Data sheet 6AG1522-5HH00-7AB0

SIPLUS S7-1500 DQ 16x230VAC 2A RLY based on 6ES7522-5HH00-0AB0 with


conformal coating, -40…+70 °C, start up -25 °C, digital output module relay 16
channels in groups of 2; 4 A per group; diagnostics
General information
Product type designation DQ 16x 230 V AC/2 A ST (relay)
Firmware version
● FW update possible Yes
Product function
● I&M data Yes; I&M0 to I&M3
● Isochronous mode No
● Prioritized startup Yes
Operating mode
● DQ Yes
● DQ with energy-saving function No
● PWM No
● Oversampling No
● MSO Yes
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Input current
Current consumption, max. 150 mA
Power
Power available from the backplane bus 0.8 W
Power loss
Power loss, typ. 5W
Digital outputs
Type of digital output Relays
Number of digital outputs 16
Current-sinking Yes
Current-sourcing Yes
Digital outputs, parameterizable Yes
Short-circuit protection No
Controlling a digital input Yes
Size of motor starters according to NEMA, max. 5
Switching capacity of the outputs
● on lamp load, max. 50 W (230 V AC), 5 W (24 V DC)
Output current
● for signal "1" rated value 2A
● for signal "1" permissible range, min. 10 mA; 10 V
● for signal "1" permissible range, max. 2 A; thermal continuous current
● for signal "0" residual current, max. 0A
Parallel switching of two outputs
● for logic links Yes
● for uprating No
● for redundant control of a load Yes
Switching frequency
● with resistive load, max. 1 Hz
● with inductive load, max. 0.5 Hz
● on lamp load, max. 1 Hz
Total current of the outputs

6AG15225HH007AB0 Subject to change without notice


6/8/2023
Page 1/3 © Copyright Siemens
● Current per channel, max. 2 A; see additional description in the manual
● Current per group, max. 2 A; see additional description in the manual
● Current per module, max. 32 A; see additional description in the manual
Relay outputs
● Number of relay outputs 16
● Rated supply voltage of relay coil L+ (DC) 24 V
● Current consumption of relays (coil current of all relays), 150 mA
max.
● external protection for relay outputs Miniature circuit breaker B10 / B16
● Contact connection (internal) No
● Number of operating cycles, max. see additional description in the manual
● Relay approved acc. to UL 508 No
Switching capacity of contacts
— with inductive load, max. 2 A; see additional description in the manual
— with resistive load, max. 2 A; see additional description in the manual
Cable length
● shielded, max. 1 000 m
● unshielded, max. 600 m
Interrupts/diagnostics/status information
Diagnostics function Yes
Substitute values connectable Yes
Alarms
● Diagnostic alarm Yes
Diagnoses
● Monitoring the supply voltage Yes
● Wire-break No
● Short-circuit No
Diagnostics indication LED
● RUN LED Yes; green LED
● ERROR LED Yes; red LED
● Monitoring of the supply voltage (PWR-LED) Yes; green LED
● Channel status display Yes; green LED
● for channel diagnostics No
● for module diagnostics Yes; red LED
Potential separation
Potential separation channels
● between the channels No
● between the channels, in groups of 2
● between the channels and backplane bus Yes
● Between the channels and load voltage L+ Yes
Permissible potential difference
between different circuits 250 V AC between the channels and the supply voltage L+; 250 V AC between
the channels and the backplane bus; 500 V AC between the channels
Isolation
Isolation tested with Between the channels: 2 500 V DC; between the channels and backplane bus:
2 500 V DC; between L+ backplane bus 707 V DC (type test)
Standards, approvals, certificates
Suitable for safety functions No
Ambient conditions
Ambient temperature during operation
● horizontal installation, min. -40 °C; = Tmin (incl. condensation/frost); start-up @ -25 °C
● horizontal installation, max. 70 °C; = Tmax; see Derating BasedOn (e.g. manual), additionally Tmax > 60 °C
max. 8 outputs (no adjacent points)
● vertical installation, min. -40 °C; = Tmin; Startup @ -25 °C
● vertical installation, max. 40 °C
Altitude during operation relating to sea level
● Installation altitude above sea level, max. 2 000 m
● Ambient air temperature-barometric pressure-altitude Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m)
Relative humidity
● With condensation, tested in accordance with IEC 60068- 100 %; RH incl. condensation / frost (no commissioning in bedewed state),
2-38, max. horizontal installation
Resistance

6AG15225HH007AB0 Subject to change without notice


6/8/2023
Page 2/3 © Copyright Siemens
Coolants and lubricants
— Resistant to commercially available coolants and Yes; Incl. diesel and oil droplets in the air
lubricants
Use in stationary industrial systems
— to biologically active substances according to EN Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna);
60721-3-3 Class 3B3 on request
— to chemically active substances according to EN Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity
60721-3-3 degree 3); *
— to mechanically active substances according to EN Yes; Class 3S4 incl. sand, dust, *
60721-3-3
Use on ships/at sea
— to biologically active substances according to EN Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on
60721-3-6 request
— to chemically active substances according to EN Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity
60721-3-6 degree 3); *
— to mechanically active substances according to EN Yes; Class 6S3 incl. sand, dust; *
60721-3-6
Usage in industrial process technology
— Against chemically active substances acc. to EN Yes; Class 3 (excluding trichlorethylene)
60654-4
— Environmental conditions for process, measuring Yes; Level GX group A/B (excluding trichlorethylene; harmful gas
and control systems acc. to ANSI/ISA-71.04 concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level
LC3 (salt spray) and level LB3 (oil)
Remark
— Note regarding classification of environmental * The supplied plug covers must remain in place over the unused interfaces
conditions acc. to EN 60721, EN 60654-4 and during operation!
ANSI/ISA-71.04
Conformal coating
● Coatings for printed circuit board assemblies acc. to EN Yes; Class 2 for high reliability
61086
● Protection against fouling acc. to EN 60664-3 Yes; Type 1 protection
● Military testing according to MIL-I-46058C, Amendment 7 Yes; Discoloration of coating possible during service life
● Qualification and Performance of Electrical Insulating Yes; Conformal coating, Class A
Compound for Printed Board Assemblies according to IPC-
CC-830A
Dimensions
Width 35 mm
Height 147 mm
Depth 129 mm
Weights
Weight, approx. 350 g

last modified: 7/28/2021

6AG15225HH007AB0 Subject to change without notice


6/8/2023