Heat Load Analysis for HVAC Design

The HVAC load calculation document outlines the parameters for the autoclave washing area on the ground floor of a project in Kota. It details input values, heat gain calculations, and total heat capacity, resulting in a grand total heat of 108,992.63 Btu/hr, equivalent to 9.08 tons. The document specifies various factors such as sensible and latent heat, ventilation, and equipment contributions to the overall HVAC load.

Uploaded by

Vikrant Rajput
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
100 views1 page

Heat Load Analysis for HVAC Design

The HVAC load calculation document outlines the parameters for the autoclave washing area on the ground floor of a project in Kota. It details input values, heat gain calculations, and total heat capacity, resulting in a grand total heat of 108,992.63 Btu/hr, equivalent to 9.08 tons. The document specifies various factors such as sensible and latent heat, ventilation, and equipment contributions to the overall HVAC load.

Uploaded by

Vikrant Rajput
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

HVAC LOAD CALCULATION - E20 FORM SHEET INPUT VALUES ARE TO BE GIVEN IN BLUE COLOR BOXES ONLY

PROJECT HSSC FLOOR Ground Floor


LOCATION KOTA SPACE REFERENCE AUTOCLAVE WASHING AREA
CLIENT AREA ( SqFt) (WxH) 88.14
CONSULTANT Falce Ceiling Height (Ft) 9.84
Volume (CuFt) 867.29
Area or Sun Gain or Factor Estimate for Summer
Item Btu/Hour Watts
Quantity Temp. Diff. (U) Design Conditions DB (°F) WB (°F) RH (%) HR (Gr/Lb)
ROOM HEAT Q= U*A*ΔT Ambient(Out Side) 113.00 75.00 17.00 38.00
ROOM SENSIBLE HEAT Room (InDoor) 75.00 55.00 40.00
Solar Gain - Glass Area ΔT U Difference Δ 38.00 75.00 38.00 2.00
Glass - N SqFt x x 0.00
Glass - NE SqFt x x 0.00
Glass - E SqFt x x 0.00 By Pass Factor (BF) = 0.12
Glass - SE SqFt x x 0.00 Contact Factor (CF = 1 - BF) = 0.88
Glass - S SqFt x x 0.00 CFM Ventilation
Glass - SW SqFt x x 0.00 CFM Per Person 5.00 No = 2.00 = 10.00
Glass - W SqFt x x 0.00 CFM Per SqFt 0.18 Sqft x 88.14 = 15.86
Glass - NW SqFt x x 0.00 Air Change Per Hour (CFM) = 12.00
Skylight SqFt x x 0.00 CFM [Link] 867.29 x 12.00 x1/60 = 173.46
Solar & Transmission Gain - Walls & Roof CFM Infiltration
Wall - N SqFt x F x 0.00 Swinging x cfm/door = 0.00
Wall - NE SqFt x F x 0.00 Revolving Doors (People) x cfm/door = 0.00
Wall - E SqFt x F x 0.00 Open Doors x 1.00 cfm/door = 0.00
Wall - SE SqFt x F x 0.00 Crack (feet) x cfm/ft = 0.00
Wall - S SqFt x F x 0.00 0.00
Wall - SW SqFt x F x 0.00 Supply CFM from Machine
Wall - W SqFt x F x 0.00 Effective Room Sensible Heat Factor =
Wall - NW 79.07 SqFt x 123.00 F x 0.12 1,167.07 Effective Room Sensible Heat/Eff Room Total Heat = 1.00
Roof 88.14 SqFt x 123.00 F x 0.05 487.85 Apparatus Dew Point (ADP)
Transmission Gain - Except Walls & Roof Indicated ADP (F) =
All Glass SqFt x 38.00 F x 0.00 Selected ADP (F) = 54.60
Partition 186.99 SqFt x 33.00 F x 0.50 3,085.34 Dehumidified Rise
Ceiling 88.14 SqFt x 33.00 F x 0.05 130.89 (Room DB - ADP) x CF = 17.95
Floor SqFt x F x 0.00 DEHUMIDIFIED AIR QUANTITY
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat = 5,398.52 CFM
Infiltration CFM x 38.00 [Link] x 1.08 0.00 Dehumidified Rise x 1.08
Outside Air 25.86 CFM x 38.00 x 127.38
Internal Heat = 2,537.30 L/s
People 2.00 Nos. x 230.00 Btu/Hour Per Person 460.00 TOTAL HEAT CAPACITY
Lighting 88.14 SqFt x 1.02 W/SqFt x 3.41 306.56 Grand Total Heat = 9.08 TR
Equipments 1.00 25,000.00 Watts x 3.41 85,250.00
Power kW/Hp x 0.00
Sub Total 91,015.09
Factor 5-15% 13,652.26
Effective Room Sensible Heat 1,04,667.35 1.00 SENSIBLE HEAT CAPACITY
ROOM LATENT HEAT Grand Sensible Heat = 9.08 TR
Infiltration 0.00 CFM x 2.00 Gr/Lb x 0.68 0.00 12,000.00
Outside Air 25.86 CFM x 2.00 Gr/Lb x BFx0.68 4.22
People 2.00 Nos. x 120.00 Btu/Hour Per Person 240.00
Sub Total 235.78
Factor 2.5 - 5% 11.79
Effective Room Latent Heat 247.57 2.00
EFFECTIVE ROOM TOTAL HEAT 1,04,914.92
OUTSIDE AIR HEAT
Sensible 25.86 CFM x 38.00 F(TD) x CF x 1.08 934.12 3.00
Latent 25.86 CFM x 2.00 Gr/Lb x CF x 0.68 30.96 4.00
OUTSIDE AIR TOTAL HEAT 903.16 Notes:
GRAND SUB-TOTAL HEAT 1,05,818.08
Factor 1 - 3% 3,174.54
GRAND TOTAL HEAT 1,08,992.63
TMBH 108.99
TKW 31.61
TSMBH 1,05,601.47
TSKW 30,624.43
TONS=GRAND TOTAL HEAT/12000 9.08