HVAC LOAD CALCULATION - E20 FORM SHEET INPUT VALUES ARE TO BE GIVEN IN BLUE COLOR BOXES ONLY
PROJECT HSSC FLOOR Ground Floor
LOCATION KOTA SPACE REFERENCE AUTOCLAVE WASHING AREA
CLIENT AREA ( SqFt) (WxH) 88.14
CONSULTANT Falce Ceiling Height (Ft) 9.84
Volume (CuFt) 867.29
Area or Sun Gain or Factor Estimate for Summer
Item Btu/Hour Watts
Quantity Temp. Diff. (U) Design Conditions DB (°F) WB (°F) RH (%) HR (Gr/Lb)
ROOM HEAT Q= U*A*ΔT Ambient(Out Side) 113.00 75.00 17.00 38.00
ROOM SENSIBLE HEAT Room (InDoor) 75.00 55.00 40.00
Solar Gain - Glass Area ΔT U Difference Δ 38.00 75.00 38.00 2.00
Glass - N SqFt x x 0.00
Glass - NE SqFt x x 0.00
Glass - E SqFt x x 0.00 By Pass Factor (BF) = 0.12
Glass - SE SqFt x x 0.00 Contact Factor (CF = 1 - BF) = 0.88
Glass - S SqFt x x 0.00 CFM Ventilation
Glass - SW SqFt x x 0.00 CFM Per Person 5.00 No = 2.00 = 10.00
Glass - W SqFt x x 0.00 CFM Per SqFt 0.18 Sqft x 88.14 = 15.86
Glass - NW SqFt x x 0.00 Air Change Per Hour (CFM) = 12.00
Skylight SqFt x x 0.00 CFM [Link] 867.29 x 12.00 x1/60 = 173.46
Solar & Transmission Gain - Walls & Roof CFM Infiltration
Wall - N SqFt x F x 0.00 Swinging x cfm/door = 0.00
Wall - NE SqFt x F x 0.00 Revolving Doors (People) x cfm/door = 0.00
Wall - E SqFt x F x 0.00 Open Doors x 1.00 cfm/door = 0.00
Wall - SE SqFt x F x 0.00 Crack (feet) x cfm/ft = 0.00
Wall - S SqFt x F x 0.00 0.00
Wall - SW SqFt x F x 0.00 Supply CFM from Machine
Wall - W SqFt x F x 0.00 Effective Room Sensible Heat Factor =
Wall - NW 79.07 SqFt x 123.00 F x 0.12 1,167.07 Effective Room Sensible Heat/Eff Room Total Heat = 1.00
Roof 88.14 SqFt x 123.00 F x 0.05 487.85 Apparatus Dew Point (ADP)
Transmission Gain - Except Walls & Roof Indicated ADP (F) =
All Glass SqFt x 38.00 F x 0.00 Selected ADP (F) = 54.60
Partition 186.99 SqFt x 33.00 F x 0.50 3,085.34 Dehumidified Rise
Ceiling 88.14 SqFt x 33.00 F x 0.05 130.89 (Room DB - ADP) x CF = 17.95
Floor SqFt x F x 0.00 DEHUMIDIFIED AIR QUANTITY
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat = 5,398.52 CFM
Infiltration CFM x 38.00 [Link] x 1.08 0.00 Dehumidified Rise x 1.08
Outside Air 25.86 CFM x 38.00 x 127.38
Internal Heat = 2,537.30 L/s
People 2.00 Nos. x 230.00 Btu/Hour Per Person 460.00 TOTAL HEAT CAPACITY
Lighting 88.14 SqFt x 1.02 W/SqFt x 3.41 306.56 Grand Total Heat = 9.08 TR
Equipments 1.00 25,000.00 Watts x 3.41 85,250.00
Power kW/Hp x 0.00
Sub Total 91,015.09
Factor 5-15% 13,652.26
Effective Room Sensible Heat 1,04,667.35 1.00 SENSIBLE HEAT CAPACITY
ROOM LATENT HEAT Grand Sensible Heat = 9.08 TR
Infiltration 0.00 CFM x 2.00 Gr/Lb x 0.68 0.00 12,000.00
Outside Air 25.86 CFM x 2.00 Gr/Lb x BFx0.68 4.22
People 2.00 Nos. x 120.00 Btu/Hour Per Person 240.00
Sub Total 235.78
Factor 2.5 - 5% 11.79
Effective Room Latent Heat 247.57 2.00
EFFECTIVE ROOM TOTAL HEAT 1,04,914.92
OUTSIDE AIR HEAT
Sensible 25.86 CFM x 38.00 F(TD) x CF x 1.08 934.12 3.00
Latent 25.86 CFM x 2.00 Gr/Lb x CF x 0.68 30.96 4.00
OUTSIDE AIR TOTAL HEAT 903.16 Notes:
GRAND SUB-TOTAL HEAT 1,05,818.08
Factor 1 - 3% 3,174.54
GRAND TOTAL HEAT 1,08,992.63
TMBH 108.99
TKW 31.61
TSMBH 1,05,601.47
TSKW 30,624.43
TONS=GRAND TOTAL HEAT/12000 9.08