FLEX28024B Input: single-phase: 230 – 400 – 500 Vac
Output: 24 Vdc 60°C
Efficiency up to 89%
Strong overload without switch-off, up to 50%
Flexible Power continuity: from 240 to 336 W
“Power Good” Relay
RoHS
Three mode of output protections:
1) Hiccup mode
2) Continuous Out Mode
3) Manual Reset
DIN Rail Mountable
Extremely small size
3 Years warranty
Input Data
Nominal Input Voltage (2 x Vac) 230 – 400 – 500 Vac Regulatory Compliance
Manual select Input from 230 to 400-500 - CE mark in conformity with EU Directives: EMC, LVD and RoHS.
Input Voltage range: (230) 187-264 Vac - UKCA mark in conformity with UK S.I. 2016/1091, 2016/1101,
(400-500) 330-550 Vac 462-770 Vdc 2012/3032.
Inrush Current (Vn and In Load) 34 A 5 msec. - REACH Regulation 1907/2006.
Frequency 47 – 63 Hz
Input Current (230 – 400 – 500 Vac) 2.49 – 1.44 – 1.15 A
Internal Fuse T4A
Standards Conformity
- EN IEC 61010-2-201:2018 Safety requirements for electrical
External Fuse (recommended) 16 A (MCB curve B)
equipment for measurement, control and laboratory use.
Output Data
Output Voltage (Vn) Factory Setting 3% 24 Vdc
Adjustment range (Vadj) 22 – 27 Vdc Approvals
Start up with Strong Load (capacitive load) 50.000F - UL508 Industrial Control Equipment for US & Canada (E308682).
Turn-On delay after applying mains voltage 1 sec. (max)
Continuous Current at 24 V < 40°C (In) 14 A EMC
Continuous Current at 24 V < 50°C (In) 12 A - EMC Immunity EN 61000-6-2 for industrial environments:
Continuous Current at 24 V < 60°C (In) 10 A EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5,
Power Boost Current at 24 Vdc 60°C(In) In 60°C x 1.5 3 min. EN 61000-4-6, EN 61000-4-8, EN 61000-4-11.
Current max. Overload 4Vdc (permanent) Imax=In60°Cx(1.8 -2.2) - EMC Emission EN 61000-6-4 for industrial environments (Class A).
Maximum Short Circuit Current Icc
Hiccup mode: Max 2 sec. Continuous Mode 30 A Output derating Curve
Hold-up Time ( min. Vac) ) Vn In 40°C Typ. 20 msec
Continuous Load
Residual Ripple 80 mVpp % 160
Efficiency 89 % 140
Over temperature Protection Yes. Shut-down output and 120
100
automatic restart. 80
Short-circuit protection 1° Manual Reset 60
2° Hiccup Mode 40
3° Continuous Out Mode 20
0
Dissipation power load max (W) 40
Over Load protection Yes -10 0 10 20 30 40 50 60 70°C
Over Voltage Output protection Yes (typ. 35 Vdc)
Parallel connection Yes. “Easy Parallel”
Power Good Contact rating (EN60947.4.1):
Output Voltage vs. Output Current, typ.
Max. DC1: 30 Vdc 1 A; AC1: 60 Vac 1A Resistive load
Min.1mA at 5 Vdc Min permissive load Out Voltage
Climatic Data 28
Ambient Temperature operation -25 up to +70 °C 24
(>60°derating 2.5% °C) 20
Ambient Temperature Storage -40 up to +85 °C 16
Humidity at 25 °C, no condensation 95 % to 25 °C 12
8
General Data
4
Isolation Voltage (In / Out) 3000 Vac
0
Isolation Voltage (In / PE) 1605 Vac
0 10 20 30 40
Isolation Voltage (Out / PE) 500 Vac
Protection Class (EN/IEC 60529) IP 20 Load (A)
Reliability: MTBF IEC 61709 > 500.000 h
Pollution Degree Environment 2
Connection Terminal Blocks Screw Type 2,5 mm2 (24 – 14 AWG)
Protection class I with PE connected
Dimension (w-h-d) 72x115x135 mm
Weight 0.85 kg approx.
All specifications are subject to change without notice