FC-360 DG
FC-360 DG
[Link] |
Design Guide | VLT® AutomationDrive FC 360
Contents
1 Introduction
1.4.1 CE Mark 9
2 Safety
3.2.1 Introduction 14
3.3.1 Introduction 18
3.5.1 Overview 22
4.1.1 Overview 24
4.2.1 Overview 24
5 Specifications
6.1 Storage 44
6.3.2 Gases 45
6.3.3 Dust 45
6.5 Cooling 46
6.6 Derating 46
7.6 Motor 57
7.7 Residual Current Devices (RCD) and Insulation Resistance Monitor (IRM) 60
7.9 IT Mains 63
7.10 Efficiency 64
7.13.1 Overview 66
7.14 Harmonics 73
8.1 Introduction 77
9.1 Introduction 89
9.1.1 Overview 89
9.2 FC Protocol 91
9.2.1 Overview 91
9.4.12 Conversion 97
9.5 Examples 98
9.6.2 Overview 99
10 Application Examples
12 Appendix
1 Introduction
1.1 Purpose of the Design Guide
This design guide is intended for qualified personnel, such as:
The design guide provides technical information to understand the capabilities of the drive for integration into motor control and
monitoring systems. Its purpose is to provide design considerations and planning data for integration of the drive into a system. It caters
for selection of drives and options for a diversity of applications and installations. Reviewing the detailed product information in the
design stage enables developing a well-conceived system with optimal functionality and efficiency.
This manual is targeted at a worldwide audience. Therefore, wherever occurring, both SI and imperial units are shown.
l The operating guide provides detailed information for the installation and start-up of the drive.
l The programming guide provides greater detail on working with parameters and many application examples.
l Instructions for operation with optional equipment.
Supplementary publications and manuals are available from Danfoss website [Link].
Edition Remarks
The CE mark is intended to eliminate technical barriers to free trade between the EC and EFTA states inside the ECU. The CE mark does
not regulate the quality of the product. Technical specifications cannot be deduced from the CE mark.
The directive mandates that the equipment design must ensure the safety and health of people and livestock, and the preservation of
material by ensuring the equipment is properly installed, maintained, and used as intended. Danfoss CE labels comply with the Low
Voltage Directive, and Danfoss provides a declaration of conformity upon request.
A drive can be used as a standalone device or as part of a more complex installation. Devices in either of these cases must bear the CE
mark. Systems do not have to be CE-marked but must comply with the basic protection requirements of the EMC directive.
2 Safety
2.1 Safety Symbols
The following symbols are used in Danfoss documentation.
DANGER
Indicates a hazardous situation which, if not avoided, will result in death or serious injury.
WARNING
Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION
Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
NOTICE
Indicates information considered important, but not hazard-related (for example, messages relating to property damage).
The guide also includes ISO warning symbols related to hot surfaces and burn hazard, high voltage and electrical shock, and referring to
the instructions.
Qualified personnel are defined as trained staff, who are authorized to install, commission, and maintain equipment, systems, and
circuits in accordance with pertinent laws and regulations. Also, the qualified personnel must be familiar with the instructions and safety
measures described in this manual.
WARNING
HIGH VOLTAGE
Drives contain high voltage when connected to AC mains input, DC supply, load sharing, or permanent
motors. Failure to use qualified personnel to install, start up, and maintain the drive can result in death or
serious injury.
l Only qualified personnel must install, start up, and maintain the drive.
l Before performing any service or repair work, use an appropriate voltage measuring device to make sure
that there is no remaining voltage on the drive.
WARNING
UNINTENDED START
When the drive is connected to AC mains, DC supply, or load sharing, the motor may start at any time.
Unintended start during programming, service, or repair work can result in death, serious injury, or property
damage. Start the motor with an external switch, a fieldbus command, an input reference signal from the local
control panel (LCP), via remote operation using MCT 10 software, or after a cleared fault condition.
l Disconnect the drive from the mains.
l Press [Off/Reset] on the LCP before programming parameters.
l Ensure that the drive is fully wired and assembled when it is connected to AC mains, DC supply, or load
sharing.
WARNING
DISCHARGE TIME (20 MINUTES)
The drive contains DC-link capacitors, which can remain charged even when the drive is not powered. High
voltage can be present even when the warning LED indicator lights are off.
Failure to wait 20 minutes after power has been removed before performing service or repair work can result
in death or serious injury.
l Stop the motor.
l Disconnect AC mains and remote DC-link power supplies, including battery back-ups, UPS, and DC-link
connections to other drives.
l Disconnect or lock PM motor.
l Wait for the capacitors to discharge fully. The minimum waiting time is 20 minutes.
l Before performing any service or repair work, use an appropriate voltage measuring device to make sure
that the capacitors are fully discharged.
WARNING
ELECTRICAL SHOCK HAZARD - LEAKAGE CURRENT HAZARD >3.5 MA
Leakage currents exceed 3.5 mA. Failure to connect the drive properly to protective earth (PE) can result in
death or serious injury.
l Ensure reinforced protective earthing conductor according to IEC 60364-5-54 cl. 543.7 or according to
local safety regulations for high touch current equipment. The reinforced protective earthing of the drive
can be done with:
WARNING
EQUIPMENT HAZARD
Contact with rotating shafts and electrical equipment can result in death or serious injury.
l Ensure that only trained and qualified personnel perform installation, start-up, and maintenance.
l Ensure that electrical work conforms to national and local electrical codes.
l Follow the procedures in this guide.
CAUTION
INTERNAL FAILURE HAZARD
An internal failure in the drive can result in serious injury when the drive is not properly closed.
l Ensure that all safety covers are in place and securely fastened before applying power.
NOTICE
HIGH ALTITUDES
l For installation at altitudes above 2000 m (6562 ft), contact Danfoss regarding PELV.
Table 2: Power Ratings, Weights, and Dimensions, Enclosure Sizes J8–J9, 380–480 V
Enclosure size J8 J9
IP 20 20
For details of any setup required, in particular motor parameters, refer to the programming guide.
The drive is protected against short circuits on the motor side by current measurement in each of the 3 motor phases. A short circuit
between 2 output phases causes an overcurrent in the inverter. The inverter is turned off when the short-circuit current exceeds the
allowed value (Alarm 16, Trip Lock).
Mains side
A drive that works correctly limits the current it can draw from the supply. Still, it is recommended to use fuses and/or circuit breakers on
the supply side as protection if there is component break-down inside the drive (1st fault).
NOTICE
To ensure compliance with IEC 60364 for CE, it is mandatory to use fuses and/or circuit breakers.
The voltage in the DC link is increased when the motor acts as a generator. This situation occurs in the following cases:
l The load rotates the motor at constant output frequency from the drive, that is, the load generates energy.
l During deceleration (ramp-down) if the inertia moment is high, the friction is low, and the ramp-down time is too short for the
energy to be dissipated as a loss throughout the drive system.
l Incorrect slip compensation setting causing higher DC-link voltage.
l Back EMF from PM motor operation. If coasted at a speed which is higher than nominal speed, the PM motor back EMF can
potentially exceed the maximum voltage tolerance of the drive and cause damage. To help prevent this situation, the value of
parameter 4-19 Max Output Frequency is automatically limited based on an internal calculation based on the value of parameter
1-40 Back EMF at 1000 RPM, parameter 1-25 Motor Nominal Speed, and parameter 1-39 Motor Poles.
l The overvoltage can be handled either using a brake function (parameter 2-10 Brake Function) and/or using overvoltage control
(parameter 2-17 Over-voltage Control).
Brake functions
AC brake is an alternative to improving braking without using a brake resistor. This function controls an over-magnetization of the motor
when the motor is acting as a generator. Increasing the electrical losses in the motor allows the OVC function to increase the braking
torque without exceeding the overvoltage limit.
NOTICE
AC brake is not as effective as dynamic braking with a resistor.
By automatically extending the ramp-down time, OVC reduces the risk of the drive tripping due to an overvoltage on the DC link.
NOTICE
Do not enable OVC in hoisting applications.
Ground fault
The drive provides low-impedance ground fault protection and high-impedance ground fault protection due to configuration of current
transducer on the output phases. Depending on whether the LCP parameter 0-06 GridType is set to IT grid or not, different protection
algorithms are executed.
Ground fault is detected during start-up stage and on-the-fly stage. After receiving the protection signals, the drive is coasted.
A fast trip/warning option is available by utilizing LCP parameters (parameter 14-17 Fast Mains Phase Loss Level and parameter 14-18
Fast Mains Phase Loss Min Power) when a quick response to mains imbalance is expected.
A power limit function limits the power distributed to the motor (power limit motor mode). Also, the power limit function can limit
generative power fed back into the mains supply (AFE) or fed to a brake resistor (power limit generator mode). The power limit function
is designed for flux open-loop control/closed-loop control and can be used for all motor types with flux control core (ASMPM).
Torque limit
The torque limit feature protects the motor against overload, independent of the speed. Torque limit is controlled in parameter 4-16
Torque Limit Motor Mode and parameter 4-17 Torque Limit Generator Mode. The time before the torque limit warning trips is controlled
in parameter 14-25 Trip Delay at Torque Limit.
Current limit
The current limit is controlled in parameter 4-18 Current Limit, and the time before the drive trips is controlled in parameter 14-24 Trip
Delay at Current Limit.
Speed limit
l Minimum speed limit: parameter 4-12 Motor Speed Low Limit [Hz] limits the minimum operating speed range of the drive.
l Maximum speed limit: parameter 4-19 Max Output Frequency limits the maximum output speed that the drive can provide.
ETR is an electronic feature that simulates a bimetal relay based on internal measurements. The characteristic is shown in the illustration
in 3.3.4 Motor Thermal Protection.
Overvoltage
The inverter turns off to protect the transistors and the DC link capacitors when a certain hard-coded voltage level is reached.
Overtemperature
The drive has built-in temperature sensors and reacts immediately to critical values via hard-coded limits.
As a response to a critical level, the drive adjusts the switching frequency. For high internal temperatures and low motor speed, the drive
can also force the PWM pattern to SFAVM.
NOTICE
The automatic derating is different when parameter 14-55 Output Filter is set to [1] Sine-Wave Filter.
l Increased efficiency.
l Reduced heating.
l Quieter operation.
There is no need to select a V/Hz curve because the drive automatically adjusts motor voltage.
Automatic switching frequency modulation regulates these conditions automatically to provide the highest switching frequency
without overheating the drive. By providing a regulated high switching frequency, it quiets motor operating noise at slow speeds, when
audible noise control is critical, and produces full output power to the motor when required.
An automatic feature of the drive is load-dependent switching frequency control. This feature allows the motor to benefit from as high a
switching frequency as the load allows.
l Transients.
l Momentary drop-outs.
l Short voltage drops.
l Surges.
The drive automatically compensates for input voltages ±10% from the nominal to provide full rated motor voltage and torque. With
auto restart selected, the drive automatically powers up after a voltage trip. With flying start, the drive synchronizes to motor rotation
before start.
Torque limit
The torque limit protects the motor from being overloaded independent of the speed. Torque limit is controlled in parameter 4-16
Torque Limit Motor Mode and parameter 4-17 Torque Limit Generator Mode. Parameter 14-25 Trip Delay at Torque Limit controls the
time before the torque limit warning trips.
Current limit
Parameter 4-18 Current Limit controls the current limit, and parameter 14-24 Trip Delay at Current Limit controls the time before the
current limit warning trips.
Parameter 4-12 Motor Speed Low Limit [Hz] sets the minimum output speed that the drive can provide.
Parameter 4-14 Motor Speed High Limit [Hz] or parameter 4-19 Max Output Frequency sets the maximum output speed that the drive
can provide.
The drive ETR function measures the actual current, speed, and time to calculate motor temperature. The function also protects the
motor from being overheated (warning or trip). An external thermistor input is also available. ETR is an electronic feature that simulates a
bimetal relay based on internal measurements. The characteristic is shown in Figure 1.
Figure 1: ETR
The X-axis shows the ratio between Imotor and Imotor nominal. The Y-axis shows the time in seconds before the ETR cuts off and trips the
drive. The curves show the characteristic nominal speed at twice the nominal speed and at 0.2 x the nominal speed.
At lower speed, the ETR cuts off at lower heat due to less cooling of the motor. In that way, the motor is protected from being overheated
even at low speed. The ETR feature calculates the motor temperature based on actual current and speed. The calculated temperature is
visible as a readout parameter in parameter 16-18 Motor Thermal.
The motor ETR function is based on NEMA thermal relay function Class 10.
NOTICE
The drive contains a software ETR function, which means that the drive has no information about what happens with the motor at
different ambient temperatures and/or what happens at 1000 m above sea level. The software ETR function cannot fully replace
a thermistor relay, because the thermistor relay includes a PTC sensor mounted on the motor, which is controlling the relay.
However, the software ETR function is flexible and takes different parameters into account to get the required results. Besides the
software ETR function, the drive has other protection features, for example, current limit and inverter thermal. In many situations,
these features protect the drive and motor against overloads.
The drive can be configured (parameter 14-10 Mains Failure) to different types of behavior during mains dropout:
l Coast with flying start whenever mains return (parameter 1-73 Flying Start).
l Kinetic back-up.
l Controlled ramp down.
Flying start
This selection makes it possible to catch a motor that is spinning freely due to a mains dropout.
Kinetic back-up
This selection ensures that the drive runs as long as there is energy in the system. For short mains dropout, the operation is restored after
mains return, without bringing the application to a stop or losing control at any time. Several variants of kinetic back-up can be selected.
Configure the behavior of the drive at mains dropout in parameter 14-10 Mains Failure and parameter 1-73 Flying Start.
The condition for an event can be a particular status, or that the output from a logic rule or a comparator operand becomes TRUE. The
condition leads to an associated action as shown in the following illustration.
e30bb671.14
Par. 13-51 Par. 13-52
SL Controller Event SL Controller Action
Running Coast
Warning Start timer
Torque limit Set Do X low
Digital input X 30/2 Select setup 2
... ...
Par. 13-43
Logic Rule Operator 2
...
...
Par. 13-11
Comparator Operator
=
TRUE longer than..
...
...
Events and actions are each numbered and linked in pairs (states), which means that when event [0] is fulfilled (attains the value TRUE),
action [0] is executed. After the 1st action is executed, the conditions of the next event are evaluated. If this event is evaluated as true,
then the corresponding action is executed. Only 1 event is evaluated at any time. If an event is evaluated as false, nothing happens in
the SLC during the current scan interval, and no other events are evaluated. When the SLC starts, it only evaluates event [0] during each
scan interval. Only when event [0] is evaluated as true, the SLC executes action [0] and starts evaluating the next event. It is possible to
program 1–20 events and actions. When the last event/action has been executed, the sequence starts over again from event [0]/action
[0]. The following illustration shows an example with 4 event/actions:
e30ba062.15
Start
event P13-01
State 1
13-51.0
13-52.0 State 2
Stop 13-51.1
event P13-02 13-52.1
Stop
event P13-02
State 4
13-51.3
13-52.3
State 3
13-51.2
13-52.2
Stop
event P13-02
Comparators
Comparators are used for comparing continuous variables (output frequency, output current, analog input, and so on) to fixed preset
values.
e30bb672.10
Par. 13-11
Comparator Operator
Par. 13-10
Comparator Operand
=
Par. 13-12 TRUE longer than.
Comparator Value ...
...
Figure 4: Comparators
Logic rules
Combine up to 3 boolean inputs (TRUE/FALSE inputs) from timers, comparators, digital inputs, status bits, and events using the logical
operators AND, OR, and NOT.
e30bb673.10
Par. 13-41 Par. 13-43
Logic Rule Operator 1 Logic Rule Operator 2
Par. 13-40
Logic Rule Boolean 1
Par. 13-42
Logic Rule Boolean 2 . . .
... ...
...
Par. 13-44
Logic Rule Boolean 3
l AC brake
The brake energy is distributed in the motor by changing the loss conditions in the motor (parameter 2-10 Brake Function = [2]). The
AC brake function cannot be used in applications with high cycling frequency since this situation overheats the motor.
l DC brake
An over-modulated DC current added to the AC current works as an eddy current brake (parameter 2-02 DC Braking Time ≠ 0 s).
e30bg823.10
225 mm (8.9 in)
l Wide compatibility, a high level of availability, support for all major PLC vendors, and compatibility with future versions.
l Fast, efficient communication, transparent installation, advanced diagnosis, and parameterization and auto-configuration of process
data via a GSD file.
l Acyclic parameterization using PROFIBUS DP-V1, PROFIdrive, or Danfoss FC profile state machines.
l Same PPO types as the VLT® PROFIBUS DP-V1 MCA 101 for easy migration to PROFINET.
l Built-in web server for remote diagnosis and reading out of basic drive parameters.
l Supports MRP.
l Implementation in accordance with Conformance Class B.
5 Specifications
5.1 Electrical Data
Table 3: Electrical Data for Normal Overload, Mains Supply 3x380–480 V AC
Enclosure size J8 J8 J8 J9 J9 J9
Typical shaft output at 400 V [kW] 110 132 160 200 250 315
Typical shaft output at 460 V [hp] 150 200 250 300 350 450
Continuous (at 400 V) [A] 212 260 315 395 480 588
Intermittent (60 s overload) (at 400 V) [A] 233 286 347 435 528 647
Continuous (at 460 V) [A] 190 240 302 361 443 535
Intermittent (60 s overload) (at 460 V) [A] 209 264 332 397 487 589
Continuous kVA (at 400 V) [kVA] 147 180 218 274 333 407
Continuous kVA (at 460 V) [kVA] 151 191 241 288 353 426
Continuous (at 400 V) [A] 204 251 304 381 463 567
Continuous (at 460 V) [A] 183 231 291 348 427 516
Mains and motor [mm2 (AWG)] 2x95 (2x3/0) 2x185 (2x350 mcm)
Maximum external mains fuses [A] 315 350 400 550 630 800
Estimated power loss at 400 V [W] 2559 2954 3770 4116 5137 6674
Estimated power loss at 460 V [W] 2261 2724 3628 3569 4566 5714
Efficiency [%] 98
Enclosure size J8 J8 J8 J9 J9 J9
Typical shaft output at 400 V [kW] 90 110 132 160 200 250
Typical shaft output at 460 V [hp] 125 150 200 250 300 350
Table 4: Electrical Data for High Overload, Mains Supply 3x380–480 V AC (continued)
Continuous (at 400 V) [A] 177 212 260 315 395 480
Intermittent (60 s overload) (at 400 V) [A] 266 318 390 473 593 720
Continuous (at 460 V) [A] 160 190 240 302 361 443
Intermittent (60 s overload) (at 460 V) [A] 240 285 360 453 542 665
Continuous kVA (at 400 V) [kVA] 123 147 180 218 274 333
Continuous kVA (at 460 V) [kVA] 127 151 191 241 288 353
Continuous (at 400 V) [A] 171 204 251 304 381 463
Continuous (at 460 V) [A] 154 183 231 291 348 427
Mains and motor [mm2 (AWG)] 2x95 (2x3/0) 2x185 (2x350 mcm)
Maximum external mains fuses [A] 315 350 400 550 630 800
Estimated power loss at 400 V [W] 2031 2289 2923 3093 4039 5004
Estimated power loss at 460 V [W] 1828 2051 2089 2872 3575 4458
Efficiency [%] 98
Maximum imbalance temporary between mains phases 3.0% of rated supply voltage(1)
During low mains voltage or a mains dropout, the drive continues until the DC-link voltage drops below the minimum stop level, which
corresponds typically to 15% below the lowest rated supply voltage of the drive. Power-up and full torque cannot be expected at mains
voltage lower than 10% below the lowest rated supply voltage of the drive.
The drive is suitable for use on a circuit capable of delivering up to 100 kA short-circuit current rating (SCCR) at 480/600 V.
Relative humidity 5%–95% (IEC 721-3-3; Class 3K3 (non-condensing) during opera-
tion)
- with full output power of typical EFF2 motors (up to 90% output Maximum 50 °C (122 °F)(1)
current)
Maximum altitude above sea level without derating 1000 m (3281 ft)
Maximum altitude above sea level with derating 3000 m (9842 ft)
•. Rated load.
•. 90% rated frequency.
•. Switching frequency factory setting.
•. Switching pattern factory setting.
Maximum cross-section to control terminals, rigid wire 1.5 mm2/16 AWG (2x0.75 mm2)
Maximum cross-section to control terminals, cable with enclosed 0.5 mm2/20 AWG
core
All digital inputs are galvanically isolated from the supply voltage (PELV) and other high voltage terminals.
Maximum current 30 mA
Bandwidth 100 Hz
The analog inputs are galvanically isolated from the supply voltage (PELV) and other high voltage terminals.
e30bd310.10
PELV isolation
+ 24 V
Control Mains
18
High
voltage Motor
31
Functional
isolation
RS-485 DC Bus
NOTICE
HIGH ALTITUDES
l For installation at altitudes above 2000 m (6562 ft), contact Danfoss regarding PELV.
The digital output is galvanically isolated from the supply voltage (PELV) and other high voltage terminals.
The analog output is galvanically isolated from the supply voltage (PELV) and other high voltage terminals.
Maximum terminal load (AC-1)(1)on 1–2 (NO) (Resistive load)(2) 400 V AC, 2 A
Maximum terminal load (AC-15)(1) on 1–2 (NO) (Inductive load @ 240 V AC, 0.2 A
cosφ 0.4)
Maximum terminal load (DC-13)(1) on 1–2 (NO) (Inductive load) 24 V DC, 0.1 A
Maximum terminal load (AC-1)(1) on 1–3 (NC) (Resistive load) 240 V AC, 2 A
Maximum terminal load (AC-15)(1) on 1–3 (NC) (Inductive load @ 240 V AC, 0.2 A
cosφ 0.4)
Maximum terminal load (DC-13)(1) on 1–3 (NC) (Inductive load) 24 V DC, 0.1 A
Maximum terminal load (AC-1)(1) on 4–5 (NO) (Resistive load)(2) 400 V AC, 2 A
Maximum terminal load (AC-15)(1) on 4–5 (NO) (Inductive load @ 240 V AC, 0.2 A
cosφ 0.4)
Maximum terminal load (DC-13)(1) on 4–5 (NO) (Inductive load) 24 V DC, 0.1 A
Maximum terminal load (AC-1)(1) on 4–6 (NC) (Resistive load) 240 V AC, 2 A
Maximum terminal load (AC-15)(1) on 4–6 (NC) (Inductive load @ 240 V AC, 0.2 A
cosφ 0.4)
Maximum terminal load (DC-13)(1) on 4–6 (NC) (Inductive load) 24 V DC, 0.1 A
The relay contacts are galvanically isolated from the rest of the circuit by reinforced isolation (PELV).
The RS485 serial communication circuit is galvanically isolated from the supply voltage (PELV).
Terminal number 12
The 24 V DC supply is galvanically isolated from the supply voltage (PELV), but has the same potential as the analog and digital inputs
and outputs.
Terminal number 50
Maximum load 15 mA
The 10 V DC supply is galvanically isolated from the supply voltage (PELV) and other high voltage terminals.
System response time (terminals 18, 19, 27, 29, 32, and 33) ≤2 ms
Scan interval 1 ms
e30bv156.10
61 (2.4)
128 (5.0)
660 (26.0)
495 (19.5)
e30bf801.10
375 (14.8)
82 (3.2)
39 (1.5)
18 (0.7)
20 (0.8)
e30bf802.10
250 (9.8)
A
180 (7.1)
A
33 (1.3)
123 M10
(4.8)
130 (5.1)
25 (1.0)
78 (3.1)
200 (7.9)
889 (35.0)
844 (33.2)
656 (25.8)
25 (1.0)
11 (0.4)
M10
20 (0.8)
24
200 (7.9) (0.9)
9 (0.3)
e30bg615.10
1
2
188 (7.4)
83 (3.3)
0.0
3
101 (4.0)
145 (5.7)
184 (7.2)
223 (8.8)
22 (0.9)
62 (2.4)
0.0
e30bg573.10
1 2
272 (10.7)
244 (9.6)
0.0
0.0
3
10 (0.4)
145 (5.7)
182 (7.2)
59 (2.3)
3X M8x18 M10
0
13 (0.5)
32 (1.3)
M10
13 (0.5)
32 (1.3)
5 Motor terminals
e30bv157.10
59 (2.3)
176 (6.9)
868 (34.2)
611 (24.1)
e30bf803.10
39 (1.5)
375 (14.8)
18 (0.7)
142 (5.6)
20 (0.8)
148 (5.8)
1050 (41.3)
e30bf804.10
350 (13.8)
280 (11.0)
A
A
33 (1.3)
107
(4.2)
1122 (44.2)
213 (8.4)
320 (12.6)
1096 (43.1)
1051 (41.4)
857 (33.7)
B
40
(1.6)
11 (0.4)
24 (0.9)
20 (0.8)
B
9 (0.3)
271 (10.7)
e30bg616.10
1
319 (12.6) 2
200 (7.9)
0.0
3
265 (10.4)
319 (12.6)
149 (5.8)
211 (8.3)
33 (1.3)
91 (3.6)
o.o
3 Ground terminals
e30bg574.10
1 2
255 (10.0)
284 (11.2)
0.0
0.0
13 (0.5) M10
259 (10.2)
200 (7.9)
91 (3.6)
3X M10X20
0
5
22 (0.9)
15 (0.6)
M10
18 (0.7)
35 (1.4)
19 (0.8)
38 (1.5)
5 Motor terminals
Periodic forming (capacitor charging) is not necessary during storage unless storage exceeds 12 months.
WARNING
RISK OF INJURY OR DEATH
Follow local safety regulations for lifting heavy weights. Failure to follow recommendations and local safety regulations can result
in death or serious injury.
l Ensure that the lifting equipment is in proper working condition.
l See chapter Product Overview and Features for the weight of the different enclosure sizes.
l Maximum diameter for bar: 20 mm (0.8 in).
l The angle from the top of the drive to the lifting cable: 60° or greater.
e30bv158.10
65° min
NOTICE
CONDENSATION
Moisture can condense on the electronic components and cause short circuits. Avoid installation in areas subject to frost.
Install an optional space heater when the drive is colder than the ambient air. Operating in standby mode reduces the risk of
condensation as long as the power dissipation keeps the circuitry free of moisture.
NOTICE
EXTREME AMBIENT CONDITIONS
Hot or cold temperatures compromise unit performance and longevity.
l Do not operate in environments where the ambient temperature exceeds 55 °C (131 °F).
l The drive can operate at temperatures down to -10 °C (14 °F). However, proper operation at rated load is only guaranteed at 0
°C (32 °F) or higher.
l If temperature exceeds ambient temperature limits, extra air conditioning of the cabinet or installation site is required.
6.3.2 Gases
Aggressive gases, such as hydrogen sulphide, chlorine, or ammonia can damage the electrical and mechanical components. The unit
uses conformal-coated circuit boards to reduce the effects of aggressive gases. For conformal coating class specifications and ratings, see
chapter Ambient Conditions.
6.3.3 Dust
When installing the drive in dusty environments, pay attention to the following:
Periodic maintenance
When dust accumulates on electronic components, it acts as a layer of insulation. This layer reduces the cooling capacity of the
components, and the components become warmer. The hotter environment decreases the life of the electronic components. Keep the
heat sink and fans free from dust build-up.
Cooling fans
Fans provide airflow to cool the drive. When fans are exposed to dusty environments, the dust can damage the fan bearings and cause
premature fan failure. Also, dust can accumulate on fan blades causing an imbalance which prevents the fans from properly cooling the
unit.
NOTICE
Improper mounting can result in overheating and reduced performance.
J8 X(1) –
J9 X(1) –
1) Can be wall-mounted, but Danfoss recommends that the drive is panel-mounted inside an enclosure due to its protection rating.
Mounting considerations:
l Locate the unit as near to the motor as possible. See the chapter Cable Lengths and Cross-sections for the maximum motor cable
length.
l Ensure unit stability by mounting the unit to a solid surface.
l Ensure that the strength of the mounting location supports the unit weight.
l Ensure that there is enough space around the unit for proper cooling. Refer to the chapter Back Channel Cooling.
l Ensure enough access to open the door.
l Ensure cable entry from the bottom.
6.5 Cooling
l Ensure that top and bottom clearance for air cooling is provided. Clearance requirement: 225 mm (9 in).
l Provide sufficient airflow flow rate. See the following table.
l Consider derating for temperatures starting between 45 °C (113 °F) and 50 °C (122 °F) and elevation 1000 m (3300 ft) above sea level.
See the chapter Derating for detailed information on derating.
The drive utilizes a back-channel cooling concept that removes heat sink cooling air. The heat sink cooling air carries approximately 90%
of the heat out of the back channel of the drive. Redirect the back-channel air from the panel or room by using:
l Duct cooling
Back-channel cooling kits are available to direct the heat sink cooling air out of the panel when IP20/Chassis drives are installed in
Rittal enclosures. Use of these kits reduces the heat in the panel and smaller door fans can be specified.
l Back-wall cooling
Installing top and base covers to the unit allows the back-channel cooling air to be ventilated out of the room.
Enclosure size Door fan/top fan [m3/hr (cfm)] Heat sink fan [m3/hr (cfm)]
6.6 Derating
6.6.1 Overview of Derating
Derating is a method used to reduce output current to avoid tripping the drive when high temperatures are reached within the
enclosure. If certain extreme operating conditions are expected, a higher-powered drive can be selected to eliminate the need for
derating. This is called manual derating. Otherwise, the drive automatically derates the output current to eliminate the excessive heat
generated by extreme conditions.
Manual derating
When the following conditions are present, Danfoss recommends selecting a drive 1 power size higher (for example H132 instead of
H110):
Automatic derating
If the following operating conditions are found, the drive automatically changes switching frequency or switching pattern (PWM to
SFAVM) to reduce excessive heat within the enclosure:
A problem can occur at low RPM values in constant torque applications. In a constant torque application, a motor can overheat at low
speeds because less cooling air is being provided by the fan within the motor.
If the motor is run continuously at an RPM value lower than half of the rated value, the motor must be supplied with extra air cooling. If
extra air cooling cannot be provided, a motor designed for low RPM/constant torque applications can be used instead.
Extra cooling or derating of the motor is not required in variable torque applications where the torque is proportional to the square of
the speed, and the power is proportional to the cube of the speed. Centrifugal pumps and fans are common variable torque applications.
NOTICE
FACTORY DERATING
Danfoss drives are already derated for operational temperature (55 °C (131 °F) TAMB, MAX and 50 °C (122 °F) TAMB, AVG).
Use the graphs in the following table to determine if the output current must be derated based on switching frequency and ambient
temperature. When referring to the graphs, Iout indicates the percentage of rated output current, and fsw indicates the switching
frequency.
Enclosure size Switching pattern High overload HO, 150% Normal overload NO, 110%
e30bx474.11
e30bx473.11
100
100
90
Iout [% ]
90
Iout [% ]
80
80
70 45 ˚C (113 ˚F)
50 ˚C (122 ˚F)
70 60
50 ˚C (122 ˚F) 55 ˚C (131 ˚F)
55 ˚C (131 ˚F)
60 50
0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9
fsw [kHz] fsw[kHz]
e30bx476.11
e30bx475.11
100 100
Iout [% ]
90
90
Iout [% ]
80
80
70 40 ˚C (104 ˚F)
70 45 ˚C (113 ˚F) 45 ˚C (113 ˚F)
50 ˚C (122 ˚F) 60 50 ˚C (122 ˚F)
55 ˚C (131 ˚F) 55 ˚C (131 ˚F)
60
0 1 2 3 4 5 6 50
fsw[kHz] 0 1 2 3 4 5 6
fsw[kHz]
WARNING
INDUCED VOLTAGE
Induced voltage from output motor cables from different drives that are run together can charge equipment capacitors even
with the equipment turned off and locked out. Failure to run output motor cables separately or use shielded cables could result in
death or serious injury.
l Run output motor cables separately or use shielded cables.
l Simultaneously lock out all the drives.
WARNING
SHOCK HAZARD
The drive can cause a DC current in the ground conductor and thus result in death or serious injury. Failure to follow the
recommendation means that the RCD cannot provide the intended protection.
l When a residual current-operated protective device (RCD) is used for protection against electrical shock, only an RCD of Type
B is allowed on the supply side.
Overcurrent protection
l Extra protective equipment such as short circuit protection or motor thermal protection between drive and motor is required for
applications with multiple motors.
l Input fusing is required to provide short circuit and overcurrent protection. If fuses are not factory-supplied, the installer must
provide them. See maximum fuse ratings in the chapter Fuses and Circuit Breakers.
See the chapter Cable Lengths and Cross-sections for recommended wire sizes and types.
CAUTION
PROPERTY DAMAGE
Protection against motor overload is not included in the default setting. To add this function, set parameter 1-90 Motor Thermal
Protection to [ETR trip] or [ETR warning]. For the North American market, the ETR function provides class 20 motor overload
protection in accordance with NEC. Failure to set parameter 1-90 Motor Thermal Protection to [ETR trip] or [ETR warning] means
that motor overload protection is not provided and, if the motor overheats, property damage can occur.
NOTICE
All cabling must comply with national and local regulations on cable cross-sections and ambient temperature. Non-UL
applications can use 75 °C (167 °F) and 90 °C (194 °F) copper conductors.
The power cable connections are located as shown in the following illustration. See chapter Specifications for correct dimensioning of
motor cable cross-section and length.
For protection of the drive, use the recommended fuses unless the unit has built-in fuses. Recommended fuses are listed in 7.5 Fuses
and Circuit Breakers. Ensure that proper fusing complies with local regulations.
e30ba026.11
3-phase
91 (L1)
power
92 (L2)
input
93 (L3)
95 PE
NOTICE
The motor cable must be shielded/armored. If an unshielded/unarmored cable is used, some EMC requirements are not complied
with. Use a shielded/armored motor cable to comply with EMC emission specifications. For more information, see chapter EMC-
compliant Installation.
Shielding of cables
Avoid installation with twisted shield ends (pigtails). They spoil the shielding effect at higher frequencies. If it is necessary to break the
shield to install a motor isolator or contactor, continue the shield at the lowest possible HF impedance.
Connect the motor cable shield to both the decoupling plate of the drive and the metal housing of the motor.
Make the shield connections with the largest possible surface area (cable clamp) by using the installation devices within the drive.
Switching frequency
When drives are used together with sine-wave filters to reduce the acoustic noise from a motor, the switching frequency must be set
according to the instructions in parameter 14-01 Switching Frequency.
Terminal 96 97 98 99 Description
U1 V1 W1 PE(1) Delta-connected.
NOTICE
In motors without phase insulation, paper, or other insulation reinforcement suitable for operation with voltage supply, use a sine-
wave filter on the output of the drive.
1
e75za114.11
U2 V2 W2 U2 V2 W2
U1 V1 W1 U1 V1 W1
96 97 98 96 97 98
e30bu003.10
PLC etc.
Drive
1
Ground Ground
PLC etc.
Drive
Ground Ground
PLC etc.
Drive
3
Ground Ground
Ground Ground
2
Minimum 16 mm
Equalizing cable
PLC etc.
Drive
Ground 4
100 nF Ground
Drive Drive
69 68
68 69
61 5
Ground
1 Control cables and serial communication cables must be 2 Do not use twisted cable ends (pigtails). They increase the
fitted with cable clamps at both ends to ensure the best shield impedance at high frequencies.
possible electrical contact.
3 If the ground potential between the drive and the PLC is 4 If long control cables are used, 50/60 Hz ground loops are
different, electric noise can occur that disturbs the entire possible. Connect 1 end of the shield to ground via a 100
system. Fit an equalizing cable next to the control cable. nF capacitor (keeping leads short).
2
Minimum cable cross-section: 16 mm (6 AWG).
Fieldbus connection
Connections are made to the relevant options on the control card. See the relevant fieldbus instruction. The cable must be tied down
and routed along with other control wires inside the unit.
e30bv185.10
COM RS 485
N RS 485
P RS 485
AO42
AO45
GND
10 V
AI53
AI54
50 53 54 42 45 55 61 68 69
COMMON
COMMON
DIO27
DIO29
VDD1
DI18
DI19
DI31
DI32
DI33
GND
NO
NO
NC
NC
RELAY 1 RELAY 2
12 18 19 27 29 31 32 33 20
01 02 03 04 05 06
27 Parameter 5-12 Terminal 27 Digital DI [2] Coast inverse Selectable for either digital input, dig-
Input DO [0] No operation ital output, or pulse output. Default
Parameter 5-30 Terminal 27 Digital setting is digital input.
Output Terminal 29 can be used for pulse in-
put.
29 Parameter 5-13 Terminal 29 Digital DI [14] Jog
Input DO [0] No operation
Parameter 5-31 Terminal 29 Digital
Output
32 Parameter 5-14 Terminal 32 Digital [0] No operation Digital input, 24 V encoder. Terminal
Input 33 can be used for pulse input.
Analog inputs/outputs
53 Parameter group 6-1* Analog Input 1 Reference Analog input. Selectable for voltage
or current.
54 Parameter group 6-2* Analog Input 2 Feedback
42 Parameter 6-91 Terminal 42 Analog [0] No operation Programmable analog output. The
Output analog signal is 0–20 mA or 4–20 mA
at a maximum of 500 Ω. Can also be
45 Parameter 6-71 Terminal 45 Analog [0] No operation
configured as digital outputs.
Output
Serial communication
Relays
01, 02, 03 Parameter 5-40 Function Relay [0] [0] No operation Form C relay output. For AC or DC
voltage and resistive or inductive
04, 05, 06 Parameter 5-40 Function Relay [1] [0] No operation
loads.
Model 380–480 V
H90K/Q110 ar-315
H110/Q132 ar-350
H132/Q160 ar-400
H160/Q200 ar-500
Model 380–480 V
H200/Q250 ar-630
H250/Q315 ar-800
Bussmann Rating
NOTICE
DISCONNECT SWITCH
All units ordered and supplied with a factory-installed disconnect switch require Class L branch circuit fusing to meet the 100 kA
SCCR for the drive. If a circuit breaker is used, the SCCR rating is 42 kA. The input voltage and power rating of the drive determine
the specific Class L fuse. The input voltage and power rating are found on the product nameplate.
7.6 Motor
7.6.1 Motor Rotation
Any 3-phase asynchronous standard motor can be used with a drive.
Table 13: Motor Cable Terminals Providing Clockwise Rotation (Factory Default)
Terminal Function
96 U/T1
97 V/T2
98 W/T3
99 Ground
The direction of rotation can be changed by switching 2 phases in the motor cable, or by changing the setting of parameter 4-10 Motor
Speed Direction.
e75ha036.11
1 U2 V2 W2
U1 V1 W1
2
96 97 98
1 U2 V2 W2
U1 V1 W1
96 97 98
l Run applications with parallel motors in U/F mode (volts per hertz).
l VVC+ mode can be used in some applications.
l Total current consumption of motors must not exceed the rated output current IINV for the drive.
l Problems can occur at start and at low RPM if motor sizes are widely different because the relatively high ohmic resistance in the
stator of a small motor demands a higher voltage at start and at low RPM.
l The electronic thermal relay (ETR) of the drive cannot be used as motor overload protection. Provide further motor overload
protection by including thermistors in each motor winding or individual thermal relays.
l Recommended to run applications with parallel motors in U/F mode parameter 1-01 Motor Control Principle[0] Asynchron. Set the
U/F graph in parameter 1-55 U/f Characteristic - U and parameter 1-56 U/f Characteristic - F.
e30bb838.12
a d
b f
c e
A Installations with cables connected in a common joint as shown in A and B are only recommended for short cable lengths.
B Be aware of the maximum motor cable length specified in the chapter Cable Lengths and Cross-sections.
C The total motor cable length specified in the chapter Cable Lengths and Cross-sections is valid as long as the parallel cables are
kept less than 10 m (32 ft) each.
F The total motor cable length specified in the chapter Cable Lengths and Cross-sections is valid as long as the parallel cables are
kept less than 10 m (32 ft) each.
7.7 Residual Current Devices (RCD) and Insulation Resistance Monitor (IRM)
Use RCD relays, multiple protective earthing, or grounding as extra protection, provided they comply with local safety regulations.
If a ground fault appears, a DC current can develop in the faulty current. If RCD relays are used, local regulations must be observed.
Relays must be suitable for protection of 3-phase equipment with a bridge rectifier and for a brief discharge on power-up. See chapter
Leakage Current for more details.
Drive technology implies high frequency switching at high power. This high frequency switching generates a leakage current in the
ground connection.
The ground leakage current is made up of several contributions and depends on various system configurations, including:
l RFI filtering.
l Motor cable length.
l Motor cable shielding.
l Drive power.
e30bb955.12
Leakage current
Figure 28: Motor Cable Length and Power Size Influence the Leakage Current. Power Size a > Power Size b.
e30bb956.12
Leakage current
THDv= 0%
THDv= 5%
If the leakage current exceeds 3.5 mA, compliance with EN/IEC61800-5-1 (power drive system product standard) requires special care.
Using RCDs
Where residual current devices (RCDs), also known as Ground Leakage Circuit Breakers, are used, comply with the following:
The leakage current includes several frequencies originating from both the mains frequency and the switching frequency. Whether the
switching frequency is detected depends on the type of RCD used.
e30bb958.12
Leakage current RCD with lowcut-off
f
The amount of leakage current detected by the RCD depends on the cut-off frequency of the RCD.
e30bb957.12
100 Hz
2 kHz
100 kHz
7.9 IT Mains
Mains supplies isolated from ground
If the drive is supplied from an isolated mains source (IT mains, floating delta, or grounded delta) or TT/TN-S mains with grounded leg,
the RFI switch is recommended to be turned off via parameter 14-50 RFI Filter on the drive and parameter 14-50 RFI Filter on the filter.
For more detail, see IEC 364-3. In the off position, the filter capacitors between the chassis and the DC link are cut off to avoid damage to
the DC link and to reduce the ground capacity currents, according to IEC 61800-3.
If optimum EMC performance is needed, or parallel motors are connected, or the motor cable length is above 25 m (82 ft), Danfoss
recommends setting parameter 14-50 RFI Filter to [1] ON. Refer also to the Application Note, VLT on IT mains. It is important to use
isolation monitors that are rated for use together with power electronics (IEC 61557-8).
7.10 Efficiency
Efficiency of the drive (ηVLT)
The load on the drive has little effect on its efficiency. In general, the efficiency is the same at the rated motor frequency fM, N, whether
the motor supplies 100% of the rated shaft torque or only 75%, if there is part loads.
The efficiency of the drive does not change even if other U/f characteristics are selected. However, the U/f characteristics influence the
efficiency of the motor.
The efficiency declines slightly when the switching frequency is set to a value of above 5 kHz. The efficiency is slightly reduced when the
mains voltage is 480 V, or if the motor cable is longer than 30 m (98 ft).
1.01
1.0
Relative Efficiency
0.99
0.98
0.97
0.96
0.95
0.94
0.93
0.92
0% 50% 100% 150% 200%
% Speed
100% load 75% load 50% load 25% load
Example: Assume a 160 kW, 380–480/500 V AC drive at 25% load at 50% speed. The above illustration shows 0.97 - rated efficiency for a
160 kW drive is 0.98. The actual efficiency is then: 0.97x0.98=0.95.
In the range of 75–100% of the rated torque, the efficiency of the motor is practically constant, both when the drive controls it and when
it runs directly on the mains.
In small motors, the influence from the U/f characteristic on efficiency is marginal. However, in motors from 11 kW (15 hp) and up, the
advantages are significant.
Typically the switching frequency does not affect the efficiency of small motors. Motors from 11 kW (15 hp) and up have their efficiency
improved (1–2%) because the shape of the motor current sine-wave is almost perfect at high switching frequency.
ηSYSTEM=ηVLT x ηMOTOR
The following table lists the typical acoustic noise values measured at a distance of 1 m (3.3 ft) from the unit.
J8 73
J9 75
Test results performed according to ISO 3744 for audible noise magnitude in a controlled environment. Noise tone has been quantified
for engineering data record of hardware performance per ISO 1996-2 Annex D.
NOTICE
To avoid the premature aging of motors that are not designed to be used with drives, such as those motors without phase
insulation paper or other insulation reinforcement, Danfoss strongly recommends a dU/dt filter or a sine-wave filter fitted on the
output of the drive. For further information about dU/dt and sine-wave filters, see the Output Filters Design Guide.
When a transistor in the inverter bridge switches, the voltage across the motor increases by a dU/dt ratio depending on the motor cable
(type, cross-section, length shielded or unshielded) and the inductance.
The natural induction causes an overshoot UPEAK in the motor voltage before it stabilizes itself at a level depending on the voltage in the
DC link. The rise time and the peak voltage UPEAK affect the service life of the motor. In particular, motors without phase coil insulation
are affected if the peak voltage is too high. Motor cable length affects the rise time and peak voltage. If the motor cable is short (a few
meters), the rise time and peak voltage are lower. If the motor cable is long (100 m (328 ft)), the rise time and peak voltage are higher.
Peak voltage on the motor terminals is caused by the switching of the IGBTs. The drive complies with the demands of IEC 60034-25:2007
edition 2.0 regarding motors designed to be controlled by drives. The drive also complies with IEC 60034-17:2006 edition 4 regarding
Norm motors controlled by drives.
High-power range
The power sizes in the following tables at the appropriate mains voltages comply with the requirements of IEC 60034-17:2006 edition 4
regarding normal motors controlled by drives, IEC 60034-25:2007 edition 2.0 regarding motors designed to be controlled by drives, and
NEMA MG 1-1998 Part [Link] for inverter-fed motors. The power sizes in the following tables do not comply with NEMA MG 1-1998 Part
[Link] for general purpose motors.
Table 16: IEC dU/dt Test Results for J8–J9 with Unshielded Cables and No Output Filter, 380–480 V
Power size [kW Cable [m (ft)] Mains voltage [V] Rise time [μs] Peak voltage [V] dU/dt [V/μs]
(hp)]
Table 17: IEC dU/dt Test Results for J8–J9 with Shielded Cables and No Output Filter, 380–480 V
Power size [kW Cable [m (ft)] Mains voltage [V] Rise time [μs] Peak voltage [V] dU/dt [V/μs]
(hp)]
Uncontrolled interaction between electrical devices in a system can degrade compatibility and impair reliable operation. Interference
takes the form of the following:
l Electrostatic discharges.
l Rapid voltage fluctuations.
l High-frequency interference.
Electrical interference is most commonly found at frequencies in the range 150 kHz to 30 MHz. Airborne interference from the drive
system in the range 30 MHz to 1 GHz is generated from the inverter, motor cable, and the motor.
Capacitive currents in the motor cable, coupled with a high dU/dt from the motor voltage, generate leakage currents. See the following
illustration. Shielded motor cables have higher capacitance between the phase wires and the shield, and again between the shield
and ground. This added cable capacitance, along with other parasitic capacitance and motor inductance, changes the electromagnetic
emission signature produced by the unit. The change in electromagnetic emission signature occurs mainly in emissions less than 5 MHz.
Most of the leakage current (I1) is carried back to the unit through the PE (I3), leaving only a small electromagnetic field (I4) from the
shielded motor cable. The shield reduces the radiated interference but increases the low-frequency interference on the mains.
e75za062.12
z L1 CS CS
U
I1
z L2 V
z L3 W
z PE PE I2 CS
1
I3
2
CS CS CS
I4 I4
3 4 5 6
Cs Possible shunt parasitic capacitance paths (varies with I1 Common-mode leakage current
different installations).
The drives comply with EMC requirements described in IEC/EN 61800-3, category C3, for equipment having greater than 100 A per-phase
current draw, installed in the 2nd environment. Compliance testing is performed with a 150 m (492 ft) shielded motor cable.
C1 EUT of rated input voltage less than 1000 V, intended for Class B
use in a residential, commercial, or light industrial loca-
tion.
C2 EUT of rated input voltage less than 1000 V, which is not a Class A Group 1
plug-in device or a movable device and not intended for
use in a residential location.
C3 EUT of rated input voltage less than 1000 V, intended for Class A Group 2
use in an industrial location and not intended for use in a
residential, commercial, or light industrial location.
The drives do not comply with generic emission standards. Extra methods, such as external filter, should be used for complying with
generic emission standards.
First environment (home and office) EN/IEC 61000-6-3 Emission standard for Class B
residential, commercial, and light indus-
trial environments.
Second environment (industrial environ- EN/IEC 61000-6-4 Emission standard for Class A group 1
ment) industrial environments.
To document immunity against burst transient, the following immunity tests have been performed on a drive (with options if relevant), a
shielded control cable, and a control box with potentiometer, motor cable, and motor. The tests were performed in accordance with the
following basic standards. For more details, see the following table.
l EN 61000-4-2 (IEC 61000-4-2): Electrostatic discharges (ESD): Simulation of electrostatic discharges from human beings.
l EN 61000-4-3 (IEC 61000-4-3): Incoming electromagnetic field radiation, amplitude modulated simulation of the effects of radar,
radio communication equipment, and mobile communications equipment.
l EN 61000-4-4 (IEC 61000-4-4): Burst transients: Simulation of interference brought about by switching a contactor, relay, or similar
devices.
l EN 61000-4-5 (IEC 61000-4-5): Surge transients: Simulation of transients brought about by lightning strikes near installations.
l EN 61000-4-6 (IEC 61000-4-6): RF common-mode: Simulation of the effect from radio-transmission equipment joined by connection
cables.
Basic standard Burst IEC Surge IEC ESD IEC 61000-4-2 Radiated RF common-
61000-4-4 61000-4-5 electromagnetic mode voltage IEC
field IEC 61000-4-3 61000-4-6
Acceptance crite- B B B A A
rion
Enclosure – – 8 kV AD 10 V/m –
4 kV CD
AD: air discharge; CD: contact discharge; CM: common-mode; DM: differential mode.
NOTICE
OPERATOR RESPONSIBILITY
According to the EN 61800–3 standard for variable-speed drive systems, the operator is responsible for ensuring EMC compliance.
Manufacturers can offer solutions for operation conforming to the standard. Operators are responsible for applying these
solutions, and for paying the associated costs.
RFI filters
The goal is to obtain systems that operate stably without radio frequency interference between components. To achieve a high level of
immunity, use drives with high-quality RFI filters.
NOTICE
RADIO INTERFERENCE
In a residential environment, this product can cause radio interference, in which case supplementary mitigation measures may be
required.
All drives control and relay terminals comply with PELV (excluding grounded Delta leg above 400 V).
Galvanic (ensured) isolation is obtained by fulfilling requirements for higher isolation and by providing the relevant creepage/clearance
distances. These requirements are described in the EN 61800–5–1 standard.
Electrical isolation is provided as shown (see the following illustration). The components described comply with both PELV and the
galvanic isolation requirements.
e30bx514.10
7 6 4 3
8
5 2
1 Current transducers 2 Galvanic isolation for the RS485 standard bus interface
3 Gate drive for the IGBTs 4 Supply (SMPS) including signal isolation of V DC, indicating
the intermediate current voltage
5 Galvanic isolation for the 24 V backup option 6 Opto-coupler, brake module (optional)
NOTICE
TWISTED SHIELD ENDS (PIGTAILS)
Twisted shield ends increase the shield impedance at higher frequencies, which reduces the shield effect and increases the
leakage current. Avoid twisted shield ends by using integrated shield clamps.
l For use with relays, control cables, a signal interface, fieldbus, or brake, connect the shield to the enclosure at both ends. If the
ground path has high impedance, is noisy, or is carrying current, break the shield connection on 1 end to avoid ground current
loops.
l Convey the currents back to the unit using a metal mounting plate. Ensure good electrical contact from the mounting plate through
the mounting screws to the drive chassis.
l Use shielded cables for motor output cables. An alternative is unshielded motor cables within metal conduit.
NOTICE
SHIELDED CABLES
If shielded cables or metal conduits are not used, the unit and the installation do not meet regulatory limits on radio frequency
(RF) emission levels.
l Ensure that motor and brake cables are as short as possible to reduce the interference level from the entire system.
l Avoid placing cables with a sensitive signal level alongside motor and brake cables.
l For communication and command/control lines, follow the particular communication protocol standards. For example, USB must
use shielded cables, but RS485/ethernet can use shielded UTP or unshielded UTP cables.
l Ensure that all control terminal connections are PELV.
NOTICE
EMC INTERFERENCE
Use shielded cables for motor and control wiring. Make sure to separate mains input, motor, and control cables from one another.
Failure to isolate these cables can result in unintended behavior or reduced performance. Minimum 200 mm (7.9 in) clearance
between mains input, motor, and control cables are required.
NOTICE
INSTALLATION AT HIGH ALTITUDE
There is a risk of overvoltage. Isolation between components and critical parts could be insufficient and not comply with PELV
requirements. Reduce the risk of overvoltage by using external protective devices or galvanic isolation.
l For installations above 2000 m (6500 ft) altitude, contact Danfoss regarding PELV compliance.
NOTICE
PELV COMPLIANCE
Prevent electric shock by using protective extra low voltage (PELV) electrical supply and complying with local and national PELV
regulations.
e30bf228.11
6
RELA
7
9L11 A INS
M
Y 1Y 2
9L22
RELA
10
9L33 8
+ BDBR
99 UMVTCO- R
W 9
-C
L-
11
1 12
90
13
2 14
3
15
u
4
v 16
4
w
4 PE
L1 17
L2
L3
PE
5 L1
L2
L3
PE 18
IEC 60309
3 Control cables 4 Minimum 200 mm (7.9 in) between control cables, motor
cables, and mains cables.
7.14 Harmonics
7.14.1 Harmonics Overview
Non-linear loads such as those found with drives do not draw current uniformly from the power line. This non-sinusoidal current has
components which are multiples of the basic current frequency. These components are referred to as harmonics. It is important to
control the total harmonic distortion on the mains supply. Although the harmonic currents do not directly affect electrical energy
consumption, they generate heat in wiring and transformers that can affect other devices on the same power line.
A non-sinusoidal current is transformed with a Fourier series analysis into sine-wave currents at different frequencies, that is, different
harmonic currents IN with 50 Hz or 60 Hz as the basic frequency.
Abbreviation Description
n Harmonic order.
Current I1 I5 I7 I11
IRMS I1 I5 I7 I11-49
The voltage distortion on the mains supply voltage depends on the size of the harmonic currents multiplied by the mains impedance for
the frequency in question. The total voltage distortion (THDi) is calculated based on the individual voltage harmonics using this formula:
e30bb540.10
PCC1
MV
LV
Z xfr
PCC2
Z 1 Z 2 Z 3
Harmonic currents drawn by non-linear loads cause distortion of the voltage because of the voltage drop on the impedances of the
distribution system. Higher impedances result in higher levels of voltage distortion.
Current distortion relates to apparatus performance and it relates to the individual load. Voltage distortion relates to system
performance. It is not possible to determine the voltage distortion in the PCC knowing only the harmonic performance of the load. To
predict the distortion in the PCC, the configuration of the distribution system and relevant impedances must be known.
A commonly used term for describing the impedance of a grid is the short circuit ratio Rsce, where Rsce is defined as the ratio between the
short circuit apparent power of the supply at the PCC (Ssc) and the rated apparent power of the load.
where and .
l Harmonic voltage distortion causes disturbance to other loads and increases losses in other loads.
Standard Definition
EN 61000-2-2, EN 61000-2-4, EN 50160 Define the mains voltage limits required for public and industrial
power grids.
There are 2 European standards that address harmonics in the frequency range from 0 Hz to 9 kHz:
EN 61000–2–2 (Compatibility Levels for Low-Frequency Conducted Disturbances and Signaling in Public Low-Voltage Power Supply
Systems
The EN 61000–2–2 standard states the requirements for compatibility levels for PCC (point of common coupling) of low-voltage AC
systems on a public supply network. Limits are specified only for harmonic voltage and total harmonic distortion of the voltage. EN
61000–2–2 does not define limits for harmonic currents. In situations where the total harmonic distortion THD(V)=8%, PCC limits are
identical to those limits specified in the EN 61000–2–4 Class 2.
EN 61000–2–4 (Compatibility Levels for Low-Frequency Conducted Disturbances and Signaling in Industrial Plants)
The EN 61000–2–4 standard states the requirements for compatibility levels in industrial and private networks. The standard further
defines the following 3 classes of electromagnetic environments:
l Class 1 relates to compatibility levels that are less than the public supply network, which affects equipment sensitive to disturbances
(lab equipment, some automation equipment, and certain protection devices).
l Class 2 relates to compatibility levels that are equal to the public supply network. The class applies to PCCs on the public supply
network and to IPCs (internal points of coupling) on industrial or other private supply networks. Any equipment designed for
operation on a public supply network is allowed in this class.
l Class 3 relates to compatibility levels greater than the public supply network. This class applies only to IPCs in industrial
environments. Use this class where the following equipment is found:
¢ Large drives.
¢ Welding machines.
¢ Large motors starting frequently.
¢ Loads that change quickly.
Typically, a class cannot be defined ahead of time without considering the intended equipment and processes to be used in the
environment. Drives observe the limits of Class 3 under typical supply system conditions (RSC>10 or Vk Line<10%).
5 3 6 8
7 3 5 7
11 3 3.5 5
13 3 3 4.5
17 2 2 4
17�h≤49 2.27 x (17/h) – 0.27 2.27 x (17/h) – 0.27 4.5 x (17/h) – 0.5
Table 27: Compatibility Levels for the Total Harmonic Voltage Distortion THDv
THDv 5% 8% 10%
l IEC61000-2-4.
l IEC61000-3-4.
l G5/4.
In its basic form, the drive can be divided into the following 4 main areas:
Rectifier
The rectifier consists of SCRs or diodes that convert 3-phase AC voltage to pulsating DC voltage.
Inverter
The inverter uses IGBTs to convert the DC voltage to variable voltage and variable frequency AC.
Control
The control area consists of software that runs the hardware to produce the variable voltage that controls and regulates the AC motor.
e30bf777.11
1 2 3
L1 U
L2 V
L3 W
l Reference handling.
l Feedback handling.
l User-defined control structure.
¢ Open-loop/closed-loop mode.
The local reference is active when the drive is operated with [Hand On] active. Adjust the reference via the Up key, Down key, Right key
and the [Back] key.
Remote reference
The reference handling system for calculating the remote reference is shown in the Figure 38.
The remote reference is calculated once in every scan interval and initially consists of 2 types of reference inputs:
1. X (the external reference): A sum (see parameter 3-04 Reference Function) of up to 4 externally selected references, comprising any
combination (determined by the setting in parameter 3-15 Reference 1 Source, parameter 3-16 Reference 2 Source, and parameter
3-17 Reference 3 Source) of a fixed preset reference (parameter 3-10 Preset Reference), variable analog references, variable digital
pulse references, and various fieldbus references in any unit the drive is monitoring ([Hz], [RPM], [Nm], and so on).
2. Y (the relative reference): A sum of 1 fixed preset reference (parameter 3-14 Preset Relative Reference) and 1 variable analog
reference (parameter 3-18 Relative Scaling Reference Resource) in [%].
Remote reference=X+X*Y/100%.
If relative reference is not used, set parameter 3-18 Relative Scaling Reference Resource to [0] No function and parameter 3-14 Preset
Relative Reference to 0%. The digital inputs on the drive can activate both the catch up/slow down function and the freeze reference
function. The functions and parameters are described in the programming guide.
The scaling of analog references is described in parameter group 6-1* Analog Input 53 and parameter group 6-2* Analog Input 54, and
the scaling of digital pulse references is described in parameter group 5-5* Pulse Input.
Reference limits and ranges are set in parameter group 3-0* Reference Limits.
e30ba184.10
P 3-00 Reference Range = [0] Min-Max
Resulting reference
P 3-03
Forward
P 3-02
Sum of all
references
-P 3-02
Reverse
-P 3-03
e30ba185.10
P 3-03 Reference Range = [1] -Max-Max
Resulting reference
P 3-03
Sum of all
references
-P 3-03
The value of parameter 3-02 Minimum Reference cannot be set to less than 0, unless parameter 1-00 Configuration Mode is set to [3]
Process. In that case, the following relations between the resulting reference (after clamping) and the sum of all references are as shown
in Figure 41.
e30ba186.11
Resulting reference
P 3-03
Sum of all
P 3-02 references
Figure 41: Sum of All References When Minimum Range is Set to a Minus Value
l When parameter 3-00 Reference Range is set to [0] Min–Max, 0% reference equals 0 [unit] where unit can be any unit, for example
RPM, m/s, and bar. 100% reference equals the maximum (absolute value of parameter 3-03 Maximum Reference, absolute value of
parameter 3-02 Minimum Reference).
l When parameter 3-00 Reference Range is set to [1] -Max–+Max, 0% reference equals 0 [unit], and 100% reference equals maximum
reference.
l When parameter 3-00 Reference Range is set to [0] Min–Max, 0% reference equals minimum reference, and 100% reference equals
maximum reference.
l When parameter 3-00 Reference Range is set to [1] -Max–+Max, -100% reference equals -maximum reference, and 100% reference
equals maximum reference.
e30bd431.10
Resource output
[Hz]
High reference/
feedback value50 P2
Low reference/ P1
feedback value
Resource input
[V]
0 1 8 10
Terminal X
high
The endpoints P1 and P2 are defined in the following table depending on choice of input.
Minimum refer- Parameter 6-14 Parameter 6-14 Parameter 6-24 Parameter 6-24 Parameter 5-52 Parameter 5-57
ence value Terminal 53 Terminal 53 Terminal 54 Terminal 54 Term. 29 Low Terminal 33
Low Ref./Feedb. Low Ref./Feedb. Low Ref./Feedb. Low Ref./Feedb. Ref./Feedb. Low Ref./Feedb.
Value Value Value Value Value Value
Minimum input Parameter 6-10 Parameter 6-12 Parameter 6-20 Parameter 6-22 Parameter 5-50 Parameter 5-55
value Terminal 53 Low Terminal 53 Low Terminal 54 Low Terminal 54 Low Terminal 29 Low Terminal 33 Low
Voltage [V] Current [mA] Voltage [V] Current [mA] Frequency [Hz] Frequency [Hz]
Maximum refer- Parameter 6-15 Parameter 6-15 Parameter 6-25 Parameter 6-25 Parameter 5-53 Parameter 5-58
ence value Terminal 53 Terminal 53 Terminal 54 Terminal 54 Term. 29 High Terminal 33
High Ref./Feedb. High Ref./Feedb. High Ref./Feedb. High Ref./Feedb. Ref./Feedb. High Ref./Feedb.
Value Value Value Value Value Value
Maximum input Parameter 6-11 Parameter 6-13 Parameter 6-21 Parameter 6-23 Parameter 5-51 Parameter 5-56
value Terminal 53 Terminal 53 Terminal 54 Terminal 54 Terminal 29 Terminal 33
High Voltage [V] High Current High Voltage [V] High Current High Frequency High Frequency
[mA] [mA] [Hz] [Hz]
To make the dead band active and to set the amount of dead band, do the following:
l Set either the minimum reference value or maximum reference value at 0. In other words, either P1 or P2 must be on the X-axis in
Figure 43.
l Ensure that both points defining the scaling graph are in the same quadrant.
Case 1: Positive reference with dead band, digital input to trigger reverse, part I
Figure 44 shows how reference input with limits inside minimum to maximum limits clamps.
Figure 44: Clamping of Reference Input with Limits inside Minimum to Maximum
Case 2: Positive reference with dead band, digital input to trigger reverse, part II
Figure 45 shows how reference input with limits outside -maximum to +maximum limits clamps to the input low and high limits before
adding to external reference, and how the external reference is clamped to -maximum to +maximum by the reference algorithm.
Figure 45: Clamping of Reference Input with Limits outside -Maximum to +Maximum
The motor is supplied with variable voltage/current and frequency, enabling variable speed control of 3-phased standard AC motors and
permanent magnet synchronous motors.
Speed control
l Speed open-loop control, which does not require any feedback from the motor (sensorless).
l Speed closed-loop PID control, which requires a speed feedback to an input. A properly optimized speed closed-loop control has
higher accuracy than a speed open-loop control.
Select which input to use as speed PID feedback in parameter 7-00 Speed PID Feedback Source.
Torque control
The torque control function is used in applications where the torque on the motor output shaft is controlling the application as tension
control. Torque control can be either in VVV+ torque open loop in flux sensorless or in flux control closed loop. The best performance
is with flux closed loop, especially near 0 speed. Torque control can be selected in parameter 1-00 Configuration Mode. Torque setting
is done by setting an analog, digital, or bus controlled reference. When running torque control, it is recommended to run a full AMA
procedure, because correct motor data is important in achieving optimal performance.
l Closed loop in VVC+ mode. This function is used in applications with low to medium dynamic variation of shaft, and offers excellent
performance in all 4 quadrants and at all motor speeds. The speed feedback signal is mandatory. It is recommended to use MCB102
option card. Ensure that the encoder resolution is at least 1024 PPR, and the shield cable of the encoder is well grounded, because
the accuracy of the speed feedback signal is important. Tune parameter 7-06 Speed PID Lowpass Filter Time to get the best speed
feedback signal.
l Open loop in VVC+ mode. The function is used in mechanically robust applications, but the accuracy is limited. The open-loop
torque function works for 2 directions. The torque is calculated based on the internal current measurement in the drive.
Speed/torque reference
The reference to these controls can be either a single reference or the sum of various references including relatively scaled references.
Handling of reference is explained in detail in the chapter Reference Handling.
e3 0 bd3 7 1 .1 0
P 4 -1 9
Max. output freq.
P 1 -0 0 P 1 -0 0
P 4 -1 4
Config. mode Config. mode
Motor speed + f max.
high limit (Hz)
P 3 -** Motor
High
controller
Ref.
Ramp -f max.
Low
+ P 4 -1 2
P 4 -1 9
S Process Motor speed
Max. output freq.
_ low limit (Hz)
P 7 -0 * + f max.
Figure 46: Control Structure in VVC+ Open-loop Configurations and Closed-loop Configurations
In the configuration shown in Figure 46, parameter 1-01 Motor Control Principle is set to [1] VVC+ and parameter 1-00 Configuration
Mode is set to [0] Speed open loop. The resulting reference from the reference handling system is received and fed through the ramp
limitation and speed limitation before being sent to the motor control. The output of the motor control is then limited by the maximum
frequency limit.
If parameter 1-00 Configuration Mode is set to [1] Speed closed loop, the resulting reference is passed from the ramp limitation and
speed limitation into a Speed PID control. The Speed PID control parameters are in parameter group 7-0* Speed PID Ctrl. The resulting
reference from the Speed PID control is sent to the motor control limited by the frequency limit.
Select [3] Process in parameter 1-00 Configuration Mode to use the process PID control for closed-loop control of speed or pressure in
the controlled application. The process PID parameters are in parameter groups 7-2* Process Ctrl. Feedb and parameter groups 7-3*
Process PID Ctrl.
e30bv187.10
P 1-00
Config. mode
P 4-19
P 4-14 Motor speed Max. output
high limit [Hz] freq.
High P 3-** P 7-0* + f max.
Ref. +
Ramp S Speed Motor
PID controller
_
Low -f max.
+
Process P 4-12 Motor speed
S
PID low limit [Hz]
_
In the configuration shown, parameter 1-01 Motor Control Principle is set to [2] Flux Sensorless and parameter 1-00 Configuration Mode
is set to [0] Speed open loop. The resulting reference from the reference handling system is fed through the ramp and speed limitations
as determined by the parameter settings indicated.
An estimated speed feedback is generated to the speed PID to control the output frequency.
The speed PID must be set with its P, I, and D parameters (parameter group 7-0* Controllers).
Select [3] Process in parameter 1-00 Configuration Mode to use the process PID control for closed-loop control of speed or pressure
in the controlled application. The process PID parameters are in parameter group 7-2* Process Ctrl. Feedb and parameter group 7-3*
Process PID Ctrl.
e30bv188.10
P 1-00 P 1-00
Config. mode Config. mode
Torque
P 4-19
P 4-14 Motor speed Max. output
high limit (Hz) freq.
Low -f max.
P 4-12 Motor speed P 7-00
P 7-20 Process feedback
low limit (Hz) PID source
1 source
P 7-22 Process feedback
2 source
In the configuration shown, parameter 1-01 Motor Control Principle is set to [3] Flux w/ motor feedb and parameter 1-00 Configuration
Mode is set to [1] Speed closed loop.
Select [1] Speed closed loop in parameter 1-00 Configuration Mode to use the resulting reference as an input for the Speed PID control.
The Speed PID control parameters are in parameter group 7-0* Speed PID Ctrl.
Select [2] Torque in parameter 1-00 Configuration Mode to use the resulting reference directly as a torque reference. Torque control
can only be selected in the flux with motor feedback (parameter 1-01 Motor Control Principle) configuration. When this mode has been
selected, the reference uses the Nm unit. It requires no torque feedback, since the actual torque is calculated based on the current
measurement of the drive.
Select [3] Process in parameter 1-00 Configuration Mode to use the process PID control for closed-loop control of a process variable (for
example, speed) in the controlled application.
e75za145.12
R+ R+
Master 1 2 3 31 Repeater
R+ R+
Repeater 1 2 3 30
R+ R+
1 2 3 30
Repeater
R+ R+
1 2 3 30 31
NOTICE
Each repeater functions as a node within the segment in which it is installed. Each node connected within a given network must
have a unique node address across all segments.
Terminate each segment at both ends, using either the termination switch (S801) of the drives or a biased termination resistor network.
Always use shielded twisted pair (STP) cable for bus cabling and follow good common installation practice.
Low-impedance ground connection of the shield at every node is important, including at high frequencies. Thus, connect a large surface
of the shield to ground, for example with a cable clamp or a conductive cable gland. Sometimes, it is necessary to apply potential-
equalizing cables to maintain the same ground potential throughout the network, particularly in installations with long cables.
To prevent impedance mismatch, use the same type of cable throughout the entire network. When connecting a motor to the drive,
always use shielded motor cable.
1. Connect signal wires to terminal 68 (P+) and terminal 69 (N-) on the main control board of the drive.
2. Connect the cable shield to the cable clamps.
NOTICE
To reduce noise between conductors, use shielded, twisted-pair cables.
e30bb795.10
61 68 69
COMM. GND
P
N
Parameter Function
Parameter 8-30 Protocol Select the application protocol to run for the RS485 interface.
NOTICE
The address range depends on the protocol selected in
parameter 8-30 Protocol.
NOTICE
The default baud rate depends on the protocol selected in
parameter 8-30 Protocol.
Parameter Function
Parameter 8-33 Parity/Stop Bits Set the parity and number of stop bits.
NOTICE
The default selection depends on the protocol selected in
parameter 8-30 Protocol.
Parameter 8-35 Minimum Response Delay Specify a minimum delay time between receiving a request and
transmitting a response. This function is for overcoming modem
turnaround delays.
Parameter 8-36 Maximum Response Delay Specify a maximum delay time between transmitting a request
and receiving a response.
Parameter 8-37 Maximum Inter-char delay If transmission is interrupted, specify a maximum delay time be-
tween 2 received bytes to ensure timeout.
NOTICE
The default selection depends on the protocol selected in
parameter 8-30 Protocol.
NOTICE
Observe relevant national and local regulations, for example, regarding protective ground connection. To avoid coupling of high
frequency noise between the cables, keep the RS485 communication cable away from motor and brake resistor cables. Normally,
a distance of 200 mm (8 in) is sufficient. Maintain the greatest possible distance between the cables, especially where cables run in
parallel over long distances. When crossing is unavoidable, the RS485 cable must cross motor and brake resistor cables at an angle
of 90°.
9.2 FC Protocol
9.2.1 Overview
The FC protocol, also referred to as FC bus or standard bus, is the Danfoss standard fieldbus. It defines an access technique according to
the master/follower principle for communications via a fieldbus.
One master and a maximum of 126 followers can be connected to the bus. The master selects the individual followers via an address
character in the telegram. A follower itself can never transmit without first being requested to do so, and direct telegram transfer
between the individual followers is not possible. Communications occur in the half duplex mode.
The physical layer is RS485, thus utilizing the RS485 port built into the drive. The FC protocol supports different telegram formats:
The control word allows the Modbus master to control several important functions of the drive:
l Start.
l Stop of the drive in various ways:
¢ Coast stop.
¢ Quick stop.
¢ DC brake stop.
¢ Normal (ramp) stop.
l Reset after a fault trip.
l Run at various preset speeds.
l Run in reverse.
l Change of the active setup.
l Control of the 2 relays built into the drive.
The bus reference is commonly used for speed control. It is also possible to access the parameters, read their values, and where possible,
write values to them. Accessing the parameters offers a range of control options, including controlling the setpoint of the drive when its
internal PI controller is used.
Parameter Setting
e95na099.10
STX LGE ADR DATA BCC
1) 10 represents the fixed characters, while n is variable (depending on the length of the text).
The follower returns the address byte unchanged to the master in the response telegram.
e30ba269.10
STX LGE ADR PCD1 PCD2 BCC
Parameter block
The parameter block is used to transfer parameters between master and follower. The data block is made up of 12 bytes (6 words) and
also contains the process block.
e30ba271.10
STX LGE ADR PKE IND PWEhigh PWElow PCD1 PCD2 BCC
Text block
The text block is used to read or write texts via the data block.
e30ba270.10
STX LGE ADR PKE IND Ch1 Ch2 Chn PCD1 PCD2 BCC
Bits 12–15 transfer parameter commands from master to follower and return processed follower responses to the master.
15 14 13 12
0 0 0 0 No command.
1 1 1 1 Read text.
15 14 13 12
0 0 0 0 No command.
0 1 1 1 Command cannot be
performed.
1 1 1 1 Text transferred.
If the command cannot be performed, the follower sends 0111 Command cannot be performed response and issues the following fault
reports in the table.
3 Sub-index is corrupted.
4 No array.
6 Not used.
7 Not used.
15 No text available.
18 Other errors.
100 –
>100 –
255 No error.
When a follower responds to a parameter request (read command), the present parameter value in the PWE block is transferred and
returned to the master. If a parameter contains several data options, for example, parameter 0-01 Language, select the data value by
entering the value in the PWE block. Serial communication is only capable of reading parameters containing data type 9 (text string).
Parameter 15-40 FC Type to parameter 15-53 Power Card Serial Number contain data type 9. For example, read the unit size and mains
voltage range in parameter 15-40 FC Type. When a text string is transferred (read), the length of the telegram is variable, and the texts
are of different lengths. The telegram length is defined in the 2nd byte of the telegram (LGE). When using text transfer, the index
character indicates whether it is a read, or a write command.
To read a text via the PWE block, set the parameter command (AK) to F hex. The index character high-byte must be 4.
3 Integer 16
4 Integer 32
5 Unsigned 8
6 Unsigned 16
7 Unsigned 32
9 Text string
9.4.12 Conversion
The programming guide contains the descriptions of attributes of each parameter. Parameter values are transferred as whole numbers
only. Conversion factors are used to transfer decimals.
Parameter 4-12 Motor Speed Low Limit [Hz] has a conversion factor of 0.1. To preset the minimum frequency to 10 Hz, transfer the value
100. A conversion factor of 0.1 means that the value transferred is multiplied by 0.1. The value 100 is thus perceived as 10.0.
74 3600
2 100
1 10
0 1
-1 0.1
-2 0.01
-3 0.001
-4 0.0001
-5 0.00001
PCD 1 PCD 2
9.5 Examples
9.5.1 Writing a Parameter Value
Change parameter 4-14 Motor Speed High Limit [Hz] to 100 Hz.
PKE = E19E hex - Write single word in parameter 4-14 Motor Speed High Limit [Hz]:
Data value 1000, corresponding to 100 Hz, see the chapter 9.4.12 Conversion.
NOTICE
Parameter 4-14 Motor Speed High Limit [Hz] is a single word, and the parameter command for write in EEPROM is E. Parameter
4-14 Motor Speed High Limit [Hz] is 19E in hexadecimal.
The response from the follower to the master is shown in the Figure 58.
e30ba093.10
PKE = 1155 hex - Read parameter value in parameter 3-41 Ramp 1 Ramp Up Time:
e30ba094.10
1155 H 0000 H 0000 H 0000 H
If the value in parameter 3-41 Ramp 1 Ramp Up Time is 10 s, the response from the follower to the master is shown in .
e30ba267.10
1155 H 0000 H 0000 H 03E8 H
3E8 hex corresponds to 1000 decimal. The conversion index for parameter 3-41 Ramp 1 Ramp Up Time is -2, that is, 0.01.
The built-in Modbus RTU (remote terminal unit) is designed to communicate with any controller that supports the interfaces defined in
this manual. It is assumed that the user has full knowledge of the capabilities and limitations of the controller.
9.6.2 Overview
Regardless of the type of physical communication networks, this section describes the process that a controller uses to request access to
another device. This process includes how the Modbus RTU responds to requests from another device, and how errors are detected and
reported. It also establishes a common format for the layout and contents of telegram fields.
If a reply is required, the controller constructs the reply telegram and sends it.
Controllers communicate using a master/follower technique in which only the master can initiate transactions (called queries). Followers
respond by supplying the requested data to the master, or by acting as requested in the query. The master can address individual
followers, or initiate a broadcast telegram to all followers. Followers return a response to queries that are addressed to them individually.
No responses are returned to broadcast queries from the master.
The Modbus RTU protocol establishes the format for the master query by providing the following information:
The response telegram of the follower device is also constructed using Modbus protocol. It contains fields confirming the action taken,
any data to be returned, and an error-checking field. If an error occurs in receipt of the telegram, or if the follower is unable to perform
the requested action, the follower constructs and sends an error message. Alternatively, a timeout occurs.
The control word allows the Modbus master to control several important functions of the drive:
l Start.
l Various stops:
¢ Coast stop.
¢ Quick stop.
¢ DC brake stop.
¢ Normal (ramp) stop.
l Reset after a fault trip.
l Run at various preset speeds.
l Run in reverse.
l Change the active setup.
l Control built-in relay of the drive.
The bus reference is commonly used for speed control. It is also possible to access the parameters, read their values, and, where possible,
write values to them. Accessing the parameters offers a range of control options, including controlling the setpoint of the drive when its
internal PI controller is used.
Parameter Setting
Transmit the entire telegram frame as a continuous stream. If a silent period of more than 1.5 character intervals occurs before
completion of the frame, the receiving device flushes the incomplete telegram and assumes that the next byte is the address field of a
new telegram. Similarly, if a new telegram begins before 3.5 character intervals after a previous telegram, the receiving device considers
it a continuation of the previous telegram. This behavior causes a timeout (no response from the follower), since the value in the final
CRC field is not valid for the combined telegrams.
For a normal response, the follower simply echoes the original function code. For an exception response, the follower returns a code that
is equivalent to the original function code with its most significant bit set to logic 1. In addition, the follower places a unique code into
the data field of the response telegram. This code tells the master what kind of error occurred, or the reason for the exception. Also refer
to chapter Function Codes Supported by Modbus RTU and chapter Modbus Exception Codes.
Holding register 40001 is addressed as register 0000 in the data address field of the telegram. The function code field already specifies
a holding register operation. Therefore, the 4XXXX reference is implicit. Holding register 40108 is addressed as register 006Bhex (107
decimal).
17–32 Drive speed or setpoint reference range 0x0–0xFFFF (-200% ... Master to follower
~200%).
66–65536 Reserved. –
Coil 0 1
03 DC brake No DC brake
08 No reset Reset
09 No jog Jog
10 Ramp 1 Ramp 2
14 Set up lsb
15 –
16 No reversing Reversing
Coil 0 1
36 No alarm Alarm
40 No warning Warning
44 Stopped Running
3 4 40004 Free – –
4 5 40005 Free – –
5 6 40006 Modbus config- Read/Write TCP only. Reserved for Modbus TCP
uration (parameter 12-28 Store Data Values
and parameter 12-29 Store Always -
stored in, for example, EEPROM).
6 7 40007 Last fault code Read only Fault code received from parameter
database, refer to WHAT 38295 for
details.
7 8 40008 Last error regis- Read only Address of register with which last
ter error occurred, refer to WHAT 38296
for details.
1) Value written in the Modbus RTU telegram must be 1 or less than the register number. For example, Read Modbus Register 1 by writing value 0 in the telegram.
Read coils 1
Diagnostics 8
Report follower ID 11
1 Illegal func- The function code received in the query is not an allowable action for the server (or follower). This
tion may be because the function code is only applicable to newer devices and was not implemented in
the unit selected. It could also indicate that the server (or follower) is in the wrong state to process
a request of this type, for example because it is not configured and is being asked to return register
values.
2 Illegal data The data address received in the query is not an allowable address for the server (or follower). More
address specifically, the combination of reference number and transfer length is invalid. For a controller
with 100 registers, a request with offset 96 and length 4 succeeds, while a request with offset 96
and length 5 generates exception 02.
3 Illegal data A value contained in the query data field is not an allowable value for server (or follower). This indi-
value cates a fault in the structure of the remainder of a complex request, such as that the implied length
is incorrect. It does NOT mean that a data item submitted for storage in a register has a value out-
side the expectation of the application program, since the Modbus protocol is unaware of the sig-
nificance of any value of any register.
4 Follower de- An unrecoverable error occurred while the server (or follower) was attempting to perform the re-
vice failure quested action.
Reading parameter 3-14 Preset Relative Reference (32 bit): The holding registers 3410 and 3411 hold the parameters’ values. A value of
11300 (decimal) means that the parameter is set to 1113.00.
For information on the parameters, size, and conversion index, see the programming guide.
Standard data types are int 16, int 32, uint 8, uint 16, and uint 32. They are stored as 4x registers (40001–4FFFF). The parameters are read
using function 03 hex read holding registers. Parameters are written using the function 6 hex preset single register for 1 register (16 bits),
and the function 10 hex preset multiple registers for 2 registers (32 bits). Readable sizes range from 1 register (16 bits) up to 10 registers
(20 characters).
Non-standard data types are text strings and are stored as 4x registers (40001–4FFFF). The parameters are read using function 03 hex
read holding registers and written using function 10 hex preset multiple registers. Readable sizes range from 1 register (2 characters) up
to 10 registers (20 characters).
9.10 Examples
9.10.1 Overview of the Examples
The examples in the following chapters show various Modbus RTU commands.
This function reads the ON/OFF status of discrete outputs (coils) in the drive. Broadcast is never supported for reads.
Query
The query telegram specifies the starting coil and quantity of coils to be read. Coil addresses start at 0, that is, coil 33 is addressed as 32.
Example of a request to read coils 33–48 (status word) from follower device 01.
Starting address HI 00
Number of points HI 00
Response
The coil status in the response telegram is packed as 1 coil per bit of the data field. Status is indicated as: 1 = ON; 0 = OFF. The lsb of the
1st data byte contains the coil addressed in the query. The other coils follow toward the high-order end of this byte, and from low order
to high order in subsequent bytes.
If the returned coil quantity is not a multiple of 8, the remaining bits in the final data byte are padded with values 0 (toward the high-
order end of the byte). The byte count field specifies the number of complete bytes of data.
NOTICE
Coils and registers are addressed explicitly with an offset of -1 in Modbus. For example, coil 33 is addressed as coil 32.
This function forces the coil to either ON or OFF. When broadcast, the function forces the same coil references in all attached followers.
Query
The query telegram specifies the coil 65 (parameter write control) to be forced. Coil addresses start at 0, that is, coil 65 is addressed as 64.
Force data = 00 00 hex (OFF) or FF 00 hex (ON).
Coil address HI 00
Force data HI FF
Response
The normal response is an echo of the query, returned after the coil state has been forced.
Follower address 01
Function 05
Force data HI FF
Force data LO 00
Quantity of coils HI 00
Quantity of coils LO 01
This function forces each coil in a sequence of coils to either on or off. When broadcasting, the function forces the same coil references in
all attached followers.
Query
The query telegram specifies the coils 17–32 (speed setpoint) to be forced.
NOTICE
Coil addresses start at 0, that is, coil 17 is addressed as 16.
Coil address HI 00
Quantity of coils HI 00
Byte count 02
Force data HI 20
(Coils 8–1)
Response
The normal response returns the follower address, function code, starting address, and quantity of coils forced.
Coil address HI 00
Quantity of coils HI 00
Query
The query telegram specifies the starting register and quantity of registers to be read. Register addresses start at 0, that is, registers 1–4
are addressed as 0–3.
Follower address 01
Number of points HI 00
Number of points LO 02 – (parameter 3-03 Maximum Reference is 32 bits long, that is,
2 registers)
Response
The register data in the response telegram is packed as 2 bytes per register, with the binary contents right justified within each byte. For
each register, the 1st byte contains the high-order bits, and the 2nd contains the low-order bits.
Follower address 01
Function 03
Byte count 04
Query
The query telegram specifies the register reference to be preset. Register addresses start at 0, that is, register 1 is addressed as 0.
Follower address 01
Function 06
Preset data HI 00
Preset data LO 01
Response
The normal response is an echo of the query, returned after the register contents have been passed.
Follower address 01
Function 06
Register address HI 03
Register address LO E7
Preset data HI 00
Preset data LO 01
Query
The query telegram specifies the register references to be preset. Register addresses start at 0, that is, register 1 is addressed as 0.
Example of a request to preset 2 registers (set parameter 1-24 Motor Current to 738 (7.38 A)):
Follower address 01
Function 10
Starting address HI 04
Starting address LO 07
Number of registers HI 00
Number of registers LO 02
Byte count 04
Response
The normal response returns the follower address, function code, starting address, and quantity of registers preset.
Follower address 01
Function 10
Starting address HI 04
Starting address LO 19
Number of registers HI 00
Number of registers LO 02
Master-follower
Bit
no.: 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
02 DC brake Ramp
03 Coasting No coasting
07 No function Reset
08 No function Jog
09 Ramp 1 Ramp 2
15 No function Reverse
Bits 00/01
Bits 00 and 01 are used to select among the 4 reference values, which are preprogrammed in parameter 3-10 Preset Reference according
to the following table.
NOTICE
In parameter 8-56 Preset Reference Select, define how bit 00/01 gates with the corresponding function on the digital inputs.
Bit 02 = 0: Leads to DC brake and stop. Set braking current and duration in parameter 2-01 DC Brake Current and parameter 2-02 DC
Braking Time.
Bit 03 = 0: The drive immediately releases the motor (the output transistors are shut off ), and it coasts to a standstill.
Bit 03 = 1: If the other starting conditions are met, the drive starts the motor.
In parameter 8-50 Coasting Select, define how bit 03 gates with the corresponding function on a digital input.
Bit 04 = 0: Makes the motor speed ramp down to stop (set in parameter 3-81 Quick Stop Ramp Time).
Bit 05 = 0: The present output frequency (in Hz) freezes. Change the frozen output frequency only with the digital inputs programmed to
[21] Speed up and [22] Speed down (parameter 5-10 Terminal 18 Digital Input to parameter 5-13 Terminal 29 Digital Input).
NOTICE
If freeze output is active, the drive can only be stopped in 1 of the following ways:
l Bit 03 coast stop.
l Bit 02 DC brake
l Digital input programmed to [5] DC brake inverse, [2] Coast inverse, or [3] Coast and reset inv (parameter 5-10 Terminal 18
Digital Input to parameter 5-13 Terminal 29 Digital Input).
Bit 06 = 0: Causes a stop and makes the motor speed ramp down to stop via the selected ramp-down parameter.
Bit 06 = 1: If the other starting conditions are met, bit 06 allows the drive to start the motor.
In parameter 8-53 Start Select, define how bit 06 ramp stop/start gates with the corresponding function on a digital input.
Bit 07 = 0: No reset.
Bit 07 = 1: Resets a trip. Reset is activated on the leading signal edge, that is, when changing from logic 0 to logic 1.
Bit 08 = 1: Parameter 3-11 Jog Speed [Hz] determines the output frequency.
Bit 09 = 0: Ramp 1 is active (parameter 3-41 Ramp 1 Ramp Up Time to parameter 3-42 Ramp 1 Ramp Down Time).
Bit 09 = 1: Ramp 2 is active (parameter 3-51 Ramp 2 Ramp Up Time to parameter 3-52 Ramp 2 Ramp Down Time).
Bit 10 = 1: The control word is used. This function is relevant because the telegram always contains the control word, regardless of the
telegram type. If the control word is not needed when updating or reading parameter, turn it off.
Bit 11 = 1: Relay 01 activated if [36] Control word bit 11 is selected in parameter 5-40 Function Relay.
Bit 12 = 1: Relay 02 is activated if [37] Control word bit 12 is selected in parameter 5-40 Function Relay.
Use bit 13 to select from the 2 menu setups according to the following table.
Setup Bit 13
1 0
2 1
The function is only possible when [9] Multi set-ups is selected in parameter 0-10 Active Set-up.
To define how bit 13 gates with the corresponding function on the digital inputs, use parameter 8-55 Set-up Select.
Bit 15 Reverse
Bit 15 = 0: No reversing.
Bit 15 = 1: Reversing. In the default setting, reversing is set to digital in parameter 8-54 Reversing Select. Bit 15 causes reversing only
when serial communication [2] Logic OR or [3] Logic AND is selected.
Follower-master
Bit
no.: 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
02 Coasting Enable
03 No error Trip
05 Reserved –
07 No warning Warning
08 Speed≠reference Speed=reference
11 No operation In operation
Bit 00=1: The drive controls are ready but the power component does not necessarily receive any supply (if there is 24 V external supply
to controls).
Bit 01=1: The drive is ready for operation, but the coasting command is active via the digital inputs or via serial communication.
Bit 02=1: The drive starts the motor with a start command.
Bit 04=1: The drive shows an error but does not trip.
Bit 08=0: The motor runs, but the present speed is different from the preset speed reference. It might happen when the speed ramps up/
down during start/stop.
Bit 08=1: The motor speed matches the preset speed reference.
Bit 09=0: [Off/Reset] is activated on the control unit or [2] Local in parameter 3-13 Reference Site is selected. It is not possible to control
the drive via serial communication.
Bit 09=1: It is possible to control the drive via the fieldbus/serial communication.
Bit 10=0: The output frequency has reached the value in parameter 4-12 Motor Speed Low Limit [Hz] or parameter 4-14 Motor Speed
High Limit [Hz].
Bit 12=1: The drive stops because of overtemperature, but the unit does not trip and resumes operation once the overtemperature
normalizes.
Bit 13=1: The DC voltage in the drive’s DC link is too low or too high.
Bit 14=0: The motor current is lower than the current limit selected in parameter 4-18 Current Limit.
Bit 14=1: The current limit in parameter 4-18 Current Limit is exceeded.
Bit 15=0: The timers for motor thermal protection and thermal protection are not exceeded 100%.
e30ba276.11
Master-follower
16 bit
Follower-follower
10 Application Examples
10.1 Introduction
The examples in this section are intended as a quick reference for common applications.
l Parameter settings are the regional default values unless otherwise indicated (selected in parameter 0-03 Regional Settings).
l Parameters associated with the terminals and their settings are shown next to the drawings.
l Required switch settings for analog terminals 53 or 54 are also shown.
10.2 AMA
Table 66: AMA with T27 Connected
+ 10V 50
A IN 53
A IN 54
COM 55
A OUT 42
10.3 Speed
Table 67: Analog Speed Reference (Voltage)
e30bf818.10
Parameter 6-10 Terminal 53 Low Voltage *0.07 V
FC
Parameter 6-11 Terminal 53 High Voltage *10 V
+ 24 V 12
18 Parameter 6-14 Terminal 53 Low Ref./ *0
D IN
19 Feedb. Value
D IN
D IN 27 Parameter 6-15 Terminal 53 High Ref./ 50 Hz
D IN 29 Feedb. Value
D IN 31
Parameter 6-19 Terminal 53 mode *[1] Voltage
D IN 32
D IN 33 *=Default value
Notes/comments:
+ 10V 50
+
A IN 53
A IN 54
COM 55
-
A OUT 42
0 ~ 10 V
e30bf819.10
Parameter 6-22 Terminal 54 Low Current *4 mA
FC
Parameter 6-23 Terminal 54 High Current *20 mA
+ 24 V 12
D IN 18 Parameter 6-24 Terminal 54 Low Ref./ *0
D IN 19 Feedb. Value
D IN 27 Parameter 6-25 Terminal 54 High Ref./ 50 Hz
D IN 29 Feedb. Value
D IN 31
Parameter 6-29 Terminal 54 mode [0] Current
D IN 32
D IN 33 *=Default value
Notes/comments:
+ 10V 50
+
A IN 53
A IN 54
COM 55
-
A OUT 42
4 - 20mA
Notes/comments:
+ 10V 50
A IN 53 ≈ 5kΩ
A IN 54
COM 55
A OUT 42
e30bf821.10
Parameter 5-10 Terminal 18 Digital Input *[8] Start
FC
+ 24 V 12 Parameter 5-12 Terminal 27 Digital Input [19] Freeze Reference
+ 10V 50
A IN 53
A IN 54
COM 55
A OUT 42
e30bb840.12
Speed
Reference
Start (18)
Speed up (29)
10.4 Start/Stop
Table 71: Start/Stop with Reversing and 4 Preset Speeds
e30bf823.10
Parameter 5-11 Terminal 19 Digital Input [1] Reset
FC
+ 24 V 12 *=Default value
D IN 18 Notes/comments:
D IN 19
D IN 27
D IN 29
D IN 31
D IN 32
D IN 33
+ 10V 50
A IN 53
A IN 54
COM 55
A OUT 42
NOTICE
To meet PELV insulation requirements, use reinforced or double insulation on the thermistors.
e30bf824.10
Parameter 1-90 Motor Thermal Protection [2] Thermistor trip
FC
Parameter 1-93 Motor Thermal Source [1] Analog input 53
+ 24 V 12
D IN 18 Parameter 6-19 Terminal 53 mode *[1] Voltage
D IN 19
*=Default value
D IN 27
D IN 29 Notes/comments: If only a warning is needed, set parameter 1-90 Motor Thermal
D IN 31 Protection to [1] Thermistor warning.
D IN 32
D IN 33
+ 10V 50
A IN 53
A IN 54
COM 55
A OUT 42
e30bd150.12
Parameter 4-30 Motor Feedback Loss [1] Warning
FC
Function
+ 24 V 12
D IN 18 Parameter 4-31 Motor Feedback Speed 100
D IN 19 Error
D IN 27
Parameter 4-32 Motor Feedback Loss 5s
D IN 29 Timeout
D IN 31
D IN 32 Parameter 7-00 Speed PID Feedback [2] MCB 102
D IN Source
33
Parameter 17-11 Resolution (PPR) *1024
+ 24 V DC
e30bd366.12
GND
A
B
12 18 19 27 29 32 33 20
1
A
2
A
l Motor.
l Brake (gearbox, mechanical brake).
l Drive.
l Encoder as feedback system.
l Brake resistor for dynamic brake.
l Transmission.
l Load.
Menu
ck
Ba
On OK
Warn.
Alarm
4 5 6 5 7
2 3
5 Transmission 6 Gearbox
7 Load
e30bv168.10
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
F C - 3 6 0 T 4 E 2 0 H 2 X X C X X X S X X X X A B X
FC-360Q110T4E20H2XXCXXXSXXXXA0BX
The meaning of the characters in the string is defined in this chapter. In the example above, a drive is configured with the following
options:
Adaptation 23 X: No adaptation
12 Appendix
12.1 Abbreviations and Symbols
Table 78: Abbreviations and Symbols
A Ampere/AMP
AC Alternating current
AD Air discharge
AI Analog input
°C Degrees Celsius
CB Circuit breaker
CD Constant discharge
CDM Complete Drive Module: The drive, feeding section, and auxiliaries.
CM Common-mode
CT Constant torque
DC Direct current
DI Digital input
DM Differential mode
°F Degrees Fahrenheit
fM Motor frequency
fMAX Maximum output frequency that the drive applies on its output.
g Gram
HO High overload
Hp Horse power
Hz Hertz
IP Ingress protection
kHz Kilohertz
m Meter
mA Milliampere
min Minute
mm Millimeter
ms Millisecond
ηVLT Efficiency of the drive defined as ratio between power output and power input.
Nm Newton meter
NO Normal overload
On/Offline parameters Changes to online parameters are activated immediately after the data value is changed
Pbr, cont. Rated power of the brake resistor (average power during continuous braking)
PE Protective earth
Process PID Proportional integrated differential regulator that maintains the speed, pressure, temperature, and
so on.
Rbr, nom Nominal resistor value that ensures a brake power on the motor shaft of 150/160% for 1 minute.
Rs Stator resistance
s Second
V Volts
VT Variable torque
12.2 Definitions
12.2.1 AC Drive
Coast
IVLT, MAX
IVLT, N
UVLT, MAX
12.2.2 Input
Control commands
Start and stop the connected motor with the LCP and digital inputs.
Functions are divided into 2 groups. Functions in group 1 have higher priority than functions in group 2.
Group 1 Coast stop, reset and coast stop, quick stop, DC braking, stop, and [OFF].
Group 2 Start, latched start, start reversing, jog, freeze output, and [Hand On].
12.2.3 Motor
Motor running
Torque generated on the output shaft and speed from 0 RPM to maximum speed on the motor.
fJOG
Motor frequency when the jog function is activated (via digital terminals or bus).
fM
Motor frequency.
fMAX
fMIN
fM, N
IM
IM, N
nM, N
ns
nslip
Motor slip.
PM, N
TM, N
UM
UM, N
Break-away torque
e75za078.10
Torque
Pull-out
RPM
ηVLT
The efficiency of the drive is defined as the ratio between the power output and the power input.
Start-disable command
A start-disable command belonging to the control commands in group 1. See the table in the chapter Input for more details.
Stop command
A stop command belonging to the control commands in group 1. See the table in the chapter Input for more details.
12.2.4 References
Analog reference
Binary reference
Preset reference
A defined preset reference to be set from -100% to +100% of the reference range. Selection of 8 preset references via the digital
terminals. Selection of 4 preset references via the bus.
Pulse reference
RefMAX
Determines the relationship between the reference input at 100% full-scale value (typically 10 V, 20 mA) and the resulting reference. The
maximum reference value is set in parameter 3-03 Maximum Reference.
RefMIN
Determines the relationship between the reference input at 0% value (typically 0 V, 0 mA, 4 mA) and the resulting reference. The
minimum reference value is set in parameter 3-02 Minimum Reference.
12.2.5 Miscellaneous
Analog inputs
The analog inputs are used for controlling various functions of the drive.
Analog outputs
The AMA algorithm determines the electrical parameters for the connected motor at standstill.
Brake resistor
The brake resistor is a module capable of absorbing the brake power generated in regenerative braking. This regenerative brake power
increases the DC-link voltage and a brake chopper ensures that the power is transmitted to the brake resistor.
CT characteristics
Constant torque characteristics used for all applications such as conveyor belts, displacement pumps, and cranes.
Digital inputs
The digital inputs can be used for controlling various functions of the drive.
Digital outputs
The drive features 2 solid-state outputs that can supply a 24 V DC (maximum 40 mA) signal.
ETR
Electronic thermal relay is a thermal load calculation based on present load and time. Its purpose is to estimate the motor temperature.
FC standard bus
Includes RS485 bus with FC protocol or MC protocol. See parameter 8-30 Protocol.
Initializing
If initializing is carried out (parameter 14-22 Operation Mode), the drive returns to the default setting.
An intermittent duty rating refers to a sequence of duty cycles. Each cycle consists of an on-load and an off-load period. The operation
can be either periodic duty or non-periodic duty.
LCP
The local control panel makes up a complete interface for control and programming of the drive. The LCP is detachable. With the
installation kit option, the LCP can be installed up to 3 m (9.8 ft) from the drive in a front panel.
GLCP
The graphic local control panel interface for control and programming of the drive. The display is graphic and the panel is used to show
process values. The GLCP has storing and copy functions.
NLCP
The numerical local control panel interface for control and programming of the drive. The display is numerical and the panel is used to
show process values. The NLCP has storing and copy functions.
lsb
msb
MCM
Short for mille circular mil, an American measuring unit for cable cross-section. 1 MCM = 0.5067 mm2.
On-line/off-line parameters
Changes to on-line parameters are activated immediately after the data value is changed. To activate changes to offline parameters,
press [OK].
Process PID
The PID control maintains speed, pressure, and temperature by adjusting the output frequency to match the varying load.
PCD
Power cycle
Switch off the mains until the display (LCP) is dark, then turn power on again.
Power factor
The power factor indicates to which extent the drive imposes a load on the mains supply.
The lower the power factor, the higher the IRMS for the same kW performance.
In addition, a high power factor indicates that the different harmonic currents are low.
The built-in DC coils produce a high power factor, minimizing the imposed load on the mains supply.
An external, digital pulse transmitter used for feeding back information on motor speed. The encoder is used in applications where great
accuracy in speed control is required.
RCD
Setup
Save parameter settings in 2 setups. Change between the 2 parameter setups and edit 1 setup while the other setup is active.
SFAVM
Acronym describing the switching pattern stator flux-oriented asynchronous vector modulation.
Slip compensation
The drive compensates for the motor slip by giving the frequency a supplement that follows the measured motor load, keeping the
motor speed almost constant.
The SLC is a sequence of user-defined actions executed when the associated user-defined events are evaluated as true by the SLC.
(Parameter group 13-** Smart Logic).
STW
Status word.
THD
Thermistor
Trip
A state entered in fault situations, for example if the drive is subject to overvoltage or when it is protecting the motor, process, or
mechanism. Restart is prevented until the cause of the fault has disappeared, and the trip state is canceled by activating reset or,
sometimes, by being programmed to reset automatically. Do not use trip for personal safety.
Trip lock
Trip lock is a state entered in fault situations when the drive is protecting itself and requiring physical intervention. An example causing a
trip lock is the drive being subject to a short circuit on the output. A locked trip can only be canceled by cutting off mains, removing the
cause of the fault, and reconnecting the drive. Restart is prevented until the trip state is canceled by activating reset or, sometimes, by
being programmed to reset automatically. Do not use trip lock for personal safety.
VT characteristics
VVC+
If compared with standard voltage/frequency ratio control, Voltage Vector Control (VVC+) improves the dynamics and stability, both
when the speed reference is changed and in relation to the load torque.
60° AVM
12.3 Conventions
l Numbered lists indicate procedures and description of illustrations.
l Bullet lists indicate other information.
l Italicized text indicates:
¢ Cross-reference.
¢ Link.
¢ Parameter name.
¢ Parameter group name.
¢ Parameter option.
¢ Footnote.
l All dimensions in drawings are in [mm] (in).
l An asterisk (*) indicates a default setting of a parameter.
Any information, including, but not limited to information on selection of product, its application or use, product design, weight, dimensions, capacity or any other technical
data in product manuals, catalog descriptions, advertisements, etc. and whether made available in writing, orally, electronically, online or via download, shall be considered
informative, and is only binding if and to the extent, explicit reference is made in a quotation or order confirmation. Danfoss cannot accept any responsibility for possible
errors in catalogs, brochures, videos and other material. Danfoss reserves the right to alter its products without notice. This also applies to products ordered but not delivered
provided that such alterations can be made without changes to form, fit or function of the product. All trademarks in this material are property of Danfoss A/S or Danfoss
group companies. Danfoss and the Danfoss logo are trademarks of Danfoss A/S. All rights reserved.
M0040401