOV. 2002
ST-IB Black Detector.

PHOTOELECTRIC SMOKE DETECTOR MODEL: ST-P


The ST-P conventional photoelectric smoke detector utilises the light scatter sensing principle, the LED pulses
every 8 seconds to maintain a low monitoring current. A quick charge time, (30 seconds), is also achieved.
The detector incorporates an alarm verification function which requires two successive pulses before an alarm
is given.

Both the ST-P and ST-I have a chemically etched screen for protection against insect ingress.
Variants:
ST-P-DA With Service Alarm facility.
ST-P-LV 12V Version.
VdS
ST-PB Black Detector G 298064 041c/06

ULTRAVIOLET FLAME DETECTOR MODEL: NFD-68P


The NFD-68-P is the direct replacement for the 2VA-P and NFD-18-2 U.V. flame detector's and operates on
the same principle. The circuitry is designed to provide protection against false alarms and the unit must
observe a fire indication for an 8.5 second period before indicating a fire condition to the control panel.

BASE COMPATIBILITY
The NFD-68-P is supplied as standard with a B4-F base, however the NFD-68-P is also compatible with our
STB-4 and RB-3/4/6 bases. NOTE: Please refer to the NFD-68P instruction manual for correct wiring details.

FLAMEPROOF FLAME DETECTOR MODEL: NFD-FPH


The NITTAN NFD-FPH flameproof UV flame detector utilises the NFD-68-P flame detector. The
NFD-FPH is for use in areas made potentially hazardous by the presence of flammable liquids, gases or
vapours, (Zone 1 or Zone 2).

The housing has a threaded cover to enable ease of access for installation and includes internal and
external earth terminals suitable for up to 4mm cable.

STANDARDS:-
CENELEC STANDARDS EN50014/50018
NBMC23.001/103
ISSeP APPOVED (Formerly INIEX)
EEXd IIC T6

BASES
Standard Bases:-
STB-4 - - Standard 4 terminal base.
STB-4 (B) - - Standard 4 terminal base (Black).
STB-4R - - Standard base inclusive of 220 or 330 or 470 Ohm resistor (Short circuit monitor resistor).
STB-4SDR - - Standard base inclusive of 470 Ohm resistor (Short circuit monitor resistor) & Diode.
STB-4IS - - Standard base for use with ST-I-IS Intrinsically Safe smoke detector.
STB-5DA - - Standard base for use with ST-I/ST-P-DA Service Alarm detector.

Deep Bases:-
STB-4SE - Standard 4 terminal deep base
STB-4SER - Standard deep base inclusive of 220 or 330 or 470 Ohm resistor (Short circuit monitor resistor).
STB-4SE-TW - Standard deep base, Two-Wire system.
STB-4SE-TW SAVWIRE - Standard deep base, SAV-Wire system.
STB-4SE-12VR - Standard deep base inclusive of a VFCO relay, 12V operation.
STB-4SE-12VRL - Standard deep base inclusive of a VFCO relay, 12V operation as above but latching.
STB-4SE-24VR - Standard deep base inclusive of a VFCO relay, 24V operation.

NITTAN (UK) LTD - BRINGING STYLE INTO FIRE DETECTION SYSTEMS


DIMENSIONS
NFD-68-P
ST-I & ST-P 120mm

15mm
15mm

35mm 24mm

NFD-FPH
M6

104mm 100mm

160mm M6

27mm 137mm
146mm

TECHNICAL SPECIFICATION
Model: NFD-68-P Model: NFD-FPH Housing
Detector Type: - Conventional, ULTRAVIOLET Part No: - 63540
Part No: - 60043 Body & Cover - Copper free
Voltage: - 10V to 30V d.c. aluminium
Quiescent Current: - 120µA (max.). @ 24V d.c. (Powder coated)
(through terminals L & C) Locking Screw - Steel zinc plated
Alarm Current: - 65 mA. max. Window - Quartz Glass
OperatingTemperature - -10 deg.C to +50 deg.C. (Heat resistant)
Remote LED Output: - 'P' terminal = 30V - 100mA IP Rating - IP54 (no gasket)
(through terminals P & C via - IP67 (c/w gasket)
3rd wire) Cable Entries - 2 x M20
Mass: - 110g, excluding base (1.5mm pitch)
Relative Humidity: - 95% Classifcation - EExd IIC T6.
Compatible Base - STB series and RB-3/6
Detector Acceptance Angle- 100 Degrees.

Model: ST-I Model: ST-P


Detector Type: - Conventional, Ionisation Detector Type: - Conventional, Photoelectric
Part No: - 80000 Part No: - 80100
Voltage: - 16V to 30V d.c. Voltage: - 16V to 30V d.c.
Quiescent Current: - 40µ A (max.). @ 24V d.c. Quiescent Current: - 40µA (max.). @ 24V d.c.
Alarm Current: - 65 mA. max. Alarm Current: - 65 mA. max.
OperatingTemperature - -10 deg.C to +50 deg.C. OperatingTemperature - -10 deg.C to +50 deg.C.
Remote LED Output: - 6V - 20mA (direct connection) Remote LED Output: - 6V - 20mA (direct connection)
24V d.c. - 100mA 24V d.c. - 100mA (via 3rd wire)
(via 3rd wire). Charge Time: - 30 seconds
Charge Time: - 30 seconds Mass: - 116g, excluding base
Mass: - 110g, excluding base Sensitivity: - BS5445/EN54 Part 7
Sensitivity: - BS5445/EN54 Part 7 Relative Humidity: - 95%
Relative Humidity: - 95% Compatible Base: - STB series, RB-3/6.
Compatible Base - STB series, RB-3/6. Approvals: - LPCB & VDS Certified
Approvals: - LPCB Certified
VDS (Expected Nov. 2001)

FOR FURTHER INFORMATION PLEASE CONSULT THE RELEVENT INSTRUCTION MANUAL


©. In pursuance of our policy of continuous product improvement, we reserve the right to change the specification without prior notice.

NITTAN (UK) LTD


Hipley Street, Old Woking, Surrey. GU22 9LQ. ENGLAND TEL: +44 (0)1483 769555 FAX: +44 (0)1483 756686
Web Site: www.nittan.co.uk E-mail: [email protected], [email protected]
NITTAN (UK) LTD
SENSORTEC - CONVENTIONAL
FAST RESPONSE HEAT DETECTOR MODELS: NHD-G1, G2, G3 and GH1
The NHD-G series heat detectors are fast response heat detectors for use in conventional
fire detection systems. They may be used in most cases as a direct replacement for our
2SA-70T-LS, TCA-60-LS and TCA-70-LS heat detectors.

The NHD Heat detector is non-mechanical and uses a thermister of low thermal mass as the
sensing element giving a fast response. Four different response grades are available to BS
5445/EN54 part 5, grades 1, 2, 3 plus a high temperature version to BS 5445/EN54 Part 8.
Although these detectors operate on the principle of a fixed threshold only, their fast
response make them generally suitable where combined rate-of-rise heat detectors would
normally be required.

The NHD heat detectors are unobtrusive and attractive in appearance. A very low
monitoring current is used and a red fire LED indicator is incorporated, which latches in
alarm. All NHD heat detectors have four terminals, as standard, allowing a transistor
switching facility capable of ‘sinking’ 100mA, ideally suitable for switching remote LED
indicators.

SPECIFICATION
24V d.c. Versions:
Sensitivity:-
Model No. BS 5445/EN54 Nominal Alarm Temp. Label Colour
NHD-G1 Grade 1 (Part 5) 58 Deg.C Green NHD-G1 NHD-G2
NHD-G2 Grade 2 (Part 5) 66 Deg.C Yellow 041a/01 041a/02
NHD-G3 Grade 3 (Part 5) 74 Deg.C Red
NHD-GH1 Range 1 (Part 8) 80 Deg.C Blue NHD-GH1 NHD-G3
041b/01 041a/03
12V d.c. Versions:
Sensitivity:-
Model No. BS 5445/EN54 Nominal Alarm Temp. Label Colour
NHD-G1-LV
NHD-GH1-LV
Grade 1 (Part 5)
Range 1 (Part 8)
58 Deg.C
80 Deg.C
Green
Blue
VdS
Operating Voltage Range:-
NHD-G1, G2, G3
16 - 30V d.c.. (Standard models) G 295027
11 - 24V d.c.. (12V d.c. versions) NHD-GH1
G 295028
Monitoring Current:-
20µA (typ) @ 24V d.c. @ 25Deg.C..

Operating Current:-
65mA (max. allowable).

Minimum Ambient Temperature:-


-10Deg.C..

Storage Temperature:-
-25 to +90Deg.C..

Base Types:-
SENSORTEC STB-4 Series (See below) and RB-3, RB-6 Series.

Mass:-
115g (Head only).

BASES
Standard Bases:-
STB-4 - - Standard 4 terminal base.
STB-4 (B) - - Standard 4 terminal base (Black).
STB-4R - - Standard base inclusive of 220 or 330 or 470 Ohm resistor (Short circuit monitor resistor).
STB-4SDR - - Standard base inclusive of 470 Ohm resistor (Short circuit monitor resistor) & Diode.
STB-4IS - - Standard base for use with ST-I-IS Intrinsically Safe smoke detector.
STB-5DA - - Standard base for use with ST-I/ST-P-DA Service Alarm detector.

Deep Bases:-
STB-4SE - Standard 4 terminal deep base
STB-4SER - Standard deep base inclusive of 220 or 330 or 470 Ohm resistor (Short circuit monitor resistor).
STB-4SE-TW - Standard deep base, Two-Wire system.
STB-4SE-TW SAVWIRE - Standard deep base, SAV-Wire system.
STB-4SE-12VR - Standard deep base inclusive of a VFCO relay, 12V operation.
STB-4SE-12VRL - Standard deep base inclusive of a VFCO relay, 12V operation as above but latching.
STB-4SE-24VR - Standard deep base inclusive of a VFCO relay, 24V operation.

NITTAN (UK) LTD - BRINGING STYLE INTO FIRE DETECTION SYSTEMS


DIMENSIONS

15mm

63mm 104mm

WIRING CONNECTIONS

3rd wire must disconnect during re-set


+
+
If +ve supply derived from L RIL
then RIL must be LED type
L +
+
3 3 3 3
RIL 4 4 E
O
1 5 1 5 1 5 1 5 L

6 6 6 6
_
Max. current through

C
5 = 100mA @ 24V d.c.

STB-4 base STB-4R base STB-4SD base STB-4SDR base

RESPONSE CHARACTERISTIC GRAPHS

FOR FURTHER INFORMATION PLEASE CONSULT THE RELEVENT INSTRUCTION MANUAL


©. In pursuance of our policy of continuous product improvement, we reserve the right to change the specification without prior notice.

NITTAN (UK) LTD


Hipley Street, Old Woking, Surrey. GU22 9LQ. ENGLAND TEL: +44 (0)1483 769555 FAX: +44 (0)1483 756686
Web Site: www.nittan.co.uk E-mail: [email protected], [email protected]
NITTAN (UK) LTD
SENSORTEC - INTRINSICALLY SAFE
INTRINSICALLY SAFE IONISATION SMOKE DETECTOR MODEL: ST-I-IS
The ST-I-IS forms part of Nittan UK’s SENSORTEC range of smoke and heat detectors. The ST-I-IS
conventional ionisation intrinsically safe smoke detector complete with it’s special STB-4IS base is for use
in hazardous areas where EEx ia IIC T4 (Tamb -10 to +50 Deg.C.) certification is required.

The ST-I-IS utilises the dual chamber, single source principle to provide optimum response to smoke. The
radioactive source is only 33.3 kBq (0.9µCi) Americium 241, therefore conforming to OECD
recommendations. The sensors design provides strong immunity to air velocities, contamination and RF
interference. (Please refer to ST-I-IS Instruction manual for installation information).

FLAME-PROOF U.V. FLAME DETECTOR MODEL: NFD-FPH


The NITTAN NFD-FPH flameproof UV flame detector utilises the NFD-68-P flame detector. The NFD-FPH
is for use in areas made potentially hazardous by the presence of flammable liquids, gases or vapours,
(Zone 1 or Zone 2). The housing has a threaded cover to enable ease of access for installation and
includes internal and external earth terminals suitable for up to 4mm cable.
(Please refer to NFD-68P/NFD-FPH Instruction manual for installation information).
CENELEC STANDARDS EN50014/50018 PART NUMBERS/ORDER CODES:-
NBMC23.001/103 NFD-68P = UV Flame Detector.
ISSeP APPOVED (Formerly INIEX) NFD-FPH = Flame Proof Housing for above (EExd IIC T6).
EExd IIC T6

INTRINSICALLY SAFE CALL POINT MODEL: NCPK-IS


The NCPK-IS intrinsically safe manual call point operates by releasing a concealed microswitch when the
glass is broken.

The glass element is pre-scored to break easily under thumb pressure and thus no striker is required.

The NCPK-IS is suitable for a Zone 2 environment, classification Ex N IIC T6. The NCPK-IS call point has
an IP rating of IP54.

EExia INTRINSICALLY SAFE WEATHERPROOF SOUNDER MODEL: DB5


An intrinsically safe sounder of rugged construction intended for use in potentially explosive
atmospheres, has been designed with a high ingress protection to cope with harsh environmental
conditions as found in the oil, gas and petrochemical industries.
Zone 0, 1 and 2 use PART NUMBERS/ORDER CODES:-
EEx ia IIC T4 DB5/1 = 12V d.c., Gas Group II.
Baseefa Certified and Cenelec Approved DB5/2 = 24V d.c., Gas Group II.
IP66
Up to 103dB(A) Output
26 User selectable tones

EExia INTRINSICALLY SAFE WEATHERPROOF XENON BEACON MODEL: XB8


An intrinsically safe zenon beacon of rugged construction intended for use in potentially explosive
atmospheres, has been designed with a high ingress protection to cope with harsh environmental condi-
tions as found in the oil, gas and petrochemical industries.

The beacon is available in 12V d.c. and 24V d.c. versions for gas groups IIB or IIC.
PART NUMBERS/ORDER CODES:-
Zone 0, 1 and 2 use XB8/1/C = 12V d.c., Gas Group IIB, Lens Clear.
EEx ia IIB/IIC T4 XB8/2/C = 12V d.c., Gas Group IIC, Lens Clear.
Baseefa Certified and Cenelec Approved XB8/4/C = 24V d.c., Gas Group IIB, Lens Clear.
IP66
XB8/5/C = 24V d.c., Gas Group IIC, Lens Clear.

FLAMEPROOF HEAT DETECTOR MODEL: ST-FPHD-XXX


The ST-FPHD-XXX flameproof heat detector incorporates a hermetically sealed sensor element within a
stainless steel and brass housing mounted to a galvanised cast iron junction box. This unit is BASEEFA
certified to Ex sd IIB T6 and is weatherproof rated to I.P.66 and is therefore ideally suited for paint spray
booths and flammable material and equipment stores.

The ST-FPHD-XXX is available as 60, 71, 88, 99, 107, 135, 163, 180, 230, 260, 316 and 385 Deg.C.
temperature settings.

PART NUMBER/ORDER CODES:-


ST-FPHD-060 = Flameproof heat detector, rated 60 Deg. C..
ST-FPHD-135 = Flameproof heat detector, rated 135 Deg. C..

NITTAN (UK) LTD - BRINGING STYLE INTO FIRE DETECTION SYSTEMS


SENSORTEC - ACCESSORIES XENON BEACON AND
SOUNDERS
IB-R-SW2-24, XENON BEACON (RED)
IB-A-SW2-24, XENON BEACON (AMBER)
Red or Amber Xenon beacon

Flash Energy: 0.65J

Output: 1 Watt

Current Consumption: 45mA @ 24V d.c.

Voltage Range: 20-30V d.c.

Operating Temperature: -20oC to +55oC

FL-RL-RD, COMBINED XENON BEACON & SOUNDER


IP65, Red Zenon Beacon/Sounder, 3 Tones

Output: 60 Flashes per Minute

Current Consumption: 68mA (average)

Voltage Range: 18-30V d.c.

Sounder dB: 101dB @ 1m

Deep Base Version

Operating Temperature: -10oC to +55oC

1992ROSH-DB, WEATHER PROOF SOUNDER


IP65, Weatherproof Sounder, 1-28 Tones

Current Consumption: 18mA

Voltage Range: 9-28V d.c.

Sounder dB: 100dB @ 1m.

Deep Base Version

Operating Temperature: -40oC to +80oC

FOR FURTHER INFORMATION PLEASE CONSULT THE RELEVENT INSTRUCTION MANUAL


©. In pursuance of our policy of continuous product improvement, we reserve the right to change the specification without prior notice.

NITTAN (UK) LTD


Hipley Street, Old Woking, Surrey. GU22 9LQ. ENGLAND TEL: +44 (0)1483 769555 FAX: +44 (0)1483 756686
Web Site: www.nittan.co.uk E-mail: [email protected], [email protected]
NITTAN (UK) LTD
SENSORTEC - ACCESSORIES
FIRE ALARM BELL MODELS: NBM-06 & NBM-08
The NBM series of bells are motorised in operation and are of lightweight aluminium alloy construction, painted
red. The NBM-06 fixing bracket is suitable for all types of conduit fittings including BESA and the bell may be
suspended on the bracket whilst terminating cables. The motors are polarised and suppressed.

The NBM-06 is designed specifically for applications where low current consumption is required.

The NBM-08 is weatherproof and comes complete with it's own mounting box, I.P. rating I.P.65.

BANSHEE LOW PROFILE SOUNDER MODEL: LFB24


The Banshee Low Profile Sounder model LFB24 complies fully with the requirements of BS5839 Part 1
1980. It features a snap-on front, for ease of installation, it also has a rear cable entry for maximum
flexibility.

Measuring only six centimetres deep this Low Profile Banshee Sounder blends unobtrusively into back-
ground in to most installations. The LFB24 features Buzz, Fast Sweep, Slow Sweep and Continuous tones.

WEATHERPROOF IP65 CONVENTIONAL SOUNDER MODEL: VPR-SA-R


The VPR-SA-R is a conventional, weatherproof, surface mounted sounder. Together with it’s new
terminal arrangements and surface mount components the VPR-SA-R sounder offers easy access
wiring together with an additional sweep tone.

Supply Voltage: 8-35V d.c., Current: <12mA, Sound Output: 103dB @ 1 metre, IP65 rated.

MANUAL CALL POINT MODEL: NCP-K470


The NCP-K470 manual call point operates by releasing a concealed microswitch when the glass is
broken. The glass element is pre-scored to break easily under thumb pressure and thus no striker is
required.

The NCP-K470 is fitted with a 470 Ohm short circuit series monitor resistor. Each call point is
supplied with a test key which, when inserted, simulates breaking the glass by allowing it to drop,
causing actual operation of the micro-switch.

MANUAL CALL POINT MODEL: NCP-K470-WP


The NCP-K470-WP Weather proof , (IP65), manual call point operates by releasing a concealed
microswitch when the glass is broken. The glass element is pre-scored to break easily under thumb
pressure and thus no striker is required.

The NCP-K470-WP is fitted with a 470 Ohm short circuit series monitor resistor. Each call point is
supplied with a test key which, when inserted, simulates breaking the glass by allowing it to drop,
causing actual operation of the micro-switch.

SMOKE DETECTOR FOR DUCT MOUNTING MODEL: STA-D5


The STA-D5 Duct Unit is for use with our SENSORTEC CONVENTIONAL smoke detectors and
SENSORTEC-ANALOGUE smoke sensors, it is also suitable for use with our 2IC/2IC-AS and 2KH/2KH-AS
low profile conventional and analogue addressable smoke detectors.

Also available are the ST-P-DA Photoelectric and ST-I-DA Ionisation smoke detectors which include a
special service alarm facility. The detector's indicating LED illuminates green when the smoke chamber
requires cleaning and red for fire alarm, also the service alarm signal can be shown at the control panel.

The STA-D5 has a revolutionary 'one pipe system', the Venturi Principle is achieved by the use of a single
pipe with two built-in channels which direct's the airflow smoothly through the detector's chamber and
return's the air back into the duct.

REMOTE INDICATOR LED MODEL: STA-R1


The STA-R1 remote indicator LED is for use with our SENSORTEC CONVENTIONAL smoke and heat
detectors and SENSORTEC-ANALOGUE smoke and heat detectors/sensors. The STA-R1 is also suitable for
use with our 2IC/2IC-AS and 2KH/2KH-AS low profile conventional and analogue addressable smoke and
heat sensors.

NITTAN (UK) LTD - BRINGING STYLE INTO FIRE DETECTION SYSTEMS


SENSORTEC - ACCESSORIES
VPR-SA2-R

VCT-03-NT c/w VCT-03-NT c/w


VRS-1-R/W
STB-4 BASE VCT-03-CPW VPR-SA2-W

CONVENTIONAL BASE MOUNTED SOUNDER MODEL: VCT-03-NT


The VCT-03-NT conventional base mounted electronic sounder has been designed for use with conventional fire detection systems and is
ideally suited for hotel bedroom environments.

The VCT-03-NT sounder base gives systems designers a new low profile design, while giving the installers reduced installation time with it’s
wide cable access and rising clamp terminals.

Wiring from the fire alarm control panel’s sounder circuit may wired directly into the VCT-03-NT base mounted sounder and then on to the next
sounder.

Please note the VCT-03-NT is not supplied with a base, the base has to ordered separately.

Supply Voltage: 8-35V d.c.


Current Consumption: <12mA
Sound Output: 90 dB @ 1m.
Number of Tones: 4
IP Rating: IP43

ACCESSORIES FOR THE VCT-03-NT


VCT-03-CP-W White Vector Cover Plate
VCT-03-CP-R Red Vector Cover Plate
STB-4 Series Bases

CONVENTIONAL BED HEAD MOUNTED SOUNDER MODEL: VRS-1-R/W


The VRS-1 conventional bedhead mounted electronic sounder has been designed for use with conventional fire detection systems.

The VRS-1 sounder is small in size but big on sound output. With it’s low current consumption and high sound output the ST-VMS gives
systems designers increased flexibility where a sounder with minimum visual impact is required.

Wiring from the fire alarm control panel’s sounder circuit may wired directly into the VRS-1 bedhead mounted sounder and then on the next
sounder.

The VRS-1 is available in either white or red colour, suffix R or W.

Supply Voltage: 8-35V d.c.


Current Consumption: <18mA
Sound Output: 101 dB @ 1m.
Number of Tones: 4
IP Rating: IP43

WEATHERPROOF SOUNDER MODEL: VPR-SA2-R/W


The VPR-SA2-R or W is a conventional, IP65 weatherproof, surface mounted sounder and is available in either red or white colour

Supply Voltage: 24V d.c.,

Current: <12mA

Sound Output: 103dB @ 1 metre

FOR FURTHER INFORMATION PLEASE CONSULT THE RELEVENT INSTRUCTION MANUAL


©. In pursuance of our policy of continuous product improvement, we reserve the right to change the specification without prior notice.

NITTAN (UK) LTD


Hipley Street, Old Woking, Surrey. GU22 9LQ. ENGLAND TEL: +44 (0)1483 769555 FAX: +44 (0)1483 756686
Web Site: www.nittan.co.uk E-mail: [email protected], [email protected]
NITTAN (UK) LTD
SENSORTEC - ANALOGUE
IONISATION SMOKE SENSOR MODEL: ST-I-AS
The ST-I-AS analogue addressable ionisation sensor utilises the dual chamber, single source principle to
provide optimum response to smoke. The Radioactive source is only 33.3 kBq., (0.9 µCi), Americium 241,
therefore conforming to OECD recommendations. The sensors design provides strong immunity to air
velocities, contamination and RF interference.

The ST-I-AS has a chemically etched screen to improve smoke entry whilst reducing the
ingress of insects and airborne contaminants.
Variant: ST-I-AS Ionisation Sensor, Black. 041c/10

PHOTOELECTRIC SMOKE SENSOR MODEL: ST-P-AS


The ST-P-AS analogue addressable photoelectric smoke sensor utilises the light scatter sensing principle,
using an LED and photodiode in a light proof chamber. The LED pulses infra-red light into the smoke
chamber, the photodiode being positioned such that a minimum of light is normally received.

As the smoke enters the sensor, the amount of scattered light increases. This change is detected
by the photo-diode and is amplified before being converted into a digital signal and transmitted to
the control equipment.
Variant: ST-P-AS Photoelectric Sensor, Black. 041c/09

HEAT SENSOR MODEL: ST-H-AS


The ST-H-AS sensor incorporates a thermistor of low thermal mass which responds quickly to changes
in surrounding air temperature.

5 bit analogue data plus 1 range selector bit are used to give greater definition over a wide temperature
sensing range.

041a/04

ADDRESSABLE CALL POINT MODELS: ST-NCP-AS & ST-NCP-AS-WP


The ST-NCP-AS and ST-NCP-AS-WP manual call points form part of the NITTAN (UK) LTD
SENSORTEC-ANALOGUE range of products and are compatible with our existing 'AS'
Analogue-Addressable range of devices and sensors.

Inside both the ST-NCP-AS and ST-NCP-AS-WP call points there is a miniature, innovative and
unobtrusive 'electronic component housing' which will allow the call point to be mounted in a variety of
surface and flush mounting back boxes.

Both call points include a LED indicator on the front cover. This LED flashes to indicate correct
ST-NCP-AS
communication with the control equipment, the LED will remain constantly illuminated when the call
point is in fire condition.

The ST-NCP-AS and ST-NCP-AS-WP call points operate on a reliable and well proven design, by
releasing a concealed microswitch when the glass is broken. The glass element is pre-scored to break
easily under thumb pressure and thus no striker is required. A plastic film which covers the surface of
the glass prevents the possibility of injury caused by the release of glass fragments.

Each manual call point is supplied with a test key which, when inserted, simulates breaking the glass
by allowing it to drop, causing actual operation of the microswitch.

The ST-NCP-AS and ST-NCP-AS-WP forms part of NITTAN (UK) LTD “AS” range of
SENSORTEC-ANALOGUE addressable equipment and should only be used on suitable and
compatible control panels. If in doubt, refer to panel manufacturer for advice. ST-NCP-AS-WP

Two-wire connection is required via the loop’s SIG+ and -S wires.

NITTAN (UK) LTD - BRINGING STYLE INTO FIRE DETECTION SYSTEMS


DIMENSIONS ST-H-AS
ST-I-AS/ST-P-AS
15mm 15mm

35mm 63mm

104mm 104mm

30mm
Back Box
ST-NCP-AS
FIRE

86mm
86mm
BREAK GLASS

PRESS HERE

86mm
20mm 32mm
Key switch location here

60mm
ST-NCP-ASWP

M20

124mm

TECHNICAL SPECIFICATION Compatible ‘AS’ Devices:-


Model: ST-I-AS/ST-P-AS/ST-H-AS
Part No: - 81000 ST-I-AS, 81100 ST-P-AS, ST-NCP-AS - Addressable call point.
81200 ST-H-AS ST-NCP-AS-WP - Addressable call point (WP).
Voltage: - 24v d.c. +/- 10%. OCM-AS2 - Addressable output module.
Operating Current: - Monitoring 200 µamps MCM-AS3 - Addressable IP/OP module.
Fire alarm (LED on) 3mA. SCM-AS3 - Addressable sounder module.
Signal Current: - 40mA (nominal) NAM-AS2 - Addressable IP module.
Address Setting: - 8 bits (presettable SCI-5 - Short circuit isolator.
Sensor Type Data: - 2 bit fixed. SCI-6 - Short circuit isolator.
Operating Temp.: - -10 deg.C to +50 deg.C.. VCT-03-NT-AS - Addressable Sounder (Base).
Sensitivity: - BS 5445/EN54 Part 7. (ST-I/ST-P-AS) VCT-03-NT-AS - Addressable Sounder c/w
BS 5445/EN54 Parts 5 & 8 (ST-H-AS) VCT-03-CP Cap
Charge Time: - 20 seconds. VPR-SA2-NTAS - Addressable Sounder (IP65).
Mass: - 108g ST-I-AS, 114g ST-P-AS,
101g ST-H-AS all excluding base. Note:- MCM-AS3 and SCM-AS3 will require a
Compatible Base: - STB-4 series 24v d.c. power supply.
Relative Humidity: - RH95%.
FOR FURTHER INFORMATION PLEASE CONSULT THE RELEVENT INSTRUCTION MANUAL
©. In pursuance of our policy of continuous product improvement, we reserve the right to change the specification without prior notice.

NITTAN (UK) LTD


Hipley Street, Old Woking, Surrey. GU22 9LQ. ENGLAND TEL: +44 (0)1483 769555 FAX: +44 (0)1483 756686
Web Site: www.nittan.co.uk E-mail: [email protected], [email protected]
NITTAN (UK) LTD
SENSORTEC - ‘AS’ MODULES
INPUT MODULE MODELS: NAM-AS2(BOX), NAM-AS(PCB)
The NAM-AS2 Addressable Module is designed to collect a fire signal from a normally open clean contact
device such as a sprinkler flow switch or similar. This module is available in either an IP55 enclosure or PCB
only.This module operates on two wires, the Sig+ and -S loop cable and does not require an external power
supply.

Considerable cost savings will be achieved as there is no need to provide additional power supply cabling.

Please refer to Instruction Manual NISM/NAM2/01 for further information on the NAM-AS2.

OUTPUT CONTROL MODULE MODEL: OCM-AS2


The OCM-AS2 is designed to perform a relay output control function via a NO/NO/C relay from an Analogue-
Addressable Fire Detection System.

As per the NAM-AS2 this module operates on two wires, the Sig+ and -S loop cable and does not require
an external power supply.

Please refer to Instruction Manual NISM/OCM2/01 for further information on the OCM-AS2.

MONITOR/CONTROL UNIT MODEL: MCM-AS3


The MCM-AS3 is an input and output module which is designed, together with an external
24V d.c. supply, to operate on the detection signalling loop of an analogue-addressable fire detection
system.

The MCM-AS3 may be used for a variety of purposes such as monitoring a zone of conventional detec-
tors and at the same time controlling fire doors, plant or smoke ventilators via the on board VFCO relay.

Please refer to Instruction Manual NISM/MCM3/01 for further information on the MCM-AS3.

SOUNDER CONTROL MODULE MODEL: SCM-AS3


The SCM-AS3 module is designed, together with an external 24V d.c. supply, to control a group of bells
or sounders on the detection signalling loop of an analogue-addressable fire detection system.

The sounder circuit is monitored with an end of line resistor, just as a conventional sounder circuit, and can
drive up to 500mA of sounder load. Polarised sounders are required, or a blocking diode should be used.

Please refer to Instruction Manual NISM/SCM3/01 for further information on the SCM-AS3.

SHORT CIRCUIT ISOLATOR MODEL: SCI-5 (BASE)


The SCI-5 (Base) Short Circuit Isolator is designed for use within Nittan (UK)'s SENSORTEC-
ANALOGUE fire alarm systems

By using short circuit isolators on the loop, the section of wiring containing the short may be isolated
from the remainder of the loop therfore limiting the extent of the disablement to only the cable between
two adjacent short circuit isolators. The remainder of the loop will still continue to function as normal.

Ideally short circuit isolators should be fitted wherever the loop crosses a fire compartment zonal
boundary, also on either side of critical devices such as sounder control modules and at the beginning
and at the end of the loop.

SHORT CIRCUIT ISOLATOR MODEL: SCI-4 (BOX)


The SCI-4 is identical in operation to the SCI-3 however this model the PCB is mounted in an IP55
enclosure which inludes 8 x 20mm knockouts.

In addition to the IP55 housing the SCI-4 incorporates two yellow LED indicators which are visible
through the enclosure and indicate the direction of the short circuit fault condition.

A new version of the SCI-4 called SCI-6, will be available at the end of 2001. The new short circuit
isolator will be mountable on a single gang, standard electrical, surface mounting type box.

Further information will be available on the SCI-6 later in 2001..

NITTAN (UK) LTD - BRINGING STYLE INTO FIRE DETECTION SYSTEMS


SENSORTEC - ‘AS’ ADDRESSABLE SOUNDERS

VCT-03-NT-AS VCT-NTAS-CP
c/w STB-4 Base c/w VCT-03-CP-W

BASE MOUNTED ADDRESSABLE SOUNDER MODEL: VCT-03-NT-AS


The VCT-03-NT-AS is a loop powered sounder and is compatible with Nittan ‘AS’ protocol control panels. The VCT-03-NT-AS is supplied
complete with a STB-4 base, the base is also pre-wired to the addressable sounder allowing a quick and easy installation.

The addressable sounder base gives systems designers a new low profile design, while giving the installers reduced installation time with it’s
wide cable access and rising clamp terminals.

Supply Voltage: 24V d.c., Current: c. 10mA, Sound Output: 90dB @ 1m, IP43 rated.

WALL MOUNTED ADDRESSABLE SOUNDER MODEL: VCT-NTAS-CP c/w RED OR WHITE CAP
The VCT-NTAS-CP is a loop powered sounder and is compatible with Nittan ‘AS’ protocol control panels.

The addressable wall sounder c/w cap gives systems designers a new low profile design, while giving the installers reduced installation time
with it’s wide cable access and rising clamp terminals.

The VCT-NTAS-CP can be supplied with either a white or red cap depending on your fire system requirments.

ACCESSORIES FOR THE VCT-NTAS-CP


VCT-03-CP-W White Vector Cover Plate
VCT-03-CP-R Red Vector Cover Plate

VPR-SA2-NTAS(R)

VPR-SA2-NTAS(W)

WEATHERPROOF ADDRESSABLE SOUNDER MODEL: VPR-SA2-NTAS


The VPR-SA2-NTAS is a loop powered, weatherproof, surface mounted sounder and is compatible with Nittan ‘AS’ protocol control
panels.

The VPR-SA2-NTAS addressable 'AS' protocol sounder has been designed for applications where low current consumption relative to
high sound output is required.

With an operating frequency of 800-1000Hz each sounder provides sound within the frequency range specified in BS5839. The sounder
also has a wide operating voltage range of 8-35V d.c..

Different tones are available by selecting either Warble, Sweep, or Continuous via the jumper fitted to the PCB.

A second stage alarm may be switched, via the control panel, so the Pips tone will override the tone selected.

The sounder casing material is ABS and is supplied in either red or white colours. (Note white special order).

The sounder is supplied complete with its own mounting base which comes with marker points for drilling two M20 cable gland entries.

Supply Voltage: 24V d.c., Current: <12mA, Sound Output: 103dB @ 1 metre, IP65 rated.

FOR FURTHER INFORMATION PLEASE CONSULT THE RELEVENT INSTRUCTION MANUAL


©. In pursuance of our policy of continuous product improvement, we reserve the right to change the specification without prior notice.

NITTAN (UK) LTD


Hipley Street, Old Woking, Surrey. GU22 9LQ. ENGLAND TEL: +44 (0)1483 769555 FAX: +44 (0)1483 756686
Web Site: www.nittan.co.uk E-mail: [email protected], [email protected]
NITTAN (UK) LTD
CONVENTIONAL CONTROL PANELS
FOUR ZONE CONVENTIONAL CONTROL PANEL MODEL: CF/4Z
The CF/4Z panel is a 2 to 4 zone expandable conventional control panel. The CF/4Z is supplied with one
CF/EXP210 two zone card and is expandable to four zones by adding an additional CF/EXP210 double zone
expansion card. It is possible to connect up to four zones of 24V Nittan conventional detectors, allowing a
maximum of 20 detectors per zone with a total of up to 80 detectors.

The control panel conforms to prEN54 parts 2 and 4 and the main circuit board is built almost entirely using SMT
components. The circuitry is housed in a strong metal casing, there are clear indication status functions and
simplified labelling for connection of the cables to the main circuit PCB.

1-10 ZONE CONVENTIONAL CONTROL PANEL MODEL: CF/210 & 11-20 ZONE
CONVENTIONAL CONTROL PANEL MODEL: C/CF210
The CF/210 fire detection panel is a 1-10 and/or 1-20 detection zone suitable for connection of 24V Nittan
conventional detectors. The CF/210 1-10 zone panel is supplied as standard with a CF/EXP210 double zone
expansion zone card, the CF/210 may supplied as double enclosure and together with a C/CF210 11-20
zone expansion card allows an additional 10 zones allowing a maximum of 20 zones.

The control panel conforms to prEN54 parts 2 and 4 and the main circuit board is built almost entirely using
SMT components. The circuitry is housed in a strong metal casing, there are clear indication/status
functions and simplified labelling for connection of the cables to the main motherboard.

FEATURES:-
Indications for FAULT, ALARM and ZONES ISOLATED.
Indications for: Mains power, battery
disconnection, battery low, general fault, siren fault,
common isolate, common fire alarm, pre-alarm and day/night Internal Buzzer indicating fire and faults.
function status of the panel
Relay outputs for ALARM, FAULT and PRE-ALARM
RESET, SILENCE, EVACUATE and DAY/NIGHT functions with NO/NC volt free contacts

Engineer Entry Codes Levels 1 and 2 Monitored output for connecting a 24V Sounder or Bells etc.

Internal connection to a CP8/REL relay card (optional) for installing 24V d.c. output for auxiliary power supply
UNIREL/24 circuits (max. 8) to repeat conditions of the following:-
ALARM zone 1, ALARM zone 2, FAULT zone 1, FAULT zone 2, Zonal Isolation of a single zone
Isolate zone 1, Isolate zone 2, AND function activated, OR function
activatation. AND function and OR functions

ER BUDGET RANGE 2, 4 & 8 ZONES


The ER range of fire detection control panels have been designed with cost effectiveness in mind. The basic
concept is to provide a BS5839 part 4 and BS5839 Part 1 (head removal) fully compliant panel with a wide range
of functions.

Features: Part Numbers:


VFCO contacts for Fire and Fault ER-2 - 2 Zone Panel
1.2 Amp power supply ER-4 - 4 Zone Panel
2 x Sounder circuits ER-8 - 8 Zone Panel

EN RANGE 2, 4 & 8 ZONES


The EN range of fire detection control panels have been designed with cost effectiveness in mind. The basic
concept is to provide an EN54 Parts 2 and 4 and BS5839 Part 1 (head removal) fully compliant panel with a wide
range of functions.

Features:
VFCO contacts for Fire and Fault
3 Amp power supply
2 x Sounder circuits
Coded Access Part Numbers:
One man walk test facility EN-2 - 2 Zone Panel
Class change input EN-4 - 4 Zone Panel
Evacute input EN-8 - 8 Zone Panel

NITTAN (UK) LTD - BRINGING STYLE INTO FIRE DETECTION SYSTEMS


CF/4Z 2-4 ZONE EXPANDABLE CONVENTIONAL CONTROL PANEL
325
Note: The CF/4Z
includes
1 x CF/EXP210 as
standard
BATTERY STATE BATTERY STATE
MAINS LOW DISCONNECTED FIRE ZONAL ALARM ZONAL ALARM MAINS LOW DISCONNECTED FIRE ZONAL ALARM ZONAL ALARM

ACCEPT COMMON FAULT ZONAL FAULT ZONAL FAULT ACCEPT COMMON FAULT ZONAL FAULT ZONAL FAULT

ALARM BELL ALARM BELL


DAY/NIGHT FAULT PRE-ALARM COMMON ISOLATE ZONE ISOLATE ZONE ISOLATE DAY/NIGHT FAULT PRE-ALARM COMMON ISOLATE ZONE ISOLATE ZONE ISOLATE

ZONES ZONES ZONES ZONES

1 2 3 4 1 2 3 4

304
DAY/NIGHTEVACUATION SILENCE RESET DAY/NIGHTEVACUATIONSILENCE RESET
ISOLATED ISOLATED ISOLATED ISOLATED

LEVEL 1 LEVEL 2 LEVEL 1 LEVEL 2

CF/4Z FIRE CONTROL PANEL CF/4Z FIRE CONTROL PANEL

98000534 98000534

3
13

CF210 1-10 ZONE & C/CF210 11-20 ZONE EXPANDABLE CONVENTIONAL CONTROL PANEL
Note: The CF210 C/CF210
CF210 includes
CF210 c/w C/CF210
1 x CF/EXP210 as
standard

Note: 1m connection lead included


with C/CF210
480 480

! !
303

303
1 2 3 1
4 2 3 4
5 6 7 8 5 6
9 7 8
10 9 10
! ! ! ! ! ! ! ! ! !
! ! ! ! ! ! ! ! ! !

132 132

CF210 (1-10 zones) C/CF210 (11-20 zones)

ER-2,4 & 8 AND EN-2,4 & 8 CONVENTIONAL CONTROL PANELS

ER-2,4 & 8 EN-2,4 & 8

225mm
285mm

285mm
355mm

80mm
80mm

NOTE:
2, 4 & 8 Zone panels are all
identical dimensions.

FOR FURTHER INFORMATION PLEASE CONSULT THE RELEVENT INSTRUCTION MANUAL


©. In pursuance of our policy of continuous product improvement, we reserve the right to change the specification without prior notice.

NITTAN (UK) LTD


Hipley Street, Old Woking, Surrey. GU22 9LQ. ENGLAND TEL: +44 (0)1483 769555 FAX: +44 (0)1483 756686
Web Site: www.nittan.co.uk E-mail: [email protected], [email protected]
NITTAN (UK) LTD

SENSORTEC -TWO-WIRE SYSTEM


The New SENSORTEC-TWO-WIRE conventional System provides 2, 4, 8 zones allowing
detectors, sounders, base sounders, strobes, IP/OP modules and manual call points on a
single Two-Wire zone, the panel is designed to comply with EN 54 parts 2 and 4.

The advantage of the Two-Wire system makes the installation easier therefore greatly
reducing installation costs. All control panels incorporate a tactile membrane display with
facilities for both the end user and Engineer. A simple code provides the end user with
restricted access but allows an Engineer entry to the operator and engineering functions.

All the Two-Wire control panels can be utilised as a standard conventional panel in addition to
the Two-Wire configuration. This enables a mixture of zones to be configured as Two-Wire
and other zones can be configured as standard conventional type.
8 Zone Panel

TWO-WIRE SENSORTEC BASE MODEL: STB-4SE-TW


The STB-4-TW Two-Wire base has been designed to compliment our other products in the Two-Wire
system range. This base is compatible with our SENSORTEC-CONVENTIONAL range of smoke and
heat detectors.

TWO-WIRE MANUAL CALL POINT MODEL: NCP-K470-TW


The NCP-K470-TW Two-Wire manual call point is supplied with a custom miniature PCB included in
the call point packaging therefore enabling an Engineer to convert the standard manual call point in to
Two-Wire type call point.

TWO-WIRE ZENON BEACON MODEL: ST-BEACON-TW


The beacon has been designed to complement our other products in the Two-Wire system range. The
beacon is supplied with a custom miniature PCB included in the call point packaging therefore enabling
an Engineer to convert the standard beacon in to Two-Wire system type beacon.
Specification:
Voltage: - - - 24V d.c. nominal.
Flash Energy: - - - 1.0 Joule
Lens Colour: - - - Red
Base Type: - - - Shallow Base (Red)
Average Current Consumption: - - 90mA @ 24V d.c.

TWO-WIRE WALL MOUNTING SOUNDER MODEL: VCT-03-NT-TW c/w RED OR WHITE CAP
This sounder together with the base sounder have been designed to compliment
our other products in the Two-Wire system range.
Specification:
Voltage: - - 24V d.c. nominal.
dB @1m - - 93dB @ 1m.
Start Current - - 30mA
Current Consumption - - <12mA
Tones - - Sweeping, Continuous & Alternating
IP Rating - - IP43
Cap - - Red or White VCT-03-NT-TW VCT-03-NT-TW
c/w STB-4 Base c/w VCT-03-CP Cap

TWO-WIRE BASE MOUNTING SOUNDER MODEL: VCT-03-NT-TW


This sounder together with the wall sounder have been designed to compliment our other products in the
Two-Wire system range. Note: STB-4SE-TW Two-Wire base is not supplied with the VCT-03-NT-TW.
Specification:
Voltage: - - 24V d.c. nominal.
dB @1m - - 90dB @ 1m.
IP Rating - - IP43

TWO-WIRE INPUT & OUTPUT MODEL: ST-MOD-TW


The ST-MOD-TW unit provides a means of interfacing auxiliary fire peripherals, e.g. door closures, input/output switching etc. via the
Two-Wire standard zone cables. The unit provides 3 x input condition and 2 x sets of VFCO.
Please see the reverse of this leaflet for connection details.

NITTAN (UK) LTD - BRINGING STYLE INTO FIRE DETECTION SYSTEMS


WIRING CONNECTIONS FOR NITTAN TWO-WIRE SYSTEM

STANDARD CONVENTIONAL ZONE

Zone +IN & +OUT


L+
3 4 +
Note:
If using remote LED indicator a 220R

1 5 RIL_ resistor must be fitted in series with LED.


ZONE OUT
6 Max. current through
5 = 100mA @ 24V d.c.

C_ Zone -IN Zone -OUT

STB-4SDR(470) Shottky Diode/


Resistor Base

TWO-WIRE CONVENTIONAL ZONE

Zone +IN & +OUT


L+
3 + Note:
+
-
2 RIL_ If using remote LED indicator a 220R

1 5 resistor must be fitted in series with LED.


Note: Connections to any standard
ZONE OUT base sounder.
+ 6 Max. current through
5 = 100mA @ 24V d.c. Nittan part number:
- VCT-03-NT, Base Sounder
_ Zone -IN Zone -OUT
C
STB-4SE-TW Two-Wire Base

TWO-WIRE MANUAL CALL POINT


ZONE
+

ZONE
+
2-Wire Module
470R
Call ZONE OUT
ZONE IN Point

ZONE ZONE
- -

TWO-WIRE INPUT/OUTPUT MODULE


GLOBAL VOLTAGE LOCAL VOLTAGE
Note: ALARM NORMALLY ISOLATED ALARM NORMALLY CLOSED SWITCHED 24V FREE CONTACT OUTPUT FREE CONTACT OUTPUT
CLOSED INPUT SUPPLY INPUT FAULT INPUT SUPPLY OUTPUT (Rated 1Amp) (Rated 1 Amp)
To operate isolated alarm external
24Vd.c. is required to terminals
provided

INPUTS SW SUPPLY OUTPUTS


ALARM N/C A24V ATV1 FLT N/C 24V 0V GN/C GP GN/O LN/C LP LN/O
LOCAL DETECTOR
REMOTE -IN
Z+ REM-

+
ZONE OUT
ZONE IN

Z+

+ ZONE OUT
ZONE IN -
Z-

-
Z-

Note:
Localvoltage free contact output is
Note: Note: Note: active when local detector remote
Use remote -IN only if local Switched 24V supply output is Global voltage free contact output -IN is active to clear this output a
voltage free contacts required active only when the zones alarms is active only when the zone panel reset condition must occur.
are active. alarms are active.

FOR FURTHER INFORMATION PLEASE CONSULT THE RELEVENT INSTRUCTION MANUAL


©. In pursuance of our policy of continuous product improvement, we reserve the right to change the specification without prior notice.

NITTAN (UK) LTD


Hipley Street, Old Woking, Surrey. GU22 9LQ. ENGLAND TEL: +44 (0)1483 769555 FAX: +44 (0)1483 756686
Web Site: www.nittan.co.uk E-mail: [email protected], [email protected]
NITTAN (UK) LTD

ANALOGUE ADDRESSABLE CONTROL PANELS,


SINGLE AND TWO LOOP
AFP-701/N, 1-2 LOOP ANALOGUE-ADDRESSABLE CONTROL PANEL
INTRODUCTION
Offering high performance at a competitive price, the AFP one or two
loop (126 devices per loop) analogue addressable fire panel supports
Nittan protocol.

Fully compliant with EN54 Parts 2 and 4, it's wide range of features
include 16 zonal alarm LEDs (expandable to 32), four separate inde-
pendently programmable sounder circuits and an integral 24V 3amp
switch mode power supply. The AFP can be programmed on-site via
tactile switches on the panel front or via an easy to use, low-cost upload/
download PC programme.

Other features include a 999 event memory, delay timer and phased
evacuation facilities, sophisticated test and maintenance facilities and
a comprehensive ‘auto-learn' facility allowing the panel to self-configure
to devices connected to the loop.

SURVEYOR ELITE SINGLE LOOP ANALOGUE ADDRESSABLE PANEL


The Surveyor Elite analogue addressable control panel has been
designed to provide compact, competitively priced, single loop
control panel. The modern robust enclosure ensure it complements
current design interior designs, while the comprehensive specifica-
tion offers compatibility with a range of applications.

* 167 Nittan AS Devices on a single loop

* 16 Zonal LEDs

* 100 Event Memory

* 40 Character of custom text per device

* Site programmable via panel or download software

* Optional panel mounted high speed thermal printer

* Designed to EN54-2 & EN54-4 standards


* Space for 7 Amp Hr batteries
* CE marked to comply with EMC and low
voltage directive * 2 Common sounder circuits

* Back lit, high resolution, LCD display * Fire, fault, and remote VFCO contacts

Short circuit protected loop driver * RS485 2 wire repeater panels

* Integral 3 Amp switch mode PSU * Flush mounting bezel avaialble

NITTAN (UK) LTD - BRINGING STYLE INTO FIRE DETECTION SYSTEMS


THIS PAGE IS INTENTIONALL Y BLANK
PLEASE REFER TO THE RELEVENT
INSTRUCTION MANUALS FOR THE AFP-701/N
AND SURVERYOR ELITE CONTROL PANELS.

FOR FURTHER INFORMATION PLEASE CONSULT THE RELEVENT INSTRUCTION MANUAL


©. In pursuance of our policy of continuous product improvement, we reserve the right to change the specification without prior notice.

NITTAN (UK) LTD


Hipley Street, Old Woking, Surrey. GU22 9LQ. ENGLAND TEL: +44 (0)1483 769555 FAX: +44 (0)1483 756686
Web Site: www.nittan.co.uk E-mail: [email protected], [email protected]
NITTAN (UK) LTD

ZX ANALOGUE ADDRESSABLE CONTROL PANELS


& INTERFACE CARDS (Networking)
ZXa - ANALOGUE CONTROL PANEL (1-2 loop), ZX1 (1-2 Loop), (Non-Networkable)
The ZXa/1 control panels are flexible, expandable analogue addressable fire panels. The ZXa/1 is expandable
from 1 to 2 loops by means of plug-in loop driver cards, allowing a total of 252 devices over two loops. It is also
possible to network the ZXa only and ZXe range of control panels as standard.

These panels are designed to be aesthetically pleasing with a contrasting membrane facia incorporating a tactile
alpha numeric keypad making it fully on-site programmable. The high quality steel enclosure may be fitted with an
optional glass window and flush mounting bezel. The main display is via an 80 character, back lit LCD with 20
zonal LED fire and fault indicators. There is also a 2 x 7 segment LED display for easy identification of Fire zone.

ZXe - ANALOGUE CONTROL PANEL (1-5 loop)


The ZXe analogue-addressable control panel is a flexible, expandable analogue-addressable fire panels. Up
to 12 x standard ZXa or ZXe panels can be networked together with any panel designated as a master control
panel. Up to 99 panels can be networked using dedicated (ZXe) Master and sub-Master
panels.

The ZXe panel designed to be aesthetically pleasing with a contrasting membrane facia incorporating a non-
tactile alpha numeric keypad making it fully on-site programmable. The high quality steel enclosure may be
fitted with an optional glass door or flush mounting kit as required.

The main display is via an 80 character, back lit LCD with 20 zonal LED fire and fault indicators expandable to
a maximum of 80 fire and fault LEDs.

EXP-044 LOOP DRIVER CARD


A single loop plug in module for expansion of the ZXa 1-2 panel and ZXe 1-5 range of fire control panels for
use up to 126 Nittan devices may be connected to one EXP-044 loop card.

EXP-004 (RS485) & EXP-005 (RS232) COMMUNICATION MODULES


The ZX range of panel’s require either a RS485 or RS232 module to be fitted to the appropriate port to
allow serial communications for networking and peripherals. These optically isolated modules plug into one
of three available serial ports on the panel’s motherboard. The 485 module supports 2 wire RS485 multi-
drop transmission between networked panels, repeaters, serial peripherals and computer graphics system
upto a total length of 1200 metres per channel.

EXP-014 4 WAY RELAY CARD


The 4 way relay card connects to the panel via the RS485 peripheral port (D). The ‘Auto-Learn’ facility in the
commissioning software will automatically add each output to the list of relay outputs on the panel. Each of these
outputs can be assigned to any zone on the system and be individually programmed for normal, delayed, or double
knock operation. The 485 peripheral address (from 1 to 31) is set via an on-board DIP switch and other peripher-
als such as repeaters can be ‘daisy chained’ together on the same line.

EXP-015 4 WAY SOUNDER CARD


The 4 way sounder card connects to the panel via the RS485 peripheral port (D). The ‘Auto-Learn’ facility in the
commissioning software will automatically add each circuit to the list of sounder outputs on the panel. Each of these
circuits can be assigned to any zone on the system and be individually programmed for normal, pulsed, delayed, or
double knock Each sounder circuit is monitored for open and short circuits, with individual LED indication on the card
for the status of each circuit. An external fault input is available for monitoring a pair of external clean contacts. The
485 peripheral address can be set from 1 to 15 via an on-board DIP switch and other peripherals such as repeaters
can be ‘daisy chained’ together on the same line.

ALSO AVAILABLE....

EXP-065 MIMIC DRIVER CARD EXP-069-20 & EXP-069-60 EXP-029


The EXP-065 mimic driver card is a 20 & 60 ZONE LED EXTENDER CARD 8 WAY INPUT CARD
switchable 1-40, 41-80, 81-120 The zone extender will increase the The 8 way relay input card communicates with
zonal LED mimic driver card number of fire & fault zones the control panel via the RS485
inclusive of it’s own CPU. displayed from 20 to 40 & peripheral port (D).
from 20 to 80 on a ZXe panel.

NITTAN (UK) LTD - BRINGING STYLE INTO FIRE DETECTION SYSTEMS


ZX-R4b & ZX-R5b REPEATER PANELS
A range of repeater panels, which display any Fire and Fault messages
simultaneously with a local fire control panel are available for use with either the ZXa
or ZXe analogue addressable control panel.

Up to 15 of these units can be connected to the peripheral D port (optional EXP-004


RS485 module required) of a local fire control panel and can be ‘daisy chained’
together on the same circuit along with other peripherals such as 4-way sounder
cards and 4-way relay cards, up to a maximum of 126 addresses. ZX-R4b

An individual flush mounting bezel is also available.

The ZX-R4b features a LCD only plus 6 dual status LED’s. The ZX-R5b is as per
ZX-R4b with the additional following two-way features: Accept, Silence/Resound,
Reset & Evacuate control keys and there is also a keyswitch which is provided to
enable/disable the two-way features/controls.

Both the ZX-R4b and ZX-R5b are supplied in plastic enclosures.

PART NUMBERS:- ZX-R5b


ZX-R4b - LCD Only Repeater
ZX-R5b - Two Way Repeater

OPTIONAL EQUIPMENT:-
EXC-014: Flush mounting bezel for ZX-R4b/R5b

MULTI MASTER MULTI SLAVE NETWORK


1 2 13
ZXe Master Submaster Slaves Slaves
220V
ZXe
1 220V
ZXe
220V
ZXe
220V
ZXa
(1-5 LOOP) (1-5 LOOP) (1-5 LOOP) Cable type
Beldon (1-2 LOOP)
Port B Port C Port B Port C Port C 8760 Port C
screened twisted pair
EXP-004 EXP-004 EXP-004 EXP-004 EXP-004 EXP-004
or
RS485 RS485 RS485 RS485 RS485 FP200 Gold, RS485
Interface Interface Interface Interface Interface 2 Core Screened. Interface
PCB PCB PCB PCB PCB PCB
RS485 RS485
EXP-043-485 - GRAPHICS
SOFTWARE AND
INTERFACE
EXP-043-485 MAX. DISTANCE 1200m

Submaster Slaves Slaves


12 220V
ZXe
220V
ZXe
220V
ZXa
Cable type
(1-5 LOOP) (1-5 LOOP) Beldon (1-2 LOOP)
Port C Port C 8760
screened twisted pair
Port C
EXP-004 EXP-004 or EXP-004
Cable type Beldon 8760 RS485 RS485 FP200 Gold, RS485
screened twisted pair Interface Interface 2 Core Screened. Interface
or PCB PCB PCB
FP200 Gold, 2 Core
RS485 RS485
Screened.

220V PERIPHERAL DEVICES ON RS485 CIRCUIT


ZXe
(1-5 LOOP)
Port B Port D Port C
EXP-004 EXP-004 EXP-004
RS485 RS485 RS485
Interface Interface Interface
PCB PCB PCB
EXP-015
EXP-016 24Vd.c.
4 way Sounder PCB MAX. DISTANCE 1200m
3A PSU (Address 1-15)
EXP-014 EXP-029 RS485 ZX-R4B
24V ZX-R5B
24V EXP-065 24V
Cable type Beldon 8760 4 way Relay PCB 8 way Input PCB
Repeater Panel Repeater Panel Mimic Driver
screened twisted pair (Address 1-31) (Address 1-126)
or
FP200 Gold, 2 Core OPTIONAL
Screened. 24Vd.c.
EXP-016 24Vd.c.

3A PSU

FOR FURTHER INFORMATION PLEASE CONSULT THE RELEVENT INSTRUCTION MANUAL