SAS LC Course Material

SAS (Safety And Security systems) offers a comprehensive course on light current systems aimed at engineers in various roles, providing essential knowledge in design, installation, and specifications. The course lasts 36 hours over four weeks and covers multiple systems including fire alarms, CCTV, and access control, with hands-on demonstrations. The instructor, Eng. Abdallah Maged Mohamed, has 10 years of experience and has worked on significant projects across several countries.

Uploaded by

moelgezawy4
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
93 views315 pages

SAS LC Course Material

SAS (Safety And Security systems) offers a comprehensive course on light current systems aimed at engineers in various roles, providing essential knowledge in design, installation, and specifications. The course lasts 36 hours over four weeks and covers multiple systems including fire alarms, CCTV, and access control, with hands-on demonstrations. The instructor, Eng. Abdallah Maged Mohamed, has 10 years of experience and has worked on significant projects across several countries.

Uploaded by

moelgezawy4
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

Safety And Security systems

Light Current systems Course


Company Profile
About Us

With experience of 10 years in light Current Systems, we established (SAS) Safety And
Security systems company for light current systems courses and consultations.
In our courses we provide complete required knowledge for an engineer in light current
systems field for Design, devices specifications, wiring and Installation.
Our courses are intended for Technical office Engineers, Site Engineers, Design Engineers,
Procurement Engineers and Pre-Sales Engineers of consultants offices, contractors and
system integrators

Our Mission

To provide light current systems market with experienced engineers who have competitive
knowledge which Satisfy worldwide customers needs and expectations through the
design, installation, and equipment quality.
Course Details
Description
• This is an engineering course designed to provide understanding of light current systems and projects
requirements
• Course provides light current systems (function, components, design and installation)
• Course provides technical office requirements and includes live hands-on demonstration

Objective
• At the completion of the course the successful candidate will be able to design, quote, install, integrate and
prepare submittals for light current systems.

Prerequisites
• Bachelor of Communication / Electrical power Engineering.
• Working or having an internship in light current systems field.

Duration
• 36 hours, 4 weeks, 3 days per week, 3 hours per session.
Instructor CV
• Name : Eng. Abdallah Maged Mohamed
• University : Canadian International College
• College : BSc. Communication Engineering 2011
• Job : Sales Manager at C&T Group (Sub-contractor for light current systems) and Founder of SAS (Safety And
Security) company
• Experience : 10 years experience in (design, technical office, installation) for light current systems field as a sub-
contractor in Egypt, Algeria, Saudi Arabia and Kuwait.

• Certified Trainings :
1. Fire Alarm system Certified from (Fike – USA)
2. Voice Evacuation system certified from (Fike – USA)
3. Access Control system certified from (Sensor Access Technology – UK)
4. CCTV system certified from (Vantage – UK)
5. Disabled Alarm system certified from (Baldwin Boxall – UK)
6. Water Leakage system certified from (Aquilar – UK)
7. Master Clock system certified from (Sapling – USA)
8. Fire Alarm system certified from (Hochiki – UK)
9. PMP
Certified Trainings
Instructor Involved Projects
• Cairo International Airport - Terminal 2 • Emirates Airlines Head Office
• Cairo International Airport - Seasonal Flights Terminal • Nile Badrawi Hospital
• Cairo Underground Metro - line 3, phase 2 • Cairo Specialized Hospital
• Cairo Underground Metro - line 3, phase 1 • Nozha International Hospital
• Grand Egyptian Museum • British University in Egypt
• Alexandria Port - MTS Logistics Center • King Salman University in Sinai
• Dekheila Port - MTS Logistics Center • QNB Bank
• Ministry of Communications and Information • Crowne Plaza Hotel in Sheikh Zayed
Technology - ITIDA in Smart Village • Mall of Egypt Mall
• District Cooling Plant of New Administrative Capital • Arkan Plaza Mall
Course Content
• Projects requirements from (RFQ, Vendors 11. Audio/Visual system
list, BOQ, Specifications and Drawings types) 12. Barrier Gates system
13. Parking Management system
1. Fire Alarm system, Voice Evacuation, LHD 14. Queuing system
cable, VESDA and Smoke detection camera 15. Tel system
systems 16. Data system
2. CCTV system 17. MATV & IPTV system
3. Access control system 18. Intercom
4. Public Address system 19. Metal Detection system
5. Intrusion system 20. Turnstiles
6. Fire Fighting system
7. Nurse Call system • Technical office work (Technical
8. Disabled Alarm system submittals, compliance sheet, SLD,
9. Water & Fuel Leakage system Material List, financial offer)
10. Master Clock system • Systems Live Demonstration
Projects Requirements
Projects Requirements
Drawings Types
1) Riser Drawing :
• Showing system devices types and numbers with their distribution on building floors.
• Consultant is responsible for making Riser diagram and send them to contractors for making single line diagram
accordingly.

2) Design Drawing :
• Showing actual location of system devices without wiring.
• Consultant is responsible for making Design drawings and send them to contractors.

3) Shop Drawing :
• Showing actual location of system devices with their wiring routes.
• Main Contractor or wiring contractor is responsible for making Shop drawings and submit them to consultant for
approval.

4) As-Built Drawing :
• As-built drawings is the same Shop drawings but with the final modifications occurred at site for any change of
devices locations, devices addition or cancellation, wiring routes changed and any change in architecture design.
• Sub Contractor is responsible for making As-Built drawings and submit them to consultant for approval.
• Used by client operators after delivery for making system maintenance.
Projects Requirements
Suppliers Projects Sequence

Pre-Sales
&
Sales Contracting Site
Technical
Office

Main Contractors and Consultants Projects Sequence

Estimation Tendering Procurement Site

• Estimations Engineers start getting budgetary offers for the required systems to put a budget for the
project.
• Then goes to Tendering Engineers who receive technical submittals and actual financial offers.
• Approved technical and financial offers goes to Procurement Engineers to finalize offers and contracting
for the systems.
• Finally Site engineers start wiring network for systems and supervise suppliers installation.
Projects Requirements
Projects Phases
1. Design : design systems locations, numbers and integration

2. Tendering : submit and negotiate technical submittals and financial offers for approvals.

3. Contracting : getting the highest quality with the least pricing and negotiate payment terms, order delivery and project
responsibilities.

4. Wiring Network 1st Fix : install systems wiring network pipes c/w accessories.
5. Wiring Network 2nd Fix : pull systems wiring network cables inside pipes.

6. Installation : fix devices and control panels on their locations wall or ceiling with screws.

7. Termination : connecting devices and control panels cables in their terminals.

8. Programming : making addressing of devices and required integration scenarios by the client.

9. Testing & Commissioning : testing systems devices, functions and finalize them for delivery.

10. Delivery : making inspection and testing with consultant and client for systems handing over.

11. Maintenance : making periodic tests and cleaning for system devices every month.
Projects Requirements
Order Phases
• Order takes approx. 90 working days to arrive warehouse for the below :
1. Money Transfer : 1 week to transfer order amount from our bank to vendor’s bank.

2. Certification and documentation : 1 week for vendor to make certification for order documents at chamber of commerce and
Egyptian embassy.

3. Lead time : 2 weeks for devices to manufactured in factory or it could be stock.

4. Packing : 3 days for packing devices at cartons and get their weight and packing list.

5. Shipping : 3 days for shipping by air for light current systems, but heavy systems like generators come by sea and may take weeks.

6. Legalization : 2 weeks to finalize order documents at Egypt ports by a legalization company.

7. NTRA : 1-2 weeks for checking some devices communications like antennas, cameras and any wireless system should have NTRA
approval before entering Egypt.

8. National Security : 1-2 weeks for checking some devices by security like control panels.

9. Customs and Taxes : 3 days for collecting order customs, VAT, taxes and all expenses.

[Link] : 1 day to be delivered to company warehouse.


Projects Requirements
Vendors List
Projects Requirements
BOQ
Projects Requirements
Specifications
Projects Requirements
Riser Drawing
Projects Requirements
Design Drawing
Projects Requirements
Shop Drawing
Projects Requirements
As-Built Drawing
Light Current Systems
• Fire Alarm
• CCTV
• Access Control
• Public Address
• Intrusion
• Fire Fighting
• Nurse Call
• Disabled Alarm
• Water Leakage Detection
• Master Clock
• Audio / Visual
• Barrier Gates
• Queuing
• Telephone
• Data
Light Current Systems
Fire Alarm System
Fire Alarm System
Definitions
• MFACP : Main Fire Alarm Control Panel
• SFACP : Satellite Fire Alarm Control Panel
• SLC : Signaling line circuit
• NAC : Notification Appliances circuit
• MCP : Manual Call Point
• MPS : Manual Pull Station
• SD : Smoke Detector
• HD : Heat Detector
• MM : Monitor Module
• RM : Relay Module
• VE : Voice Evacuation
• VESDA : Very Early Smoke Detection Aspirator
• HVAC : Heat Ventilation and Air conditioning
• FFL : Finished Floor Level
• LHD : Linear Heat Detection Cables
• FPH : Fire Phones
• SCI : Short Circuit Isolator
Fire Alarm System

• Fire alarm system is designed to detect smoke, heat and flame of fire in any
building and makes an alarm.

• Fire Alarm system has two types : Addressable and Conventional


Addressable Conventional
Detection per detector Detection per zone
Loop wiring network Zone wiring network
Loop have 100 - 300 devices Zone have 20 - 30 devices

Programmable Not Programmable


Big projects Small projects
Fire Alarm System
• Addressable System :

• Conventional System :
Fire Alarm System

• Addressable system with conventional detectors :


If we have a project with an existing conventional fire alarm detectors, we could
replace the conventional control panel with an addressable panel and connect the
detectors with (zone monitor module) to give them address. Or if we have open
areas which the exact address is not required like theaters or halls.

• Fire Alarm system applications :


▪ Marine approved : for ships and oil rigs
▪ Intrinsically safe : for high current systems
▪ Explosion proof : for hazardous areas
Fire Alarm System

System Video Introduction

[Link]
Fire Alarm System

1) Control Panel

• Locates the presence of fire, troubles and supervisory with address and type of the
device on LCD screen

• Gives power to all loop devices and equipped with back up batteries in case of no
electricity

• Operates audio and visual signals to sounders and flashers in case of fire on 2
NAC circuits

• Controls required actions by modules for integration with HVAC, elevators, AC,
PA, BMS

• LEDs green for AC power, red for alarm, yellow for trouble

• Control panels comes in 1,2,4 and 8 loops, or 1,2,4 and 8 zones.


Fire Alarm System
2) Manual Call Point
• When a person detects a fire while the system didn’t detect it automatically he uses
the manual call point to give an i/p signal to the FACP to be warned with fire and
takes the necessary action.
• Manual call point named also Manual pull station , Break Glass, ‫كاسر‬.
• Manual call point Design :
▪ Installed at all floor exits at ground floor and emergency staircase at above floors.
▪ We should put MCP every 30 m (Don’t run more than 30 m)
▪ Installed at 1.4 m height from FFL on the right hand side of leaving person, in a
clear location with enough light, its color is different than the wall color to be clear
enough and away from any other buttons like lights, AC,…etc.

• Egyptian Code for Fire Alarm system design :


Fire Alarm System
3) Detectors
• Detectors are designed to detect the presence of fire automatically and sends an i/p
signal to the FACP to take the necessary action, type of detector depends on type of
fire we need to detect.
• Majority of detectors comes with bases and heads, bases are installed on ceiling and
heads are fixed on bases, bases are 4 inch, 6 inch, bases could came with sounder like
hotels or relay.
• Fire occurs first with a flame then smoke then heat.

• Detectors Types :
▪ Ionized Smoke detector : detects ions of smoke by radio active materials, but as its
harmful it is prohibited.

▪ Photoelectric Smoke detector : replacement for ionized detector which detects


photons of smoke inside the detector chamber, so it is slower in detection than
ionized but it is used as it not harmful, smoke detectors are the standard used
detector in all offices, corridors, halls, its sensitivity is (1.3-3.6 %) smoke from air
photon.
Fire Alarm System
Ionized Smoke Detector

Photoelectric Smoke Detector


Fire Alarm System
Detectors Types
• Heat detector : areas which have existing smoke which could make false alarm like (kitchens, cafeterias, smoking
areas, dusty areas and garages), its types are :
o Fixed 60 : above 60c makes alarm (standard)
o Fixed 90 : for high temperature applications
o Rate of Rise : if temperature raised 15 c degrees in 1 min. makes alarm for different temperatures applications
o Combined : working with both scenarios fixed temperature or rate of rise.
• Multi Sensor : detects smoke or heat, used in server rooms, generators, data centers or hazardous applications
• Beam detector : for high ceiling applications (above 7m) and open areas like malls, available with transmitter &
receiver for 100 m length detection or transceiver with plate for 35 m length detection and both their width is 15 m
• Flame detector : for flammable materials applications like chemical, oils, papers and wood factories, detector is
available in IR or UV, detector should not be installed facing light or sun rays for false alarm.
• Duct detector : installed on the return of centralized AC and air flow rooms in which air flow is above 4000 fpm
• Air Sampling detector : for high sensitivity applications (0.0001 % smoke) like data centers, oil & gas and nuclear
• Gas detector : used for CO gas detection and installed in garages, or Methane gas and installed in kitchens
Fire Alarm System

Detectors Design
• Most common used detector is the smoke detectors.

• For applications which have existing smoke which could make false alarm like kitchens, cafeterias, smoking
areas, dusty areas we put heat detectors.

• For applications which have high ceiling more than 7m or open areas we put beam detectors.

• For applications which have flammable materials and could have fast fire like chemicals, oils, papers and wood
we put flame detectors.

• For hazardous areas or areas which could have fire from smoke or heat we use multi sensors.

• For flame detector coverage area it is function of height by the area of the circle πh2.

• If we have false ceiling or false ground its height is more than 80 cm and have cables we should put detectors and
put LEDs above ground or under ceiling, for long cable trays it is better to have LHD cables.
Fire Alarm System

Detectors Design

Feature Smoke Detector Heat Detector


Coverage Area 100 m2 50 m2
Farthest Point 7.5 m 5.3 m
Distance Between detectors 9m 7m

Egyptian Code
Fire Alarm System
Detectors Design
Fire Alarm System
4) Modules
• Control function :

▪ Relay module : used to release a dry contact signal from control panel to shut down HVAC, open fire exit doors,
deactivate elevators, open AC doors, stop music on PA and play EVAC message in the event of alarm.

▪ Control module : gives 24 v for specific devices like sounders and solenoids to be activated, used for making
alarm on specific sounders not all sounders on NAC circuit, control module requires a separate 24 v DC line from
auxiliary power of control panel.

• Monitor function :

▪ Single monitor module : to monitor a single device like tamper switch, flow switch, pull station and beam detector

▪ Dual monitor module : to monitor 2 devices with the same address like monitoring on board relays of other
systems control panels for alarm and fault notifications.

▪ Zone monitor module : to monitor group of conventional detectors (average 20 detectors) and used with some
beam detectors models.
Modules Integration

Tamper Fire Conventional


HVAC Sounder Detectors
Switch Fighting

Dual Zone
Relay Control Monitor Monitor
Module Monitor
Module Module Module Module
Fire Alarm System
Modules Integration
• Elevators : Relay module to move it to the ground floor or nearest floor and switch it off.
• HVAC : Relay module to switch off AC for not increasing or distributing the fire.
• Public Address : Relay module to stop music or sound and play evacuation message
• Access control : Relay module to open all access doors
• Sounders : Control module to give address and power to sounders.
• Fire Phones : Fire phone module to give address to fire phones.
• Tamper Switch : Monitor module to monitor control valve of sprinklers.
• Flow Switch : Monitor module to monitor water flow in sprinkler system pipes.
• Shops : Monitor module / Relay module to monitor or control each shop control panel.
• Other systems control panels : Dual Monitor module to monitor alarm and trouble status
of other systems control panels.
• Electricity panels : Relay module to switch off electricity panels.
• Conventional Detectors : Zone monitor module to monitor a group of conventional
detectors and give them an address.
• Beam Detector : Zone monitor module / monitor module to monitor beam detector and
give it an address, type of monitor module depends on beam detector model.
Fire Alarm System

Optional Modules
• Network module : connect FACPs together by RS485 for less than 1.2 km or by Fiber
optics for 3 - 4 km max., let control panels monitor all events of other control panels.
• Ethernet Module : connect FACP with TCP/IP network for remote monitoring.
• Fire Phone Module : for making conventional fire phone an addressable device.
• Multi Interface Module : connect FACP with serial printer or graphic software.
• Supplemental Loop Module (SLM) : card for adding additional loop to the control
panel, could come with 1 loop or 2 loops.
• Supplemental Power Supply Module (SPS) : for doubling the power of the FACP
for additional required power, as control panel has 2 A in steady state situation and 6
A in alarm state, while (SPS) double the FACP power to become 4 A in steady state
and 12 A in alarm state, for additional power we could use another control panel or
external power supply.

Note : FACP power requirements are determined by making battery calculation for the
FACP which will be described in the last session in the course in Systems Live
Demonstration.
Fire Alarm System
5) Sounders
• Audio :
▪ Bell : 90 db mechanical move, comes in 6 or 10 inch.
▪ Siren or Horn : 115 db electrical move.
• Visual :
▪ Strobe or Flasher or Beacon : for high noise applications and night fire, its candela 15-120.
• Audio/Visual :
▪ Siren/Strobe : for high risk applications, or locations with high background noise.

• Sounders Design :
▪ To be installed in corridors every 30 m on 2.3 height from FFL.
▪ Bell range is 15 m, and its intensity must be higher than the normal background noise
(65 db) with 15 db, should make a test with sound meter in projects for db confirmation.
▪ Each door or wall decrease sound with - 3db , decay signal 20 log (distance).

• Egyptian Code for Fire Alarm system Design :


Fire Alarm System
6) Accessories
• Batteries : working as a back up power supply in case of main AC power got cut of,
operates panel for 24 hours in steady state and 30 minutes in alarm state as per NFPA-72.
• Auto dialer : dial automatically fire brigade, send recorded message to saved number.
• Serial Printer : print control panel occurred events of alarm and trouble of field devices
with their timing.
• Graphic display : show the installed system graphically on a PC software for monitoring
and control.
• Repeaters : show the system status on FACP in other location and could control the
system.
• Short Circuit Isolator : isolate devices in between isolators which had short circuit and
let the remaining devices work normally, recommended to be installed every 20 devices
or upon consultant design, some consultants put all detectors with isolators and for
modules every 15 device, some vendors have a short circuit isolator module and other
vendors could have all devices (detectors, modules, with built-in isolator or without.
• Field server protocol : for complete devices integration with BMS or other control
panels brands, should determine communication type, baud rate, number of points.
Fire Alarm System

Design Codes
• NFPA 72 (USA)
• BS 5839 (UK)
• ‫( الكود المصري ألنظمة الحريق‬Egypt)

Equipment Approvals
• UL : Underwriter Laboratories (USA)
• FM : Factory Mutual Laboratories (USA)

• LPCB : Loss Prevention Certification Board (UK)


• BSI : British Standard Institute (UK)

• VDS (Germany)
• Afnor (France)
Voice Evacuation System
• Statistics showed that majority of people who die in case of fire are dying from the rush of escaping the building
more than from the fire itself, for that reason engineers created this system.

• System objective is to guide building occupants for the best and safest route for leaving the building.

• Voice Evacuation system scenario : is Fire fighters come to the building check the fire in each floor, then use
the fire telephone or connect portable handset in the fire phone jack beside each emergency stair case to call the
fire fighter leader through fire command center master fire phone to inform him with the fire status in each floor,
then leader use the paging microphone to guide building occupants for the safest route for leaving the building,
and uses audio control cards on panel to play evacuation and alert recorded messages to specific floors.

• System has different types :


▪ Single channel : to play one message at a time EVAC or Alert.
▪ Dual channel : to play 2 messages at a time EVAC and Alert.
▪ Multiple channel : to play a different message at each floor.

• Fire floor, floor above and floor down should play EVAC
message, and other floors should play Alert message.
Voice Evacuation System
• Voice Evacuation system consists of :

• Fire Command Center : large enclosure fire alarm control panel equipped with voice
evacuation system devices which are :
▪ Master fire phone : to communicate with fire fighter telephones in building
▪ Paging microphone : to guide building occupants for safest route escape.
▪ Audio paging module : distribute audio to amplifiers and connects microphone and fire
phone
▪ Paging control card : to choose to page to EVAC or Alert zones or all.
▪ Fire phone cards : showing which fire phone floor is calling.
▪ Voice evacuation switch card : used to control speaker zones to page or play EVAC or
Alert recorded messages.

• Amplifiers : which distribute audio to speakers, majority are 50 w.


• Speakers : speakers are fire rated, with 2 w power and could have tapping for (1/4,1/2,1,2
w), comes in ceiling or wall mounted, indoor or outdoor, could come with strobe.
• Fire telephones / Fire phone jacks with portable handsets : installed at each floor
emergency stair case, connected to fire phone module to become addressable.
Voice Evacuation System

System Design
Linear Heat Detection (LHD) Cable
• Linear Heat Detection cable is a system used to detect fire in tunnels, cable trays,
tanks, cold storage, elevator shafts, generators and motors….etc.

• When the cable senses a heat over its entire length, it sends a detection signal to
the fire alarm control panel through a monitor module.

• System could be addressable with a distance locating module which will detect
the exact meter of the detected fire.

• System consists of :

▪ LHD cable : detects fire by sensing heat increase.


▪ Distance locating module : make the system addressable.
▪ Junction box : for connecting the LHD cable with the distance locating module.
▪ End of line resistor : to close the LHD cable circuit.
▪ Fixation accessories : like cable tie, L bracket, clamp.
▪ Monitor Module
▪ Fire Alarm Control panel
Linear Heat Detection (LHD) Cable

System Design
For supplying LHD cable we should determine these specifications for cable :
• Detecting temperature : (68, 78, 88, 104 C)
• Length : (150, 450, 900 m)
• Cable covers : (Nylon, Polypropylene, Guide wire)
• Fixation Accessories : (cable tie, L bracket, beam clamp, push pin)
• Addressable or conventional : distance location module for addressable.
VESDA Aspirator Detector
• Aspirator detector which is famous under the name of VESDA detector (Very Early Smoke
Detection Aspirator).
• Used in highly sensitive areas which could detect fire at an early stage, like (cold storage,
museums, data centers, oil & gas and nuclear facilities).

• System consists of :
▪ ASD detector
▪ Aspiration pipes
▪ Air pump inside the detector
▪ Fire alarm panel

• System takes samples of air and tests them for the presence of smoke, air is drawn by a pump
from several holes in the pipes network, then air sample goes into the detector to be filtered
from dust then tested for smoke by laser light source.
• Sensitivity range : 0.00029 – 6.25% Obs/ft
• Coverage area : 2,500 m2, single pipe run 120 m, total pipe network 320 m.
• There are 3 factories which are manufacturing Aspirator detector (VESDA, System Sensor
and Wheel lock).
Smoke Detection Camera
• Smoke detection camera is used to detect :
▪ Smoke
▪ Flame
▪ Reflected flame
▪ Motion

• System used in applications where we can’t have smoke detectors for high ceiling or we have
obstacles to install beam detectors, like : (ware houses, stadiums, planes hangers and power plants).

• System consists of :
▪ Smoke detection cameras
▪ NVR
▪ Smoke detection software installed on a server
▪ Monitor module connected to a fire alarm control panel
▪ Network switch for connecting cameras

• For existing buildings with IP CCTV system working on ONVIF protocol we could supply only
smoke detection server and software, and CCTV cameras will act as smoke detection cameras.
Smoke Detection Camera

System Video Introduction

[Link]
Smoke Detection Camera

System Design
Fire Alarm System
Vendors
• Notifier by Honeywell – USA (UL&FM)
• Edwards (EST)
• Fike – USA (UL&FM)
• Siemens – Germany
• Simplex – USA
• Mircom – Canada
• Farenhyt by Honeywell
• Gamewell by Honeywell
• Firelite by Honeywell
• Hochiki – USA
• Avenger – USA
• Apollo – USA (UL)
• Hochiki – UK
• C-Tec – UK
• Thorn
• HST - China
• Zeta
Fire Alarm System
Vendors List
Fire Alarm System
BOQ
Fire Alarm System
Riser Drawing
Fire Alarm System
Specifications
Fire Alarm System
Financial Offer
Fire Alarm system
Assignment 1
• If we have a client has a car factory with area 50 m length x 15 m width x 5 m height, he needs to get
certification from fire brigade to get the license of the factory, what should we propose to him ? And what are
our inquiries to the client to make the suitable design ?
CCTV System
CCTV System
• CCTV is Closed Circuit Television.
• System Types :
▪ Analog system : analog cameras connected with coaxial cables on DVR to the monitors.
▪ IP system : IP cameras are connected with Ethernet cables on NVR to the monitors, also IP cameras could be
connected to Video Management sever for large scale applications.
CCTV system
Analog VS IP
Feature Analog system IP system
Resolution TVL or MP MP better resolution
Cabling 2 cables data and power 1 cable Ethernet POE
Coaxial cable with BNC from camera and Ethernet cable with RJ45 connected to
DVR side POE switch or NVR
Max. 300 - 400 m Max. 90m
Installation Needs several cables and hard installation Less cabling and easier in installation
Data Transfer Analog signal with Normal rate Digital signal so faster
Control Control DVR Control each camera
Cost Low cost High cost
Remote Monitoring Access DVR by LAN port Access each camera by IP address
Functionality Live view Live view and video analytics
Application Villas and shops Companies and projects
Cameras Specifications

1) Cameras Types :
• Dome : for indoor applications, better design and lens could be hidden.
• Bullet : for outdoor applications, weatherproof.
• Box : used for customized specifications like lens, sensor, enclosure.
• PTZ : 360° movable camera, Pan 180°, tilt 180°, optical zoom
(10,15,25,32,40x) which differs than digital zoom with lens movement.
• LPR : License Plate Recognition camera to capture cars plates.
2) Monitors :
• CCTV system could be monitored on PCs monitor, LCD displays and video wall, also could
have a console for security monitoring contains displays, workstations, DVRs and joystick.
Cameras Specifications

• Camera Components :
1) Lens : which combines the light coming from the objects.
2) Sensor : which converts this light to an image or video, sensor have several types like CCD
and CMOS which is faster, takes higher video frames and less sensitive to light.
3) Enclosure : which is outer box of the camera which could be indoor or weatherproof for
outdoor application.
• Distance between sensor and lens called focal length, when you move the lens near to the
sensor you see a wide angle with less distance and the opposite.
Cameras Specifications

Environment Indoor Outdoor weather proof IP67

Resolution TV Line (380-1000 TVL) Mega Pixel (1,2,3,4,5,8 MP)

Fixed Lens Vari-Focal Lens (2.8-12 mm)


Focal Length
(2.8,3.6,6,8,12,16mm) manual or motorized
Infra Red for night mode
IR distance To 150 m
from 20 m
General
WDR, BLC, Star Light, Auto IRIS, aspect ratio
Specifications
CCTV System
CCTV System

[Link]
CCTV system
Analog System
1) DVR :

• Digital Video Recorder has several functions :


▪ Working as switch to connect cameras
▪ Includes hard drives for recording
▪ Compress video for less storage
▪ Monitor cameras, include alarm features, change cameras settings and control PTZ cameras
▪ Supports mobile remote monitoring by connecting LAN port to the router

• Digital Video Recorders come in 4, 8, 16, 24 and 32 channels

2) Cameras :

• Analog cameras have 2 types :


▪ TV Line cameras : resolution from (380 – 1000 TVL), but it is obsolete now after releasing HD cameras.

▪ AHD cameras : Analog High Definition cameras with resolution (1,2,3,4,5,8 MP).
CCTV system
Analog System
• Analog cameras have different video signals like :
▪ CVBS : Composite video base band signal, used for analog standard definition video cameras with TV lines
resolution.
▪ SDI : Serial Digital Interface, used for transmission of digital video signals over a coaxial cable but had
limitations for cables length.
▪ TVI : Transport Video Interface, used for transmission of high definition analog video over a coaxial cable,
it was released in 2014 and has become the most popular analog HD security camera technology, and it was
first adopted by Hikvision, TVI is popular in USA.
▪ CVI : Composite Video Interface, very similar to TVI but with a different digitized transmission signaling,
CVI was adopted by Dahua, CVI is popular in China.
▪ AHD : Analog HD, similar technology to TVI and CVI in theory, but differs by video transmission signal
digitization. AHD technology was adopted by Nextchip. AHD is popular in Korea and Japan.
▪ 4in1 : majority of cameras now could support the 4 types of video signals (CVBS, TVI, CVI and AHD)

• Analog cameras have 2 cables : coaxial cable for data with BNC connected to the camera and the DVR with
max. 300 - 400 m length between DVR and camera, and power cable from power supply to the camera
or by an adaptor to a power outlet beside the camera.
CCTV system
IP CCTV System
• 1) NVR :
• Network Video Recorder has several functions :
▪ Receives video signals from cameras and give them power through POE ports.
▪ Includes hard drives for recording
▪ Enables smart functionality and video analytics.
▪ Flexible that not necessarily cameras to be connected physically to NVR, only to be on the same network.
• Network Video Recorders come in 4, 8, 16, 24, 32, 64 and 128 channels.
• 2) Cameras :
• IP cameras have the following features :
• IP cameras are available with resolution (1,2,3,4,5,8 MP)
• IP cameras have a chipset which is processing the video data in the camera itself not the NVR and transmit it to
the NVR, it could work as a standalone image capturing device.
• IP cameras have good video quality and better resolution by transmitted digital signal.
• IP cameras also enables improved smart functionality and video analytics, such as facial recognition.
• IP cameras have 1 cable : Ethernet cable with RJ45 connectors which transmit video, audio and power to
cameras, Ethernet cables are easier in installation for routing and termination, no need for connection between
NVR and cameras only to be on the same network, max. 90 m length but could be extended with switches.
CCTV System
CCTV System Design
• Required design vary upon project volume and identity, client should determine required security level.
• We put a camera every 20 m as a min. coverage for all cameras, or you could put it for longer distances upon
camera type like outdoor varifocal cameras and long IR distances cameras.
• First camera must be covered with additional camera for the dead zone behind it.
• Cameras are fixed on the wall, on a stand or on the building itself, cameras should be in a convenient height (3-4m)
• Outdoor cameras don’t require high resolution (1 or 2 MP) are enough, while indoor camera require high resolution
(2 or 4 MP) are good for reviewing people faces details.
• Outdoor cameras should be weatherproof and should be vari-focal to zoom in and out for near or far objects, while
indoor cameras no need to be vari-focal they should be fixed, except if there are long corridors and you may zoom
for near or far people.
• Indoor cameras to be fixed in the corner of the room.
• Cameras installed inside rooms should have small focal lens like (2.8 – 3.6 mm), while corridors could have large
focal lens like (8 – 12 mm).
• Any doors or staircases or elevators must have a facing camera to monitor entering and exiting people.
• PTZ cameras are used for tracking not monitoring and installed at higher locations to make good coverage.
CCTV System
CCTV System Design
VMS
Video Management System

• Benefits :
▪ Could Connect unlimited number of cameras.
▪ Complete redundancy failover for recording servers and redundant for application servers.
▪ Video analytics features for smart action, smart search and business intelligence.
▪ Smart search for events, objects, line crossing, coloured object,..etc.
▪ Give authorizations for different users like (operator for viewing cameras only, investigator for reviewing
recordings and admin who can change system configuration)
▪ Integration with building automation systems like Access control and Intrusion.

• System Components :
▪ Network Cameras
▪ Application server
▪ Recording servers c/w HDDs
▪ Licenses for cameras and server
▪ Monitoring Workstation
Video Management System

System Video Introduction

[Link]
CCTV Video Analytics
Video Analytics features :
• Smart Action feature : to detect specific events during live monitoring like
(person moving in an are, person crossing a line, person is loitering,..etc.)
CCTV Video Analytics
Video Analytics features :
• Smart Search feature : to search specifically for (person, vehicle or object), its movement (moving, stopped,
crossing line), its colour, its size, on a specific camera and at a specific time.
CCTV Video Analytics
Video Analytics features :
• Business Intelligence : used in retails shops, traffic as an example for people counting to define rush hours for
retail management, and detect crowding areas to assist business owners to know people interest, or for cars
counting to determine rush hours by high traffic roads and route them to other directions.
Video Management System
VMS system components
• Application server :
▪ Contains the Video Management software.
▪ We should have one server as a main and another one as redundant for the main server, it takes back up
every 20 minutes.
▪ If main server fails we could switch manually the redundant server to be a main server, in this times live
viewing and recording will be working normally, only configuration will not be allowed.

• Recording Server :
▪ Contains HDDs, server could contains 8,16,24 HDDs with 16 TB max. for each.
▪ One recording server could have 100 cameras.
▪ Client should determine how many fail over servers are required as a back up for recording servers, we
should have one fail over server min.
▪ There are 2 different types of storing back up data called RAID, they are :
o RAID-6 : makes 3 HDDs from the 8 HDDs are back up for the 5 HDDs and this type called (Hot swap).
o RAID-5 : makes 2 HDDs from the 8 HDDs are back up for the 6 HDDs.
o If any HDDs fails, its data is not getting loss from the server.
o Configuration differs between brands, you have to check with your vendor.
Video Management System
VMS system Design
Video Management System
Storage Calculations
Bandwidth
Cameras Resolution Compression FPS Days Scene Activity Recording Profile Frame Size (KB) Bitrate (kbits/s) (Mbit/s) Disk Space (GB)

523 1920x1080 (2MP) H.264 25 30 Medium - Mall Continuous - 24 Hr 13 2552 1303.4 412,408

0 1920x1080 (2MP) H.264 15 30 Medium - Mall Continuous - 24 Hr 13 1531 0.0 -


Total 1303.41 412408.4
• Standard parameters for recording is 2 MP resolution, H.264 compression, 25 FPS, 30 days continuous recording.
• Total required TBs is multiplied by 1.1 risk factor then divided by number of recording servers, to know how many
TBs is required for configuration for each recording server.
• Example: if we have 523 cameras, we will have 6 recording servers, we need 412 TBs for recording * 1.1 risk
factor = 453 TBs / 6 servers = 76 TB per server, so each recording server will be configured as 80 TB RAID6.
• Estimation for site surveys 2 MP camera requires 40 - 70 G recording per day, and requires 6.5 Mbps bandwidth,
NVR bandwidth must cover required bandwidth of cameras.
• To decrease storage size choose recording with motion only, make FPS 15 but could have delay in video, decrease
recording resolution while live view will stay with the same resolution, number of recording days.
Video Management System
• Licenses for cameras and server :
▪ License purchased for cameras and server to be activated on VMS, could have upgrade license for
automatic future updates.

• Monitoring station :
▪ Monitoring workstation to view cameras by security.
▪ Could come with 2 or 4 monitors outputs.
▪ Monitors could be a workstation display or TV display or video wall.
▪ Could come with keypad for multi-screen controls, quick playback, playback speed and
controls PTZ cameras.
▪ We should have a console consists of desk, displays with their wall mount, keyboard, server, tel.
CCTV System
CCTV System Vendors
• Pelco - USA
• Bosch
• Cisco - USA
• Axis - Sweden
• Vicon - USA
• Honeywell
• Samsung / Hanwha - Korea
• American dynamics - USA
• Infinova - USA
• Panasonic
• Uniview - China
• Hikvision - China
• Dahua - China
CCTV System
CCTV System BOQ
CCTV System
CCTV System Finanical Offer
CCTV System
Assignment for CCTV System
• CCTV system design for a villa:
Access Control System
Access Control System
System Design
Input Output
Reader
Lock
Door
Contact
Controller

RTE Alarm
Break
Glass
• System Components :
▪ Controllers
▪ Inputs : Reader, Door contact and Request To Exit, Break glass
▪ Outputs : Lock (Electric or Magnetic) and Alarm module used to make an alarm when door is forced.
▪ Server with software is connected to network to monitor the system and for ID badging printing
Access Control System

System Video Introduction

[Link]
Access Control System
Controllers
• 1 door / 2 reader controller :
Reader IN and Reader or RTE OUT
• 2 door / 2 reader controller :
2 Readers IN and 2 RTE OUT
• 2 door / 4 reader controller :
2 Readers IN and 2 Readers or
2 RTE OUT
• 4 door / 4 reader controller :
4 Readers IN and 4 RTE OUT
Access Control System
Controllers Connection
• Controllers are connected together by serial RS485 or bus TCP/IP network on switches.
• Bus connection is better than serial as in serial of there is a circuit break in the connection all zone will be
down, while in Bus each controller is connected to a switch direct, also in serial connection you could have
interference or delay in signal between controllers.
• In Serial connection controllers are connected in series and at the end we put RS485-USB converter to be
connected to the server, and could have 32 controllers max.
• Serial connection could be used as a back up for Bus connection if LAN network was down.
Serial Connection Bus Connection
Access Control System
Controller Specifications
Access Control System
Readers
• Card Reader (Proximity) : most common used, with different radio frequencies (Proximity, Mifare and Smart)
▪ Proximity cards use 125 KHz frequency, standard cards
▪ Smart cards use 13.56 MHz frequency with advanced features
• Keypad Reader (PIN) : used for advanced security on doors entrance.
• Fingerprint Reader (Bio-metric) : used for high security area and commonly used in time attendance devices.
• Long Range Reader : for parkings, use UHF readers from 2-10 m which could detect cards, tags or sticker.
• Face Recognition Reader : used for high security and used lately for Covid situation for not touching readers.
• Eye Recognition Reader : detects person eye IRIS to give access.
• Voice Recognition Reader : give access by persons voice recognition.
Readers commonly are used for entry only, but sometimes are used in entry and exit for high security areas or
for time reporting of entry and exit of people in this building for main gates, parking, data center,…etc.
Access Control System

Anti Pass-Back feature


• Readers have a feature called (Anti Pass-back) which is used for preventing persons from entering with the
same ID card, its scenario is when a person access the entry reader with his ID card, this ID card couldn’t
be used with the entry reader till this card access the exit reader, after that it could be used in the entry
reader again, but this feature must have reader for entry and reader for exit, can’t work with entry reader
only with request to exit.
• And this is feature could be (Timed Anti Pass-back) for preventing the same ID card from accessing the
entry reader for a period of time then he got access.
• Also there is a feature called (Regional Anti Pass-back) which is person can’t access readers inside the
building before accessing the outside readers for entering the building.
• Finally (Nested Anti Pass-back) is used for a specific sequence for entry and exit of readers for highly
secured areas.
• Denying this feature causes (Hard Anti Pass-back) which will deny the access for this user, or could have
(Soft Anti Pass-back) which will permit access, but this violation will be reported on the software for taking
corrective action with this person.
Access Control System
Door Hardware
3) Locks :
• Electric Lock (Strike) : for wooden doors, to install the lock flushed inside the door with its cable.
• Magnetic Lock : for glass and heavy doors, lock force is (300 – 1500 kg) depends on door weight, could be
installed as fail-safe to be unlocked when power is removed or fail-secure to be locked when power is removed,
could come single or double for double doors.
Locks need power supply, and some locks come with door contact.

4) Request to Exit : to open door from inside without a reader.

5) Glass Break : to open door in case of emergency, installed with doors which have reader for exit.

6) Door Contact : for monitoring doors opening, also to know if door was forced without accessing the reader, could
come single or double for double doors.
Access Control System
System Wiring
Access Control System

Software
• Access control software is a real time reporting software for systems up to 65,000 users, 512 readers,
features Alarm Graphics, Badge Printing and simple reporting.
• Softwares depends on number of readers (16, 64, 128, 256 and 512).

• Software functions :
Access Control System

Software Functions
• Cardholder Screen to check their access • Statistic Report for selection and filtering upon our
requirements
Access Control Software
• There are additional softwares are ordered upon client requirements which are below :
Access Control System
Additional Softwares
• Badge Design & Printing : ID card design and production - Produce and print ID cards from software

• CCTV Integration : CCTV integration module to integrate cameras with readers

• Alarm : Alarm Control and Graphics - Import graphical maps and manage interactive system alarms

• Parking : Parking Control - Manage car park spaces according to user and company privilege

• Lift Control : Lift Control - Manage access to floors within the building

• Guard Patrol : Guard Tour - Monitors security guard patrol activity

• Multi Work stations : Multi Company Database - Use one software for each company to manage their own
system on a single database

• Multi Sites : Multi-Site Module - Enable independent administration of multiple sites


Access Control System

Accessories

• Cards : there are proximity and smart cards, also it could be printable.

• Tags : there are proximity and smart tags

• Desktop Enrollment Reader : used by operator to give access to cards

• Extension Boards : to add inputs, relays, TCP/IP interface

• Cards Printers : to print user ID on cards


Access Control System

Access Control Vendors


• HID – USA

• RBH – Canada

• Sensor Access Technology – UK

• Honeywell – USA

• Bosch – Netherland

• Vanderbilt – USA

• Lenel – USA

• Andover (By Schneider) – USA


Access Control System

Access Control BOQ


Access Control System
Access Control Financial Offer
Access Control System Financial Offer
(RBH - Canada)
U. Price T. Price
S. Item Description Part No. Qty.
($) ($)
Supply of Door contact
1 EL-800P 1 107 5.00 535.00
Supply of Double Door contact
2 2*EL-800P 1 7 10.00 70.00

Supply of The Elock-600L electromagnetic lock is capable of holding doors ELOCK-600L 121 116.00
3 14,036.00
Supply of power supply 121 36.00 4,356.00
Supply of exit push button
5 FA-975 114 32.00 3,648.00

RBH-AX-
6 Supply of Access Control Panels Master 2 readres controller Axiom™ UNC100 40 970.00
UNC100-122S 38,800.00

7 Supply of Access Control Panels slave 2 readers Controller Axiom™ Controller RBH-RC2S 40 921.00
36,840.00

6 Supply of Proximity card reader RBH-FR-360N 112 112.00


12,544.00
11 Equipment installation&programming Upon your request -
Total Price In USD Excluding VAT $110,829.00
VAT (14%) $15,516.06
Grand Total Price In USD Including VAT $126,345.06
Access Control System

Access Control Assignment


Assignment for Access Control System design for a Bank :
• We have a bank with 10 rooms (4 VIP rooms and 5 standard rooms and a safe room), VIP and safe rooms doors
are metal heavy doors, while the standard rooms doors are wooden, and there is a parking outside the bank.
Kindly propose an Access control system design for this bank.
Intrusion System
Intrusion System

System Components
Intrusion System

System Video Introduction

[Link]
Intrusion System
Control Panel
• Intrusion control panel connect different types of sensors wireless.

• Control panel is 8 zones and could be expandable to (24, 48, 88, 168, 640
zones), while each zone could have 4 sensors.

• Activate alarm on sounders.

• Arm and disarm the system by a keypad.

• Have LEDs or LCD showing the zone which has an alarm.

• Connected to an auto dialer to call Police and property owner.

• Connected to batteries in case of no electricity.

• Have different versions compact and with keypad.


Intrusion System
Sensors
• Motion PIR Sensor : sensor detects human motion on 9 m and 90 degree
using different scenarios to decrease false alarm :

▪ High immunity PIR : uses Intruder Confirmation Circuitry ensures false


alarm immunity from RF, lightning and mobile.

▪ Digital PIR : uses digital signal processing and digital temperature


compensation provides excellent catch-performance even in extreme
temperature conditions.

▪ Twin dual element PIR : uses two dual element sensors provide
exceptional stability, ideal for commercial applications.

▪ Quad element digital PIR : Genuine quad detection provides additional


stability for harsh environments.

▪ Digital dual technology detector : uses adjustable microwave range and


advanced signal processing ensures maximum false alarm immunity.
Intrusion System

Sensors
• Motion Beam Sensor : used to protect fences from intruders jumping, consists of
transmitter and receiver.

• Glass Break Sensor : used to protect windows and glass doors, detects glass break.

• Vibration Sensor : used to protect banks walls, safe and safe rooms, detects vibrations
in walls or safe.

• Smoke & Heat Detectors : fire detectors integrated with intrusion control panel, smoke
and heat detectors.
Intrusion System

Sensors Design

Motion PIR Sensor Glass Break Sensor

Motion Beam Sensor


Intrusion System
Manual Detection
• Push Buttons : used manually in case of robbers detected, installed under desk or counter.

• Foot or Knee Rails : to be used by foot or knee if robber is viewing my hand, installed
on the floor under the desk.

Alarm & Auto Dialer


• Siren / Strobe : siren with flasher mandatory as majority of robberies occurs at night and
to facilitate for the police location finding, 115 db, IP 65, have (Sabotage Alarm) feature
which enables Siren to make an alarm if anyone tried to cut its cable.

• Auto Dialer : to call police, home owner, send alert recorded message with address, mic.
Intrusion system
System Design
Intrusion system
System Wiring
Intrusion System

Intrusion System Vendors


• Texecom – UK

• Pyronics – UK

• Honeywell – USA

• Bosch

• Lenel – USA

• Schneider
Intrusion System

Intrusion System BOQ


Intrusion System

Intrusion System Financial Offer


Intrusion System

Intrusion System Assignment


• We have a Villa needs Intrusion system. Kindly propose an intrusion system design with the appropriate sensors.
Public Address System
Public Address System
System Components
1) Control Unit / Matrix, Monitor panel (zones), Automatic change over unit

2) Amplifiers / Pre-Amplifier

3) Speakers

4) Microphones

5) Inputs :
• CD/DVD, AM/FM Tuner, MP3, Bluetooth, Blu-ray
• Digital Message Recorder

6) Power supply

7) Volume Control

8) Racks
Public Address System

System Components
Public Address System

System Video Introduction

[Link]
Public Address System
Control Unit
• Functions :

▪ System management
▪ Control all parts of system
▪ Audio signal processing
▪ Distribution
▪ Connected with power supply and batteries

• Direct access to :

▪ Zones statues : fault, blocked or playing including type of source


▪ Simple matrix activation by selecting zones / groups and audio inputs / messages
▪ Fault register in details
▪ Global audio signal management over the network
Public Address System
Microphones
• Intercom functionality
• Audio inputs
• Headset connection
• Powered over POE or local 48 VDC PS
• There are several types of microphones :
• Fire microphone, Zone microphone, LCD microphone
• Could have microphone extension for additional zones

Amplifiers
• Connect outputs speakers lines
• Connect inputs audio sources
• Amplifiers have different range of wattage (50w,100w, 200w,
300w, 500w, 600w,…) and could have multiplexed amplifiers
(8x80w), (8x160w), (2x650w),…
• Amplifiers could have bridges to multiply wattage
Public Address System
Sound Pressure Level
• Normal noise sound pressure level is from 60-65 db
• Audible sound alarm should be above normal noise with 10 db min.
• Maximum alarm sound pressure level is 120 db
▪ Speakers db start from 80 db
▪ Bell is 90 db
▪ Siren is 115 db
▪ Horn is 120 db
• Decay signal is 20 log (Distance)
• Each door decreases 3 db
• Doubling distance decreases 6 db
• Doubling wattage increases 3 db
Public Address System
Decibel Examples
DECIBEL SOUND EXAMPLE

10 Almost inaudible A leaf falling

20 Audible Rustles of autumnal leaves

30 Very quiet Whispering

40 Living room, quiet classroom

50 Limited sound Refrigerator working, car driving past

60 Audible Sound of human voice, machinery

70 Irritating Loud Television, several people on the telephone

80 Unpleasant Alarm clock, door bell / Speakers sound pressure level

90 Extremely unpleasant screaming, shouting / Bell sound pressure level

100 Extremely unpleasant Machine in a factory, compressor, fighter jet at 300 m

110 Extremely loud Rock concert, chainsaw


Public Address System
Decibel Examples

DECIBEL SOUND EXAMPLE

120 Human voice at its loudest / Siren Sound pressure level

130 Thunder
140 Pain threshold Siren from close by
Permanent damage
150 Fireworks
to hearing
160 Shooting with pistol or rifle
170 Avalanche firework
180 Rocket launch platform
Quality of messages are affected by :
• Level of background noise
• Signal level
• Audio source features
• Sound source location
• Acoustics in the room
Public Address System
Speakers
• Ceiling Speaker : most common used speakers, installed on ceiling, comes in 6 w, 90 db, tapping
(0.75 / 1.5 / 3 / 6 w), also could come in 10 w, 100 db, tapping (1.25 / 2.5 / 5 / 10 w)
• Wall mounted Speaker : used for wall mounted applications, comes in 6 w, 90 db, tapping (0.75 / 1.5 /
3 / 6 w)
• Projector Speaker : used in garages, warehouses and factories, resistance to mechanical damage
and changing weather, comes in 20 w, 105 db, tapping (2.5 / 5 / 10 / 20 w)
• Horn Speaker : used in areas with high level background noise and open areas, comes in 30 w, 120
db, tapping (3.75 / 7.5 / 15 / 30 w)
• Column Speaker : used for good quality speech without reverberation, comes in 60 w, 114 db, tapping
(7.5 / 15 / 30 / 60 w)
• Tunnel Speaker : used in tunnels, comes in 100 w, 130 db, tapping (25 / 50 / 100 w), waterproof IP66,
over 50 m distance
• High Power Speaker : used in stadiums and industrial area, comes in 240 w, 120 db, tapping (60 /
120 / 240 w), waterproof IP65
Public Address System

System Wiring
Public Address System

System Wiring
Public Address System
Speakers Design
• Distance between speakers is = 2 x (ceiling height – listener height), if person is standing listener height
will be 1.5 m, if person is sitting listener height will be 1 m.
Example : 2 x (3 m height – 1.5 m person ear height) = 3 m between speakers

• Regarding wall mount speakers design, it varies but we calculate it by the decay signal
equation : 20 log (distance), as an average estimation : speaker could cover 10 m in depth.
Public Address System
Speakers Design
• For redundancy we should use 2 crossing lines for 1 zone in case of any line damage
Public Address System
Speakers Design
• In our system design we make audio zones, as an example in a hotel we could have one zone to play
background music in reception and corridors, and other zone for rooms not used, but in case of alarm
both zones will have alert message.
Public Address System
Fire Voice Evacuation Scenario
• In case of fire, music and audio inputs stop, then fire floor and floor above & below should have
evacuation message, while other floors will have alert message, then after 3 minutes delay all floors
should have evacuation message.
Public Address System

Public Address System Vendors


• Ambient – Poland

• Bosch

• Toa – Japan

• Ateis – France

• JBL
Public Address System

Public Address System BOQ


Public Address System

Public Address System Financial Offer


Public Address System

Public Address System Assignment


• We have a hotel with the below design needs public address system which could plays music and could make
announcements, ceiling height is 5 m. Kindly propose the required system.
Fire Fighting System
Fire Fighting System
• Fire fighting of fire extinguishing system is similar to fire alarm system but it is used to extinguish fire.

• System has different types :


1) Manual system : for civil defense requirements
• Fire Hose reels connected to fire water tank, valves
• Extinguishers (dry power, foam, carbon dioxide, wet chemical
and fire search for electricity panels)
• Sand buckets, fire blanket

2) Clean Agent system : used for specific rooms detection where water can’t be used as it will damage
machines or devices like generator, server, data center, IT rooms, system reference code is NFPA-2001
• FM200 system : not toxic and clean gas, safe for humans and servers, used in rooms have people
inside or servers, gas name in code is HFC-227ea, its concentration ratio is (7 - 7.6) %.
• CO2 system : toxic gas, used in rooms clear from humans and servers like generator rooms.
There are other used gases with other applications like : NOVEC, AEROSOL, HALOGEN.

3) Sprinklers system : used in large areas which could require huge capacity of gas like :
factories, warehouses, storage, garages.
Fire Fighting System

System Video Introduction

[Link]
Fire Fighting System

Clean Agent System


Fire Fighting System
Clean Agent System
1) Control Panel : receives detection signals from detectors and send output signal to bell,
solenoid and horn/strobe.

2) Smoke & Heat Detectors : detect fire and send signal to control panel.

3) Gas Cylinder : contains FM200 or CO2 gas, connected with pipes, gas released within 10 sec.
cylinder capacity = protected volume x flooding factor x altitude factor (use vendor calculator)

4) Nozzles : connected at the end of pipes to spread gas in the area.

5) Pipes : connect between gas cylinder and nozzles.


6) Solenoid valve : explodes when receives signal from control panel to spread gas in pipes.

7) Bell & Horn / Strobe : makes an alarm in case of fire detection.

8) Manual release : to activate fire fighting system manually.

9) Abort switch : when we have a false alarm and cancel gas discharge.
Fire Fighting System

System Design
• Fire fighting system is designed for rooms detection like (generator rooms, data center,..etc) not for the whole
building like fire alarm system, as cylinders are expensive.

• Must have detection from 2 detectors on 2 zones.

• Zones must be crossed in case of any zone break.

• Detection Area is like fire alarm system but divided by 4.

• Double knock scenario :


▪ When 1st detector on 1st zone detects fire, bell activated and shut down HVAC.
▪ When 2nd detector on the other zone detects fire, siren/strobe activated and start counting down for releasing gas.

• Detection Scenario Video:


[Link]
Fire Fighting System
Sprinklers System
Fire Fighting System

Sprinklers System

• Sprinklers come in different shapes which are below :

• Detection Scenario :
[Link]
Fire Fighting System
Sprinklers System
• Sprinkler system have 4 different types :
1) Wet Pipe system : The most common type of sprinkler system, pipes are filled with water with
sprinklers, not all the sprinklers are activated at once, only the one who detected fire, this reduce
damage in the event of a false alarm.

2) Dry Pipe system : same wet pipe system except that pipes are pressurized by air or nitrogen not
water, water is hold by a valve until the system is activated. This system is used in cold applications
where wet pipe system could have pipes freezing.

3) Pre-Action system : is a dry pipe system but the water is hold by an electronically controlled valve
which is connected to a fire alarm system. Only after fire alarm system is activated water will enter
pipes and each sprinkler is activated individually. This system is great for applications where water
discharge could cause damage like data centers and libraries.

4) Deluge system : is designed for high-hazard areas, pipes are dry and unpressurized, sprinklers are
open, connection to a water source directly, and water is hold by a valve. When the system detects a
fire, water is pumped through pipes and discharged through all open sprinklers.
Fire Fighting System

Sprinklers System Design


Fire Fighting System

Fire Fighting System Vendors


• Fike – USA

• Tyco

• LPG

• Pyrochem

• Globe

• Viking
Fire Fighting System

Fire Fighting System BOQ


Clean Agent Fire Extinguishing System
FM-200 System c/w control panel, strobe- horn unit, 6''
alarm bell, flashing lamp, manual release station, abort
switch, discharge nozzles, optical smoke detector, wiring,
warning signs, galvanized steel piping network and all
other
accessories. contractor shall verify final gas quantities
based
on actual room dimensions (Supply and Install)
MTR B-021 (104KG) Set 1
IT B-037 (31KG) Set 1
SERVER B-012 (96.7KG) Set 1
CONTROL ROOM B-013 (61KG)
Set 1
IT B-055 (34.5KG) Set 1
IT G-043 (20.7KG) Set 1
IT G-003 (12.8KG) Set 1
IT G-065 (8.5KG) Set 1
IT 1-003 (12.8KG) Set 1
IT 1-044 (20.7KG) Set 1
IT 1-065 (8.5KG) Set 1
IT 2-002 (12.8KG) Set 1
IT 2-045 (20.7KG) Set 1
IT 2-066 (8.5KG) Set 1
IT 3-003 (12.8KG) Set 1
IT 3-042 (20.7KG) Set 1
Fire Fighting System
Fire Fighting System Financial Offer
FM200 Automatic Gas Exinguishing System Financial Offer
S. Item Description Unit. Qty. U. Price T. Price
Supply of LPG FM200 System 35 kg c/w Manual, Union, Brackets
1 LS. 1 63,500 63,500
Electrical Actuator& label
Electronic Works:-
2 Supply of Exinguishing Fire Alarm Control Panel without batteries NO. 1 7,500 7,500

3 Supply of Conventional photoelectric smoke Detector NO. 1 400 400

4 Supply of Conventional Fixed Temperature 57 C and rate of rise NO. 1 400 400

5 Supply of Manual Release Double Action c/w Back Box NO. 1 710 710

6 Supply of Abort Switch NO. 1 1,400 1,400


7 Supply of Conventional Sarin NO. 1 300 300
Supply & installation of cabling and conduit networks complete with
8 By your side 0
their accessories
Supervision visit
9 Upon your request 0
(One Day Visit)
10 Equipment installation, Testing & Commissioning Upon your request 0
Total Price In EGP Excluding VAT 74,210.00
VAT (14%) 10,389.40
Grand Total Price In EGP Including VAT 84,599.40
Nurse Call System
Nurse Call System

System Video Introduction

[Link]
Nurse Call System
• System is used in hospitals or clinics for patients to call a nurse for help.
• System has 2 types :
▪ Addressable : to know which room or bed is calling.
▪ Conventional : to know which zone which have a call and look for the flashing lamp.
• System could be analog or IP.
• System could come with speech at Nurse station and Patient station to allow the patient
to make 2-way communication call with the nurse without coming to his room.
• System consists of :
1) Control panel :
• Control panel is the main controller of the system.
• Gives power to all connected devices.
• Have back up battery power supply in case of no electricity.
• Connected to main server and software.

2) FJB :
• Fuse junction board is the connection between devices and control panel.
• Each device has a current unit (example : PS 4 CU, Reset 1 CU, PC ½ CU), FJB
have 4 zones, each zone could have 25 current units with a total of 100 current units.
Nurse Call system
3) Nurse Station :
• Nurse station is installed at nurses disk to monitor the calls of any rooms or beds.
• Nurse station LCD shows the number of calling room and the call status if it is nurse
call signal or emergency call.
• Could come in speech system with built in microphone and speaker to talk with patients
through patient station without going to the patient, also could call other nurse stations
in other nurses disks.

4) Patient Station :
• Patient station is installed at BHU Bed head unit.
• Patient station has the following features :
• Call button to be pressed from the patient attendant.
• Reset button to be pressed from the nurse after entering the room to check the patient.
• Jack for connection of call lead button to be pressed from the patient on bed.
• Emergency option to press call and reset buttons at same time in case of patient
emergency to make alarm at nurse station.
• Could come in speech system with built in microphone and speaker to talk with nurse
through nurse station.
Nurse Call system
5) Pull Cord :
• Installed at WC beside toilet or shower, could be ceiling or wall mounted, to be pulled from patient in case of any
emergency and sends emergency call to nurse station.

6) Reset Button :
• Installed beside bed, could come in patient station or stand alone, to be pressed by nurse after entering the room.

7) Over door light & Sounder :


• Installed over room door to notify nurse with the calling room, have lamp and buzzer, activated when patient press
on call button or pull toilet pull cord.

8) Corridor Display :
• Large LED display to be installed at corridors to show calling room number for nurses.

9) Code Blue :
• Code blue button to be installed beside bed, to be used by nurse to call doctors in case of emergency.
• Code blue lamp installed over room door, activated in blue colour when pressing code blue button.
Nurse Call system
System Design
Nurse Call system

Nurse Call System Vendors


• Intercall – UK

• C-Tec – UK

• Legrand
Nurse Call system
Nurse Call System BOQ
Nurse Call system

Nurse Call System Financial Offer


Disabled Alarm System
Disabled Alarm System
• This system is mandatory to be installed in airports, rail way stations, underground metro stations, hotels, schools,
hospitals, cinemas, stadiums, theatres, exhibitions area,…etc.
• Disabled Alarm have 3 types :
1) Emergency :
▪ Remote stations installed beside emergency staircase to be used by disabled persons in case of emergency like fire
to press the call button on the remote station to make a call with the control panel and talks to the operator to send
one for getting the disabled person out of building.
2) Normal Help :
▪ Advanced Remote stations with Braille feature, built in induction loop amplifier for T position disabled persons,
built in microphone and speaker to be located in service areas like parking, tickets booth, passport check, luggage
area to be used by disabled persons to press the call button on the remote station to make a call with the control
panel and talks to the operator to send one at the assembly point to help him getting to the plain or train or any.
3) Toilets :
▪ Any building must have special toilets for disabled persons help which includes pull cord beside the toilets to be
pulled from the disabled person if he has any problem or need any help inside the toilet, then an alarm signal will
be sent to the control panel and an over door light and sounder outside the toilet will be activated for any passing
person to come and help, and when the operator reach the disabled person and solve his problem, he press on the
reset button to reset the control panel and clear the alarm.
Disabled Alarm System

System Video Introduction

[Link]
Disabled Alarm System
1) Control Panel : control panel with the below functions :
▪ Handset for communications with remote units.
▪ Gives power for remote units.
▪ Fully monitoring for remote units power, programming and faults.
▪ Have LEDs for power, alarm, fault, battery
▪ Connected to back up power supply battery in case of no electricity.
▪ Could have (4,8,16,32,48,64,80,128 devices).
▪ Could be networked to other control panels to have bigger system.
▪ Have relays for integration with other systems.

2) Remote Stations : 2 way communication remote unit, single button push to activate,
hands-free, speech steered operation.

3) Advanced Remote Stations : 2 way communication remote unit with advanced features
like Braille typing, built in induction loop amplifiers, big buttons and luminescent.

4) Toilet Kits : which is 3 part kit : pull cord with 2 cords installed beside toilet, reset
button beside toilet and over door light/sounder above toilet door.
Disabled Alarm system
System Design
Disabled Alarm system
Toilets System Design
Disabled Alarm system
Mounting Positions
Disabled Alarm system
Cable Requirements

• Enhanced fire rated cable – four-core, screened, LS0H, 1.5mm.

• Recommend soft skinned, harmonised, FP200.

• Maximum cable runs can be extended by using a repeater unit.

Brown: +24V
Blue: 0V
Grey: CAN H
Black: CAN L
Disabled Alarm system
Refuge Area
• A safe place for disabled to await assistance for their evacuation.

• An enclosed area of fire-resisting construction.

• Must be served directly by a safe route of exit.

• Minimum size = 900mm x 1400mm – sufficient space for


wheelchair to manoeuvre.

• Minimum of 30 minutes fire-resisting separation.

• Wheelchair space should not reduce the width of escape route.

• Wheelchair space must not obstruct flow of persons escaping.


Disabled Alarm system
Disabled Alarm System Vendors

1) Baldwin Boxall – UK

2) Eaton

3) Notifier
Disabled Alarm system
Disabled Alarm System BOQ
Disabled Alarm system
Disabled Alarm System Financial Offer
Water & Fuel Leakage System
Water Leakage System
Water Leakage System Overview
Water Leakage System
Water Leakage System
System Benefits
Water Leakage System

System Video Introduction

[Link]
Water Leakage System
• Water Leakage system is mandatory to be installed in data centers, server rooms, control rooms, archives,
museums,… and any place which water leakage could make a big damage for.
• System has 2 types of detection :
▪ Point detection : if we know specifically the exact location which could have leakage we use point sensor
which is probe, like when we have an AC, sink, toilet, tank, tray,…etc.
▪ Linear detection : if we don’t know from where could we have the leakage, so we install a sensing cable
around the devices which we need to protect from water leakage like servers, monuments and any.
• System could be addressable or conventional :
▪ Addressable : detection is by meters of sensing cables by + / - 1 m accuracy.
▪ Conventional : detection is by zones.
Water Leakage System
Control Panel
• Gives power for devices.

• Fully monitoring for sensing cables alarm, faults and service.

• Have LCD for power, alarm, fault, battery and service.

• Have detection by meters of sensing cables by +/-1 m accuracy.

• Connected to back up power supply battery in case of no electricity.

• Control panel could have (1,4,6) zones, each zone could have : 100 m sensing cables or 15 probes.

• Could monitor the system by web interface.

• Have relays for alarm, fault and service for integration with other systems.

• Could be integrated with PC, BMS and Email


Water Leakage system
2) Power Supply : gives 220v AC to the control panel and connected to 12v battery for back up power supply in
case of no electricity.

3) Probes : point sensor to be used in specific leakage locations, when water leakage touches the probe front
metals, system will have alarm.

4) Sensing Cable :
• Could sense water leakage by two circuits inside the cable, when there is a water it connects between the two
circuits, so by this change in current, control panel is informed that there is a leakage and know the exact location
of leakage by the rate of change in current.
• Very strong could not got cut
• Available in 1,3,5,7,10,15,25 m length.
• Pipes Sensing Cable : have different type for pipes which have a cover could absorb pipes leakage.
Water Leakage system

Sensing Cable
Water Leakage system
5) Leader Cable :
• Connects sensing cable to the control panel.
• Comes in 2 core or 4 core.
• Available in 3,5,7,10,15,25 m length.

6) Modular end termination : installed at the end of sensing cable connector to close the circuit.

7) Clips and cautions : we put a clip every 1 m to fix the sensing cable on the ground and a caution every 5 m to
guide us in detection.

8) Sounder/Flasher : to make an alarm and flash when there is a leakage in any room.

9) Accessories : bulk jumper cable, female/male connectors, splice kits, branch connector, tester.
Water Leakage system
System Design
Water Leakage system
Data Center / Server Room
Water Leakage system
AC Detection
Water Leakage system
System Design
Water Leakage system
Pipes Detection
Water Leakage system
Design Inquiries
1) What are the rooms names which need water leakage system ?
2) What is the perimeter of these rooms ?
3) If you have more than one room, will they be connected to one control panel or each room will have its control
panel ?
4) If rooms will be connected to one control panel, we need to know the distance between control panel and each
room for determining the leader cable length.
5) Required system is addressable or conventional ?
6) Do they require a siren / strobe to be connected to the control panel or control panel alarm and buzeer are
enough for them ?
7) Do they required a back up power supply or not ?
8) Is there a raised floor in the room which require water leakage detection or not ?
9) Are there any water sources inside the room like (AC, water pipes, drain, pump,…etc.) ?
Fuel Leakage system
Fuel Sensing Cable
• Fuel sensing cable can detect and locate spills of gasoline, jet fuel, diesel,
crude oil and similar hydrocarbon liquids. It will not detect or react to water.
• The cable is available in outdoor (above ground), underground and indoor
versions.
• Detects fuel by chemical reactions so it take minutes not like water detection in
seconds.
• Could be connected to the same water leakage panel.
• Used in common in Oil & Gas applications, and majority requires ATEX specifications
which is available in the fuel cable.
• Comes with metal connectors.
Fuel Leakage system
Generator Room Detection
Fuel Leakage system
Oil Tank Detection
Fuel Leakage system

Optical Sensor
• Optical sensor offers fast detection within seconds for fuel oils, chemicals and water by light reflection
on the leaked liquid
• Suitable for generator, oil storage and tank rooms.
• Reusable after cleaning.
• Could come with external sensor to protect the controller from rain or weather.
Water Leakage system

Water Leakage System Vendors


• Aquilar – UK

• TTK – France
Water Leakage system

Water Leakage System BOQ

SECTION ITEM ELECTRICAL WORKS


QTY. UNIT
NO. NO. DESCRIPTION
16830 46 LIQUID LEAKAGE DETECTION SYSTEM
46.1
Supply, install, testing, commissioning and put into operation
a complete leak detection system including but not limited to:
control panel, detection cables/sensors, control cables, back-
up batteries and all needed/related accessories The system
should cover IT &Control room complete with All equipments
needed , power supplies, terminations, fittings, components,
battery charger, accessories and all necessary accessories to
finish works as per drawings, specification and standard
2 LS
Water Leakage system

Water Leakage System Financial Offer


Master Clock System
Master Clock system

System Video Introduction

[Link]
Master Clock system
• Master clock system is used to provide accurate timing for all the clocks in the building at one time with the
ability to adjust daylight savings time.
• Master clock system is necessary to be installed in applications in which timing is very important like airports, rail
way stations, underground metro, hospitals, schools, factories,…etc.

• System consists of :
▪ Master Clock : get timing and gives it to slave clocks
▪ Analog Clocks : comes in round or square shapes.
▪ Digital Clocks : comes in 4 digits or 6 digits (for showing date)
▪ World Clocks : which have different cities time zones, used in airports and hotels.
Clocks could come in single or double, double clocks are 2 single clocks with a ceiling or wall double mount.
Master Clock system
▪ Converter Box (for Wired system) : transmits data and power from master clock to wired clocks.
▪ POE Switch (for IP system) : transmits power through Ethernet cable and data from NTP servers to IP clocks.
▪ Accessories : like count down timer, buzzer, temperature sensor, covers, wire guards and double mount housing.

• Master Clock get timing from :


▪ NTP server through TCP/IP network (10 NTP servers around the world).
▪ Satellite through an antenna fixed on the roof.
Master Clock system

System Types
• Wired system

• IP system

• Wireless system
Master Clock system

Wired System

[Link]
Master Clock system
Wired System
• The 2-Wire System starts with the Master Clock sending time data to a Converter Box. The Converter
Box is powered locally at 110-240VAC and has two functions: it reduces the voltage to provide 24 volt
power to the secondary clocks, and it sends the time data every second over the same pair of electrical
wires.

• The same two electrical wires that are used to power the clock will also provide the time signal. The
clocks are connected in parallel so if one clock fails, all other clocks in the system will not be affected
and will function normally.

• System is simple to install, both analog and digital clocks may be installed on the same run, no limit for
number of Converter Boxes that can be added to the system, so system can serve anything from a
small facility with 20 clocks to mega projects with 5,000 clocks or more.
Master Clock system
Wired System
• One converter box can power many secondary clocks, this will be determined by the type and size of
the clock – analog or digital, thickness of the electrical wire used for installation and the distance
between the converter box and the last clock in the run.
• All of the above mentioned variables will determine how many secondary clocks can be powered by
one converter box, we have a Converter Box Calculator to determine how many converter boxes will
be needed for the project.
Converter Wire Thickness Length of run # Analog # of 2.5" # of 2.5" # of 4" # of 4" Current Voltage At
Load % Comments
Box #5 (mm2) (meters) clocks x 4 digits x 6 digits x 4 digits x 6 digits Consumption End of Line

Run #1 1.31 30 0 0 0 0 0 0 0% 24.0


This
setup
Run #2 1.31 30 0 0 0 0 0 0 0% 24.0
meets
the
Run #3 1.31 30 0 0 0 0 0 0 0% 24.0 specs

Total: 0 0 0 0 0 0 0% 24.0
Master Clock system

IP System

[Link]
Master Clock system
IP System
• In IP system clocks are connected through POE switch with CAT5 cable which transmits data and
power to clocks.
• In IP system no need for Master clock, as clocks could be connected to NTP servers direct through
TCP/IP network.
• Clocks programming could be held by web interface for time zone and daylight saving time
programming, also you could receive a mail for any clock failure.
• By web interface you could monitor all clocks in the project status.
Master Clock system

Wireless System

[Link]
Master Clock system
Wireless System
• A Wireless Clock System starts with a master clock with a transmitter transmits the time data to the
secondary clocks in the system wirelessly, Wireless System works autonomously, which does not rely
on existing Wi-Fi or Bluetooth infrastructure; at the same time, it has no interference with other wireless
systems that might be in the facility.
• The Sapling Wireless System is offered in 2.4GHz frequency range (approved worldwide).
• The Sapling Master Clock may interface with existing wired clock systems, allowing the facility to
upgrade from their existing clock system and benefit from wireless system advantages.
• All slave clocks have built in repeater which repeats the signal coverage of the master clock and no
need for additional master clocks for coverage.
• For multiple buildings project, we could have a network repeater which receives signal from master
clock through LAN cable, and then makes coverage and send signal to the slave clocks in its area,
also it could be connected to master clock wirelessly.
Master Clock system
Integration
• Master clock system could have integration with other systems like :

▪ Lighting

▪ HVAC

▪ Bells
Master Clock system
Master Clock RFQ Options
Master Clock system
Accessories RFQ Options
Master Clock system

Master Clock System Vendors


• Sapling – USA

• Bodet – France

• Gorgy Timing – UK
Master Clock system

Master Clock System BOQ


Master Clock system

Master Clock System Financial Offer


Audio / Visual System
Audio / Visual System

Projectors
• Projectors are measured by light output with lumens or ANSI from 800-5,000
lumens, also there are bigger projectors like cinemas and concerts projectors.
• Installed on desktop or ceiling or with elevator or as short though.
• Showed on white fixed board, rolled motorized board, tripod or interactive.
• Projector lens must be perpendicular to the center of the screen or you will
have keystone error which could be adjusted automatically in some models.
• System introduction : [Link]

HDMI & VGA Outlets


• For connecting laptops to HDMI or VGA outlets to share screen and
audio on projectors or monitors.
• Connected to switchers and matrix with HDMI, VGA and audio cables.
• Installed in wall or floor box or in cable cubby in meeting tables. HDMI
sends audio and video with same cable.
• VGA sends video signal and must have audio cable for audio signal.
Audio / Visual System

Video Conference
• Used for video meetings for companies, authorities, universities and schools.
• Consists of (codec unit which connects camera and microphone, compress
video, call other location IP address, makes management, scheduling, recording
and streaming, movable HD camera and microphone with speaker).
• System covers 6 m radius, cancel noise, share content and presentations.
• System introduction : [Link]

Audio Conference
• Used in conferences, parliament and universities.
• Consists of (control unit, master microphone which gives access for
talking and voting to delegates microphones, delegates microphones with
voting options and come with batteries in wireless, access point which gives
wireless signal to microphones and digital recorder for sessions recording).
• System could be wired or wireless, and connected to amplifier and speakers.
• System introduction : [Link]
Audio / Visual System
Video Wall
• Used in CCTV security rooms, traffic monitoring and advertising.
• Used to have multiple displays on one screen, and divided to any
combination, frameless screens are recommended for not having separations.
• Consists of (monitors, wall mounts, power supply to separate monitors from
power heat and noise, and video controller which controls using software the
input sources with their sizes, positions and monitor screens status).
• System introduction : [Link]
KVM
• KVM is to have (Keyboard, Video and Mouse) only on the desk
and remove servers at racks data center for less devices, cabling,
noise and heat at each user’s desk and for better IT maintenance.
• Also, for having access for multiple severs on multiples screens.
• System consists of : transmitter connected to the server, receiver
installed
Control Uni under user’s desk, splitter for splitting video on several
screens and matrix for combining group of servers.
• System introduction : [Link]
Audio / Visual System
Digital Signage System
• Digital signage is LCD/LED displays which show images, videos, weather
data, restaurant menus, or text.
• Installed in airports, rail way stations, metro stations, restaurants, retail
stores,…etc.
• They are used as a network of displays that are centrally managed and
individually addressed for the display of text, animations or video messages
for advertising.
• System consists of displays with wall mount, media player and a server with
software to control media.
Audio / Visual System
Martix and Switchers
• VGA inputs are combined on VGA Switcher and HDMI inputs are combined on HDMI Switcher, then VGA
and HDMI Switchers are connected to a Matrix to manage inputs and outputs
Control Unit
• Control audio/video sources, projector elevator, lighting, HVAC, binders, could
have saved modes like presentation or meeting for automatic control of devices,
controller comes with a display for easy control installed wall or desktop mounted.
Audio Sources
• Audio sources are combined on an amplifier which distributes audio to speakers, when we have more
than audio source in the room we should have feedback suppressor for echo cancellation.
Audio / Visual system
System Design
Audio / Visual system
Audio / Visual System Vendors
• 1) Video Conference : Polycom, Cisco

• 2) Audio Conference : Televic, Barco, Audio Technica

• 3) Projectors : Sony, Panasonic, Epson, Benq

• 4) HDMI & VGA outlets and cable cubby : Extron

• 5) Video Wall : Eyevis, Planar, 9x media, Bouyer

• 6) KVM : Aten, NTI

• 7) Matrix and switchers : Extron, AMX

• 8) Control unit : AMX

• 9) Digital Signage : Samsung, LG


Audio / Visual system
Audio / Visual System BOQ
Audio / Visual system
Audio / Visual System Financial Offer
Telephone System
Telephone system
Telephone System Types
• Active : devices which need power.

• Passive : devices which doesn’t need power.

Passive System Components


• PSTN : Public Switched Telephone Network which is the office responsible for
delivering telephone lines to surrounded buildings.

• MDF : Big Telephone box for distributing lines from PSTN to each building telephone
box, MDF could have from (50 – 500 pair of cables), distribute telephone cables for
group of buildings in an area.

• Tel Box : receive telephone cables from MDF and then distribute it to each apartment or
company, could have from (5 – 50 pair of cables).

• Now we have (FTTH) option which is a fiber cable comes to each building direct.
Telephone system
Passive System Design
Telephone system

Active system
(PABX) Private Automatic Branch Exchange

• Manages telephone calls in an organization internally and externally.

• Makes cost reduction for companies by using one land line with several extension rather
than using a land line for each extension, also internal call are free of charge.

• Each telephone has an extension number to be dialed internally.

• Could have external calls through (PSTN) Public Switched Telephone Network by (TSP)
Telecommunications Service Provider.

• PABX could be located as a hardware in the company or as a software over cloud and it
could be hybrid also for existing systems.
Telephone system

System Video Introduction

[Link]
Telephone system
System Components
1) PABX :
• Comes with 8 extensions and 3 outside lines, could have extension cards till 24
extensions and 8 lines, also could reach 24 outside lines and 128 extensions in
some systems.

2) Proprietary telephone set :


• Used by operator for handling several calls through several outside lines.
• Comes with LCD display, caller ID, outside buttons for choosing lines,
programmable keys for dialing extensions and speaker.
• Could have add on key module which could reach 60 key.
• Have several features like call forwarding, handle voice mail messages, auto
answer, conference, intercom.

3) Single telephone sets :


• used by occupants to receive single calls routed from operator or through IVR.
• Could come with LCD display, caller ID and speaker.
Telephone system

PABX Features
• Caller ID : shows caller number before answering on master and slave telephones.

• IVR : allow callers to call their required extension without going through an operator.

• Voice mail : allow callers could leave message if you are not available.

• Call Forwarding : for routing calls to extensions.

• Multiple devices connection : could be connected to wireless telephones, fax, answer machine, door
phone and door opener.
Telephone system

Telephone System Types


• Analog

• Digital

• VOIP

• SIP

• Hybrid
Telephone system

Telephone System Types


• Analog : uses 2 wire system which transmits data by analog signal and it is connected to Tel outlet
by RJ11 cable, which is connected to a PABX.

• Digital : same like analog but transmits data by digital signal which enables advanced features like
sound ringtone, caller ID, voice mail, recorded message, extensions for several lines.
Telephone system
VOIP
Voice Over Internet Protocol
• Uses Ethernet cables connected to data outlet by RJ45 cable connected to a
POE switch connected to a router to TCP/IP network through (ISP) Internet
Service Provider.
• PABX could be on Premise as a hardware or as a software over cloud.
• Router transmits data over cloud through VOIP provider who use servers to
make connections between VOIP phones.
• VOIP system have several features like :
• Cost Effective as no need to have a PABX system as calls are routed through
VOIP servers on cloud network.
• Easy mobility for phones which could connect remotely in any place have
internet from home, office or anywhere.
• VOIP software which enables you to make calls through your laptop or mobile
so no need even to have a telephone.
• Reliable as service exists on cloud network not on a hardware PABX which
may need maintenance, flexible upgrade no need to replace existing devices.
Telephone system
• SIP : Session Initiation Protocol
▪ It is a protocol used for VOIP systems which offers multimedia communications through a vendor
provides (UCaaS) Unified Communications as a Service.
▪ Media like : video conferencing, instant messaging, text, and other multimedia communications.

• Hybrid : combined system between Analog / Digital system and VOIP system for existing old
facilities.
Telephone system

Telephone system Vendors


1) Panasonic – China

2) Avaya – USA

3) Cisco – USA

4) Huawei – China

5) Alcatel – France
Telephone system

Telephone system BOQ


Telephone system

Telephone system Financial Offer


Barrier Gates System
Barrier Gates system

System Video Introduction

[Link]
Barrier Gates system

Barrier Gate system Body


Barrier Gates system
• System consists of :
• Arm / Beam : arm comes in 2,3,4,6 and 8 m long, could come in folding version, opens
90 degree in 1-5 sec, made of Aluminum for its low weight, comes in right hand or left
hand versions, comes with LED strips for night use and contact for not hitting cars.

• Body : metal box contains motor, gear unit and controller.

• Motor : motor operated by 220v AC power supply to operate the gear unit to move the
arm.

• Gear Unit : set of gears responsible for moving the arm barrier by the motor rotation
which installed at the bottom of the gear unit.

• Controller : controls the system, receive input signals from reader or photo sensor or
remote and send output signal to the motor to open and close the arm, controller has
several terminals for arm control : (common, open, close, stop, step by step, photo)

• Power supply and Back up Battery : gives power to the controller and the motor.
Barrier Gates system
• Photo sensor : transmitter and receiver with infrared signal for detecting car in case of closing the arm to
go up automatically for not hitting the car.

• Loop detector : cable installed at ground before the arm at exit, when car moves above it, signal is sent
to controller to open the arm automatically, also used for detecting cars under barrier for not hitting car.

• Long range reader : RFID long range reader to be accessed by cars drivers proximity cards, tags and
stickers from 2 – 10 m distance.

• Push Button and Remote control : to be connected to the controller to open and close the arm
manually.
• Demonstration video 1 : [Link] ,video 2 : [Link]
Barrier Gates system

Barrier Gate system Vendors


• FAAC – Italy

• BFT
Barrier Gates system

Barrier Gate system BOQ


Barrier Gates system

Barrier Gates system Financial Offer


Parking Management system
Parking Management system

System Video Introduction

[Link]
Parking Management system
• System is designed to manage parking facility free and occupied slots with sensors
and displays.

System Components
1) Motion Sensors : Ultrasonic Diagonal Sensor to detect cars in Parking slots, IP67.

2) LED displays : to show available free slots and number of available cars in
parking.

3) Server : is responsible for data communication with all devices installed in parking
facility and for database management.

• Sensor Detection :
Parking Management system

System Components
4) Power supply and communication module :
supplies power to devices and controls data
communication.

5) Ticketing Dispenser : issue tickets or tags for


chargeable parkings.

6) 3-way arrow displays : shows the way for exit or free


slots, available in straight, right, left and cross.

7) User interface software : web interface application


for monitoring and managing parking facility.
Parking Management system
System Design
Parking Management system

Parking Management System Vendors


• Indect – Austria

• Designa – Germany

• FAAC - Italy
Parking Management system
Parking Management System BOQ
Parking Management system
Parking Management System Financial Offer
# DESCRIPTION QTY UP/EUR TP/EUR
1 Ultrasonic Diagonal Sensor IP67 1,085 69.38 75,271.88
- UDS Casing Base 1,085
- UDS Sensor Top 1,085
2 Space indicator, RGB, Single Sided, Snapped on 1,085 10.47 11,362.12
3 C Channel mounting set 1,085 2.78 3,010.88
4 Cable Cover 1,085 1.44 1,565.66
5 Row & Level Sign 570x240x80mm, 130mm Digits, IP65 58 743.64 43,130.84
- LEDI 2.0 Digit 130mm Green 122
- LEDI 2.0 Digit 130mm Green/red X 58
- LESY 2.0 A/C straight green 58
- DIMO 2.0 58
6 Main Sign multilevel, 130mm Digits, IP65, TCP/IP 5 5,859.16 29,295.80
- LEDI 2.0 Digit 130mm Green 10
- LEDI 2.0 Digit 130mm Green/red X 5
- MAMO 2.0 15
7 Communication Module TCP/IP, in IP65 Enclosure 14 728.16 10,194.24
8 Power Supply in IP65 Enclosure 9 284.16 2,557.44
9 System server iCOM with admin and reporting licenses 1 10,449.60 10,449.60
- iCOM server 1
- iVIS license up tp 500 spaces 1
- iCOM license up to 500 spaces 1
- License per space 1,085
10 Support for preplanning, training and switch on 1 5,000.00 5,000.00
11 TOTAL SUM, IN EUROS, EXW VIENNA: 191,838.45
12 DISCOUNT: 20%
13 FINAL SUM, IN EUROS, EXW VIENNA: 153,470.76
Queuing System
Queuing system
• Queuing Management system is used to manage queues and people traffic for getting different services.
• Used in Banks, traffic departments and public services like telecommunication branches,…etc.
System consists of :
1) Control unit with power supply : main controller of system and gives power for devices.

2) Ticketing station : used by visitors to choose the service and get a number for queue.

3) Client display : 7 segment display shows the number of existing client.

4) Operator Keypad / Software : used by operator to call next client.

5) Speakers and Amplifier : for calling the client number.

6) Workstation with Software: to manage queuing system and waiting area.

7) Media Player : to play media with showing number of serving client.

8) Wide Area Screen : installed in waiting area for showing client number.
Queuing system
System Design
Queuing system

Queuing system Vendors


1) Q-Matic – Seweden

2) Alfa – Egypt

3) QMS – Malyasia
‫‪Queuing system‬‬
‫‪Queuing system BOQ‬‬
‫الكمية‬ ‫وحدة‬ ‫بيان االعمال‬ ‫م‬
‫نظام إستدعاء العميل بالشاشات‬
‫‪2‬‬ ‫عدد‬ ‫وحدة كونترول خاصة بالنظام‬ ‫‪1‬‬

‫‪66‬‬ ‫عدد‬ ‫وحدة تحكم فرعية لكل موظف شاملة شاشة رقمية ‪ 3‬خانة باإلضافة إلى زر طلب الرقم‬ ‫‪2‬‬

‫‪66‬‬ ‫عدد‬ ‫شاشات رقمية ‪ 3‬خانة موجودة أعلى كل موظف يتم ربطها بوحدة التحكم الفرعية إلظهار رقم العميل‬ ‫‪3‬‬

‫‪6‬‬ ‫عدد‬ ‫شاشات رقمية ‪ 5‬خانة على خدمة العمالء والتلر‬ ‫‪4‬‬

‫‪2‬‬ ‫عدد‬ ‫ماكينة إصدار أرقام مسلسلة إليكترونيا ً مرتبطة بالنظام شاملة وحدة طلب الخدمة‬ ‫‪5‬‬

‫‪2‬‬ ‫عدد‬ ‫البرنامج الخاص بتشغيل النظام ‪SOFTWARE‬‬ ‫‪6‬‬


‫‪30‬‬ ‫عدد‬ ‫سماعة اإلستدعاء قدرة ‪ 10‬وات‬ ‫‪7‬‬

‫‪2‬‬ ‫عدد‬ ‫بالعدد توريد وتركيب ‪amplifier‬قدرة (‪200‬وات)‬ ‫‪8‬‬

‫بالعدد توريد وتركيب جهاز كمبيوتر ‪dell‬او ‪HP‬بشاشة ‪LCD 32‬بوصه لتشغيل النظام طبقا ً للمواصفات ‪ram6 GB HARD‬‬
‫‪2‬‬ ‫عدد‬ ‫‪10‬‬
‫‪500 GBVEGA 1 GB PROCESSOR I7WINDOWS 10‬كامل مما جميعه‬
Queuing system

Queuing system Financial Offer


Data System
Data system

System Video Introduction

[Link]
Data system
Data System Types
• Active : devices which need power.
• Passive : devices which doesn’t need power.

Active System Components


• Switches : used for connecting devices to TCP/IP network, used when we require to run the data cable
more than 90m, could come with Power Over Ethernet feature (POE) for connecting (IP Telephones, IP
Cameras and Access points), switches come with (4,8,16,24,32,48) ports, and there are copper, fiber
and hybrid switches with copper ports and fiber port for connection with core switch, switches have
different types like :
▪ Edge Switch : economic switch comes with 4 or 8 ports, home routers come with built-in Edge switches.
▪ Modular Switch : enclosure switch connects modular switch cards for the required ports like 8 ports.
▪ Managed Switch : used for configurations of several VLANs on the same switch for separation between
devices like (VLAN-1 for cameras and VLAN2 for IP Telephones), also to configure each port bandwidth.
▪ Industrial Switch : weatherproof switch used in factories or outdoors which resists mechanical damage.
▪ Core Switch : Main switch which combines all switches and devices, comes with advanced features like
processor, RAMs, fans, takes more than 1U, and client IT specifies its specifications.
Data system
• Router : gateway for routing internal data to WAN network, it doesn’t have WIFI as
it is different than home routers which are combo having (Router, Access point and
a Switch) in the same device.

• Access Point : provides WIFI to facility and connected to the router by a data cable
as a standalone, takes power from a POE switch or with a 12v adaptor, installed
ceiling mounted, its coverage is 100 m2 or a circle with 8.5 m radius.

• Controller : let all access points in building as one network.

• Server : used for data storage or applications, specified by IT department of client,


could be a tower or rack mounted, different than standard PCs and workstations.
PC is used for personal use with standard specifications, but work stations come
with advanced specifications like working 24/7, better processor, better RAM,
additional outputs for additional monitors.

• Firewall : hardware advanced security for data network, used in banks and facilities
which need high security data, and also gives access for users for applications.
Data system

Data Active system Design


Data system

Passive system Components


• Patch Panel : 1U 24 RJ45 port copper patch panel, connect between data wall
outlets and switches, its function is to maintain switch ports from damage.

• Patch Cords : 0.5/1/2/3/5 m RJ45 pre-connected data cable, to connect


switches to patch panel, or devices to data outlets.

• Data Outlets : consists of RJ45 socket, frame for 1 or 2 modules and faceplate.

• Data Cables : Ethernet copper (CAT5e, CAT6, CAT6a, Cat7) or Fiber optics
cable (SM/MM) which transfer data by light impulses for large bandwidth and
long distance.

• Connectors : RJ45 connectors to be fixed to cables.

• Data Rack : contains all system devices, racks could be wall mounted or free
stand, have different dimensions.
Data system

Data Passive system Design


Data system
Data Cable Types
• Data Cable could come in :
▪ UTP : Unshielded Twisted Pair
▪ STP : Shielded Twisted Pair
▪ S/FTP : Shielded Foil Twisted Pair
• Max distance is 90 m
• After connecting cables to outlets, we should make a fluke test by a tester to test cables length, colors
arrangement, losses, if all are good we will have a pass report.
Data system
Fiber Optic Passive Components
• Fiber optic Cables : in fiber optic cable data transfers by light impulses for
fast speed in data transfer, large bandwidth, large data (1-100 GB) and
long distances (1-100 KM) without interference, there are 2 types Single-
Mode and Multi-Mode, cables consists of cladding with 125 µm and core
from (9 – 50) µm (for reference : a human hair is closer to 100 µm), cable
could have several cores for larger data and bandwidth like in Telecom.
• Fiber optic Connectors : for connecting the fiber optic cables like the
RJ45 connector in Ethernet cables.
Data system
Fiber Optic Cables Comparison
Feature Single-Mode Multi-Mode
Data Transfer sends the light one enables multiple light modes
mode at a time to be propagated at a time
Core Size 9 µm 50 µm
Distance 10 – 100 KM 0.5 – 2 KM
1 – 100 Gb 1 – 100 Gb
could send 100 Gb on could send 40 Gb on 150 m
Bandwidth
10 Km distance distance
cheaper than Multi- more expensive than Single-
Mode Mode
Cost
While its electronics
are more expensive
Color yellow orange or aqua
Application used in Telecom used in security systems
and LANs
Data system
Fiber Optic Passive Components
• Fiber optic Patch Cords : for connections between devices inside the rack.

• Fiber optic Switches : differs than the copper switches that have SFP modules
for connecting fiber optic cables, switches could have copper and fiber.

• Fiber optic SFP Module : there are different modules (SX, LX, ZX, EX), we
choose SFP module according to our requirements of speed, bandwidth and
cable type, majority SFP speed is 1 Gb, but SFP+ could reach 10-25 Gb.

• Fiber optic Patch Panel : interface between devices and switches.


Data system
Racks
Consists of :
• Rack Cabinet, dimensions (width and depth) are specified according to the dimensions
of the devices installed inside it, and height function of (RU) Rack Units (RU = 4.4 cm)
according to number of devices installed inside the rack, each device could take 1U or 2U
according to its height, we keep 1U separation between each 2 devices for ventilation.
• Cooling unit with required number of fans and thermostat according to the devices
installed inside the rack heat consumption calculations.
• 1U Cable management panel with required number of cables rings.
• 1U power distribution unit (PDU) with required number of power sockets.
• Rack shelves with number of the devices which are not rack-mounted and will be
installed on a shelf.
Small racks are installed wall mounted, but bigger racks are free stand.
Data system
Racks Dimensions
Data system

Data system Vendors


• Legrand

• Systimax – USA

• Leviton – USA

• R&M – Switzerland
Data system

Data system BOQ


Data system

Data system Financial Offer


Intercom System
Intercom system

System Video Introduction

[Link]
Intercom system

System Features
• Two-way communication
• Access for opening outdoor main door from my apartment.
• Built in microphone and speaker in main door unit.
• Access for communication internally with neighbors.
• Available with Audio and Video
• Integration with Access control system.

System Types
• Audio Intercom
• Video Intercom

System Wiring
• Analog : with 2 wires cables
• IP : with Ethernet cables
Audio Intercom system

System Components
• Main outdoor door unit : communicate with all apartments, built in
microphone and speaker, integration with access control, weatherproof.

• Apartment Audio Indoor Handset : two way communication handset,


enable door unlocking.

• Guard station : Audio guard management handset with two way


communication and enable door unlocking.

• Audio distribution module : distribute audio between main door unit and
apartments handsets, installed every floor, supports 4 apartments.

• Power supply : provides power for the intercom system.

• Buttons Extender : to be connected to main outdoor unit for additional


apartments.
Video Intercom system

System Features
• View visitor by video
• LCD display
• Picture memory with snapshot option
• Time and date display
• Voice mail
• Audio/Video clip recording
• SD card
• Unlocking door remotely
• Data sharing photo and video
• Calendar and alarm clock function
• Do not disturb mode
• Integration with existing IP CCTV cameras
• Integration with existing NVR/DVR recording
• PSTN landline integration for transferring calls to mobile phones
• Easy control by mobile application
Video Intercom system
System Components
• Main outdoor door unit : comes with HD camera, white light LEDs for night
vision, built in microphone & speaker and weatherproof.

• Apartment Video Indoor Phone : LCD screen, picture memory with snapshot
option, voice mail, audio/video clip recording, SD card, PSTN landline integration
for transferring calls to mobile phones.

• Guard Management station : guard management unit with video intercom


functioning between visitors and apartments residents, comes with LCD screen,
monitors main door unit, supports emergency alarm receipt from apartments units,
in-built card reader for ID registration.

• Video distribution module : distribute audio/video between main door unit and
apartments video phones, supports 4 apartments.

• Network Gateway : provide audio/video transmission for building.

• Network Switch : to connect system devices to TCP/IP network.


Intercom system

Video Intercom system Design


Intercom system

Audio Intercom system Design


Intercom system

Intercom system Vendors


• Panasonic – China

• Comelit – Italy

• Farfisa – Italy
Intercom system

Intercom system BOQ


MATV System
MATV system

System Video Introduction

[Link]
MATV system
• MATV system is Satellite Master Antenna Television, used for supplying and controlling number of
satellite TV and Radio channels to multiple televisions.

• Used in hotels, hospitals, gyms, clinics, apartments towers and commercial offices.

• MATV system is used rather than normal satellite TV system for the following features :
▪ Better building design : as it decreases number of satellite dishes on the building, as in stand
alone system we have to provide a satellite dish for every TV.
▪ Less Cost : for decreasing the cost of the required number of satellite dishes.
▪ Better signal : as there will be no interference for big number of satellite dishes in the same area
which will impact the receiving signal.
▪ Easy maintenance : for troubleshooting one centralized system for the whole facility rather than
dealing with several systems with several specifications.
MATV system

TV Signal Types
• TV Radio Frequency (RF) : from 47 to 862 MHZ,
contains 69 channels, received by (VHF & UHF) aerial,
for ground channels, divided to :

▪ VHF : Very High Frequency channels from 47 to 300


MHZ like ground channels 1,2 and 3.
▪ UHF : Ultra High Frequency channels from 300 to
862 MHZ like ground nile channels.

• Satellite Intermediate Frequency (IF) : from 950 to


2400 MHZ, contains 3000 channels, received by
satellite dish antenna with LNB, for satellite channels.
MATV system

Feature RF IF
MATV System Types 300 – 800 800 – 2000
Bandwidth
MHZ MHZ
• Radio Frequency (RF)
Cable Type RG-6 RG-11
• Intermediate Frequency (IF) Number of 60 3000
Channels
Head-end
Amplifier Amplifier
System Devices
Splitter Multi switch
Tap-off Receiver
Receiver TV Receiver
Less Better
Quality Resolution Resolution

Cost Cheap Expensive

Application Small Hotels Big Hotels


MATV system

System Design
MATV system
IF System Components
• Dish Antenna : collect satellite frequencies, each satellite should have an
individual dish, we could have 1,2,3 or 4 dish antennas, dish diameter is 1/2/3m
,dish is connected with LNB.

• Radio Frequency Antenna : receive VHF/UHF/FM Radio frequency signals and


send them to a combiner which combine them in one coaxial cable to the amplifier.

• LNB : convert satellite frequencies to a video signal, comes with 4 ports which
connects 4 coaxial cables for (low vertical, high vertical, low horizontal and high
horizontal).

• Amplifier : to increase db signal attenuation through distance, we need amplifier


every 100m or several switches, requires PS.

• Multi switch : we put it every floor to distribute TVs, it receives satellite cables
from above floor and send them to lower floor, and distribute cables to required
number of TVs, comes in (5(1sat)/9(2sat)/13(3sat)/17(4sat)x4/8/12/16/24/32).
MATV system

IF System Components
• Receiver : controls satellite TV & Radio channels.

• TV : receive satellite channels signal with 60-70 db.

• Coaxial cables : RG11 for high frequency signals and long distances.

• TV Wall Outlets : for connecting coaxial cables with BNC between receiver and
switch or LNB.
MATV system
MATV system Riser
MATV system

RF System Design
MATV system

RF System Components
• Same like IF has Dish Antennas, Radio frequency Antennas, LNB, Amplifier,
TV wall outlet, TV and the below devices :

• Coaxial cables : RG6 for low frequency signals and short distances.

• Head-End : connect the satellite dish antennas and the radio frequency
antennas, contains 30 cards (modulator) for channels, each modulator has 2
channels, its output is 110 db.

• Tap-Off: receive the 110 db signal coming from Head-End and adjust it for
the required db of the TV.

• Splitter : receive coaxial cable from Tap-Off from Head-End and splits it to
required number of TVs, available in (2,4,8,16 and 32 ways).
IPTV system

IPTV System Design


IPTV system

IPTV System Features


• Personalization : to choose when and what I need to watch, play back, recording,…etc.).

• Easy Installations : using network switches without the need of amplifiers for signal attenuation.

• Accessibility : could access IPTV from several devices : TV, mobile, laptop,..etc.

• Features : IPTV has several advanced features like : Video On Demand, Live TV, Pause TV, Video
Recorder, Media players, interactive games, internet browsing.

• Better signal : better quality and delivery for signals through TCP/IP network.
IPTV system
IPTV System Components
• Same like MATV has Dish Antennas, Radio frequency Antennas, LNB, Amplifier,
TV and the below devices :

• IPTV Server : contains hospitality software, manage devices and deliver video
assets like play channels and Video on Demand.

• IPTV Head-End : connect the satellite dish antennas and the radio frequency
antennas, contains channels gateway cards.

• Set Top Box (STP) : which is the channels receiver connected between TV with
HDMI cables and TCP/IP network through network switch and router with Ethernet.

• Network Switch : distribute TV signals to STPs every floor.

• Network Router : receive TV signals from IPTV server and send through the
network switches.
MATV system

MATV system Vendors


• Wisi – Germany

• Grunding – Gemrany

IPTV system Vendors


• Exterity – UK

• Cisco – USA

• NEC – Japan
MATV system

MATV system BOQ


IPTV system
IPTV system BOQ
Ser. Item Description Qty.
1.1 Dish Plate 3 x (TDS110) 1.1 M Dishes with QUATTRO LNB (TQT002) 3
1.2 Diseq Switch Diseq switch Triax TMS 17x16 2
1.3 Coaxial Cables RG11 coaxial cable, Cavel cable (L/S) L/S
1.4 VHF Antenna TRIAX Combi Combi 12 w. mast bracket Antenna / Aerial 1
Rack 19-inch equipped with power supply unit and all necessary accessories as per
1.5 RACK 36U 1
specification
2.1 Chassis Enclouser Exterity avstr-c1103-uk:- vediaStream c1103, 3-slot chassis (UK power cord) 2
Free To Air gateway Exterity avstr-g4418 :- AvediaStream g4418, octal DVB-S/S2 Tvgateway, 8 x free to air transponer can provide up to 120 FTA
2.2 3
24x FTA transponder channels
Exterity avstr-g4412 :- AvediaStream g4412, dual DVB-S/S2 Tvgateway with dual CA slotswith 2x CAM slot for Encrypted
2.3 10x CA Encrypted Channel 1
channels, for OSN subscription (2x CAM can provide up to10 scrambeld Channels
DVBT/T2 gateway
2.4 Exterity avstr-g4440 :- AvediaStream g4440 TVgateway blade, dual DVB-T/T2/C/C2 1
for Local Channels
Exterity avsrv-m8365 :-AvediaServer m8365 ArtioGuest hospitality software module creation and delivery of video assets as
2.5 Middleware application 1
play channels or Video on Demand
2.6 IPTV Server Exterity avsrv-c1520 :- AvediaServer c1520 hardware platform 1U, fixed 500GB content storage 1
3.1 DVD LG or Samsung DVD 1
Exterity avply-r9300:- AvediaPlayer r9300 receiver with FHD 1080p AV (802.3af PoE) -
Exterity STB for
4.1 LED TV includes remote control & PSU accessory, receiver external power supply, European 23
power cord
Buit in STB License
Alter. Alternative Exterity artio-stv :- Artio SmartTV Client - floating single user license 23
4.2 Samsung TVs Samsung 43" HG43-690" Smart Hospitality Full HD Display 1080p with built in STB 23
MATV system

MATV system Financial Offer


Metal Detection System
Metal Detection system

System Video Introduction

[Link]
Metal Detection system

Walk Through Gate


• Used in airports, rail way stations, metro stations, malls,…etc. to detect metal
objects by transmitting and receiving magnetic filed.
• Makes an audible alarm and visual LEDs when detecting a metal object.
• Gates come in several zones could reach 33 zones (left, right and center) from head
to feet, which confirm the exact location of metal by gate LEDs.
• Could be IP55
• Consists of upper control unit, right and left panels.
• Needs a nearby power source.
• Could come with control monitor analyser to control settings, real time monitoring,
passenger traffic and alarm history.
• Counts number of passing people and number of detected people with metals.
• Accessories : Back up battery, remote control, tester, removable wheel for
portability, rain shelter and queue barrier.
Metal Detection system
Hand Held
• Used after detecting metals by the walk through gate to detect the exact detected
area to confirm detection.
• Uses microprocessor technology.
• Operates on long life battery.
• Have audible & visual LED alarm.
• Accessories : charger, battery, belt holder, vibration and ear phone
Luggage Scanner
• Used in airports, rail way stations, metro stations, malls,…etc.
• Used to detect any suspicious object inside bags by building a picture of what is
inside the bag using X-ray, and allow security staff to check the bags themselves.
• Comes in 50x30, 65x50, 80x65, or 100x100 tunnels depends on size of bags
• Comes with 24” LCD for monitoring, could have 64x zoom.

Under Vehicle Mirror


• For checking bombs under vehicles by security.
Metal Detection system

Metal Detection system Vendors


• Garret – USA

• Rapiscan – USA

• CEIA – USA

• Elektral – Turkey
Turnstiles System
Turnstiles system

System Video Introduction

[Link]

[Link]
Turnstiles system
People Entrance Management Types
• Half Height Tripod Turnstiles : stainless steel 3 arms, could be integrated
with access control reader, comes with a LED showing route direction, comes
in right or left, used in metro stations, rail way stations, service areas,….etc.
• Double Half Height Tripod Turnstiles : same but for double lane.

• Full Height Turn stiles : stainless steel full height arms, could be integrated
with access control readers, used for a complete security like in embassies,
ministries, stadiums,…etc.
• Double Full Height Turn stiles : same but for double lane.

• Flap Barrier : barriers with stylish design and faster than turnstiles, barriers
are manufactured from glass, used in commercial offices, museums,…etc.

• Half Height Swing Gate Barrier : like turnstiles but opens in swing direction,
bi-directional, stainless steel, used in metro and railway stations.
• Full Height Swing Gate Barrier : same swing gate but with full height barrier
which prevents jumping above barrier.
Turnstiles system

Turnstiles system Vendors


• ZK – Korea

• Dormakaba – UK

• Tansa – Turkey
Technical Office Work
• In this session we will review technical office work for the following :

▪ How could we make technical submittals and what is it consists of ?

▪ How could we make material list ?

▪ How could we make compliance sheet ?

▪ How could we make SLD ?


Entertainment City - DA23022021.1103

Disabled Emergency Alarm System Financial Offer (Loop Wired)


(Baldwin Boxall - UK)

U. Price T. Price U. Price

▪ How could we make battery calculations ?


S. Item Description Part No. Qty.
(£) (£) (£)

1 Supply of 8-Way controller w/o batteries BVOC8M 1 1,550 1,550 1,690 689
1521 1480.275

Opt. Supply of Flush Mount Bezel for controller BVCRFB2 0 45 0 75 20


67.5 51.075

Supply of DTA Kit 3 Parts (White Plastic Finish)


1) Pull Switch
2 DTAKIT 8 225 1,800 298 64
2) Reset Point
3) Light/Sounder
268.2 240

Alt. Ditto but Stainless Steel Finish DTASKIT 0 325 0 390 115

▪ How could we make a financial offer ?


351 345.57

3 Supply of Omnicare Repeater & DTAKIT/S Interface BVOCRIF 8 225 1,800 280 78
252 248.512

4 Supply of Omnicare Repeater & DTAKIT/S Interface BVOCRIF 0 225 0 280 78


252 248.512

Spare Parts
0 0 0

Supply of Zone card Q1233M-7 1 245 245 78


77.5 213.125 220 4840

Supply of PSU card Q1321 1 495 495 179


179.25 492.9375 495 10890
5
Supply of PSU QSR60W 1 265 265 88
88 242 245 5390

▪ What are the payment terms, order conditions and project responsibilities ?
Supply of Toilet alarm kit DTAKIT 1 225 225 64
64 176 220 4840

Supply of Interface for DTAKIT BVOCRIF 1 225 225 78


78 214.5 220 4840

Supply & installation of cabling and conduit networks


6 By your side 0
complete with their accessories
0

Supervision visit
7 Upon your request 0
(One Day Visit)
150

8 Equipment installation & programming Upon your request 0

Total Price In GBP Excluding VAT £6,605.00


Special Discount (5%) £330.25
Site Work

• Fire Alarm : Fire rated cable 2 x 1.5 mm El Sewedy 105 c (loop) / 2 x 2.5 mm (NAC)
• CCTV : Analog : Coaxial cable / IP : Ethernet cable
• Access control system : Ethernet cable
• Public Address system : 2 wires x 1.5 mm speaker cable
• Intrusion system : Ethernet cable
• Fire Fighting : Fire resistant cable 2 x 1.5 mm (loop) / 2 mm (NAC) El Sewedy 105 c
• Nurse Call : Ethernet cable
• Disabled Alarm : Fire rated cable 4 x 1.5 mm LS0H (loop) / 2 x 1.5 mm (star)
• Water Leakage : jumper cable 4 core LSF / 2 core
• Master Clock : IP : Ethernet cable / Wired : 2 wires 0.5 mm cable
• Audio/Visual & Digital Signage : HDMI cable or VGA cable for video + audio cable
• Parking Management : 4 x 1.5 mm cable
• Queuing : Ethernet cable
• Tel : Analog : telephone cable with RJ-11 socket / IP : Ethernet cable
• Data system : Ethernet cable or Fiber optic cable
• MATV : coaxial cable / IPTV : Ethernet cable
• Intercom : Audio : 2 wires cable / IP Video : Ethernet cable
Live Demonstration
• In this session we will have live demonstration for light current systems for the following :

▪ Control panels description with their functions and features.

▪ System devices and components.

▪ Device functions and features.

▪ How could we make an alarm detection on the system.

▪ What kind of troubles could we have in systems.

▪ How could we make devices installation.

▪ How could we make termination for devices.

▪ How could we make programming for systems.


SAS systems company would like to thank you for attending our Light
current systems course, and it will be very helpful for us if you could put
your reviews on our Facebook page with the benefits you got from our
course or the weakness points which we have to improve.