Low Voltage Motor Protection System
Low Voltage Motor Protection System
• Flexible protection, control, and communication options to suit low voltage motor applications • Auto / Manual Control
• Small footprint designed specifically for IEC and NEMA MCC applications • Configurable Inputs
• Integrated pushbuttons and LED indicators reduce external components and wiring • Power Fail Restart
• Support for Hand Held Display (HHD) that provides a graphical color local interface allowing local
operators to view and change setting files and quickly access relay diagnostic information Communications
• Networking through RS485
Applications
• Multiple protocols - Modbus RTU ODVA
• Low Voltage Three-Phase Motors Compliant DeviceNet Internally powered
• MCC and standalone Panel Mount Applications Profibus
• IEC and NEMA Motor Control Center (MCCs) • Simultaneous Communications
• Process control applications
• System architecture requiring multiple simultaneous communications EnerVista™ Software
• FVNR, FVR, two speed • Simplify setup and configuration
• Strong document archive and management
system
• Simplify full featured monitoring and data
recording
• Strong maintenance and troubleshooting tool
• Seamless integration toolkit
MM200 Motor Manager
2
Current Unbalance
Overload Curves 1
1
In addition to the Thermal model, current
The MM200 thermal model can be programmed 0.1 1 10
Full Load Phase Current unbalance is available in the MM200 relay as
with one of 15 standard overload curves. Setpoint (Multiples of full load) an independent element with a built-in single
When properly selected to match the motor phasing detection algorithm.
manufactures thermal damage curves, the 15 Standard Curves available in the MM200
MM200 overload curve and Overload Pickup Undercurrent Protection
Level will determine the thermal capacity Undercurrent protection is standard in the
accumulated within the motor. be adjusted proportionally if the motor load is MM200. providing additional protection while
lower then rated. the motor is in the running state and any of the
Hot / Cold Safe Stall Ratio phase currents drop below the defined pick-up
This ratio defines the steady state level of
Motor Cool Time Constants
level for the durartion specified.
thermal capacity used (TCU) by the motor. When the MM200 detects that the motor is
This level corresponds to normal operating running at a load lower then the overload pickup
temperature of a fully loaded motor and will setpoint or the motor is stopped, it will start
2 [Link]
MM200 Motor Manager
[Link] 3
MM200 Motor Manager
Viewpoint Maintenance
Viewpoint Maintenance provides tools that will create reports on the
operating status of the relay, simplify the steps to download fault and event
data, and reduce the work required for cyber-security compliance audits.
EnerVista setup software simplifies every aspect of using the MM200 relay. The EnerVista
suite provides all the tools required to configure monitor & maintain the relay. Advanced
communications support ensures easy integration into new or existing DCS scada systems.
4 [Link]
MM200 Motor Manager
User Interface
Dimensions
[Link] 5
MM200 Motor Manager
The Hand Held Display (HHD) provides a rugged local interface for MM200 Motor Protection Systems
where a local display is not used in the MCC.
The HHD provides a graphical color local interface to the MM200 Motor Protection Systems allowing
local operators to view and change setting files and quickly access relay diagnostic information.
The HHD provides a clear and detailed view of all motor settings, diagnostic information and
metering data available in the MM200 allowing local operators to make informed decisions on the
motors operation.
Wiring Diagrams
6 [Link]
MM200 Motor Manager
[Link] 7
Technical Specifications
INPUTS POWER SUPPLY SPECIFICATIONS TYPE TESTS
PHASE CURRENT INPUTS POWER SUPPLY (LO RANGE) Dielectric voltage EN60255-5
CT Primary: 0.5A to 1000A Nominal 24 V DC withstand:
CT Secondary: 1A or 5A (Both supported as standard) Range 18 to 36 V DC Impulse voltage EN60255-5
Burden: 0.2VA Power Consumption 10 W typical withstand:
Conversion Range: 0.2 to 40 A (8x CT) POWER SUPPLY (HI RANGE) Damped IEC 61000-4-18/ IEC 60255-22-1
Nominal Frequency: 50/60 Hz Nominal 120 to 240 V AC; 125 to 250 V DC Oscillatory:
Frequency Range: 40-70 Hz Range 60 to 300 V AC (50 and 60 Hz); 84 to Electrostatic EN61000-4-2 / IEC 60255-22-2
Accuracy: (Ext CT) 2% of injected or 1% of 8xCTP 250 V DC Discharge:
Accuracy: (Direct) 2% of injected or 0.1A Power consumption 10 W typical RF immunity: EN61000-4-3 / IEC 60255-22-3
CT Withstand: 0.2 seconds at 100 x rated current Voltage withstand 2 × highest nominal voltage for 10 ms Fast Transient EN61000-4-4 / IEC 60255-22-4
1.0 second at 50 x rated current Disturbance:
2.0 seconds at 40 x rated current Surge Immunity: EN61000-4-5 / IEC 60255-22-5
continuous at 3 x rated current Conducted RF EN61000-4-6 / IEC 60255-22-6
(40DegC) PROTECTION Immunity:
SENSITIVE GROUND CURRENT INPUT THERMAL MODEL Power Frequency EN61000-4-7 / IEC 60255-22-7
CT Primary: 0.5A to 15A Standard Curve 1 to 15 in steps of 1 Immunity:
Conversion Range: 0.5A to 15A, 2000:1 CBCT Time Multiplier: Voltage IEC 60255-11
Accuracy: 0.1A (0.5A to 3.99A) Thermal Overload 1.01 to 1.25 in steps of 0.01 x FLA interruptionand
0.2A (4.0A to 15A) Pickup: Ripple DC:
DIGITAL INPUTS X7 Motor Full Load 0.5A to 1000A step 0.1A Radiated & CISPR11 / CISPR22 / IEC 60255-25
Current (FLA): Conducted
Fixed Threshhold: 24VDC
Motor Rated 100Vac - 690Vac Emissions:
Recognition Time: 2 cycle recognition Voltage:
Continuous Current 4mA Sinusoidal IEC 60255-21-1
Curve Biasing: Hot/Cold Curve Ratio Vibration:
Draw: Stopped / Running Cool Rate
Type: Opto-isolated inputs Shock & Bump: IEC 60255-21-2
Stopped/Running Exponential Siesmic: IEC 60255-21-3
External Switch: Wet Contact Time Cool
Max. Inputs Voltage: 30VDC Power magnetic IEC 61000-4-8
Constants Decay: Immunity:
DIGITAL INPUTS (HI) Hot/Cold Safe Stall 1% to 100% steps 1%
Nominal voltage 120 V AC to 240 V AC Pulse Magnetic IEC 61000-4-9
Ratio: Immunity:
Recognition time 2 cycles Timing Accuracy: ±500 ms
Continuous current 4 mA @120 V AC; 8 mA @ 240 V AC Damped Magnetic IEC 61000-4-10
Elements: Trip and Alarm Immunity:
draw CURRENT UNBALANCE
Type opto-isolated inputs Voltage Dip & IEC 61000-4-11
Unbalance: (Imax - Iav) / Iav, if Iav >= Ifla interruption:
External switch wet contact (Imax - Iav) / Iflc, if Iav < Ifla Damped IEC 61000-4-12
Voltage range 65 V AC to 300 V AC Range/Pickup 4% to 40% steps of 1% Oscillatory:
Level: Voltage Ripple: IEC 61000-4-17
OUTPUTS Time Delay: 1 to 60s in steps of 1 Ingress Protection: IEC 60529
Configuration: Electromechanical 2 x Form-A and 1 x Pickup Accuracy: ±2% Environmental IEC 60068-2-1
Form-C Timing Accuracy: ±500ms (Cold):
Contact Material: Silver aloy Elements: Trip and Alarm Environmental IEC 60068-2-2
Operate Time: 10ms UNDERCURRENT (Dry heat):
Minimum Contact 10mA at 5Vdc Pickup Level: 1 to 100% of FLC Relative Humidity IEC 60068-2-30
Load: Time Delay: 1 to 60 s in steps of 1 Cyclic:
Maximum Switching 300 ops / min (no load), Timing Accuracy: ±500ms Safety: UL508 / UL C22.2-14 / UL1053
Rate: 30 ops per min (load) Elements: Trip and Alarm
Mechanical Life: 10,000,000 ops MECHANICAL JAM ENVIRONMENTAL
Continuous Current 5 A at 60°C Pickup Level: 1.01 to 4.50 of FLA in steps of 0.01 Temperature Range *:
Make and Carry 30A per ANSI C37.90 Time Delay: 0.1 to 30.0s in steps of 0.1
for 0.2s: Ambient Operating: -20°C to +60°C
Timing Accuracy: ±500ms Ambient Storage: -40°C to +90°C
OUTPUT RELAY BREAK CAPACITY (FORM_A) Elements: Trip Humidity: Up to 90% non-condensing @ 55C
AC resistive, 5A GROUND FAULT Pollution degree: II
120Vac: Pickup Level: 0.5 to 15.0A in steps 0.1 (CBCT) IP Rating Base Unit IP20, Control panel IP54
AC resistive, 5A Time Delay: 0 to 10s in steps 0.1s (start)
240Vac: 0 to 5s in steps 0.1s (run) Alarm time *Temperature range based on 1” around base unit
AC inductive, 240VA delay on start/run: 0 to 60s in steps of 1s
PF = 0.4 pilot duty: Timing Accuracy: +100ms or ±0.5% of total time
DC resistive, 30Vdc 5A Elements: Trip and Alarm
OUTPUT RELAY BREAK CAPACITY (FORM_C) ACCELERATION TIMER COMMUNICATIONS
AC resistive, 5A (NO) 5A (NC) Pickup: Iav > Icuttoff SERIAL RS485
120Vac: Dropout: Iav < Ipu or Timer expired Baud Rates: Up to 115kbps
AC resistive, 5A (NO) 8A (NC) Time Delay 0.5 to 250.0 s in steps of 0.1 Parity: None
240Vac: (force to running if 0 to 5s in steps 0.1s (run) Protocol: Modbus© RTU/half duplex
AC inductive, 2 40VA expired): Typical Distance: 1200m
PF = 0.4 pilot duty: Timing Accuracy: ±500ms or ±1.5% of total time Isolation: 2kV
DC resistive, 30Vdc 5A Elements: Trip and Alarm DEVICENET (COPPER)
Modes: Slave at 125, 250, 500 kbaud
Connector: 5 pin terminal
CERTIFICATION PROFIBUS (COPPER)
ISO: Manufactured under an ISO9001 Modes: DP V0 Slave, up to 1.5MB
registered system Connector: 5 pin terminal
conforms to EN60255-5, EN60255-27,
EN60255-26, EN50263
cULus UL508 / UL1053 / [Link] 14
Please refer to MM200 Motor Manager Instruction Manual for complete technical specifications.
Ordering
MM200
* X * * * Description
Control Panel X None
B Basic Control Panel, no USB
Power Supply L 24 VDC
H 60 - 300 VAC
Communication 1 RS485 Modbus RTU + DeviceNet Slave
2 RS485 Modbus RTU + Profibus DP Slave
Protection S Standard Protection & Control
GE reserves the right to make changes to specifications of products described at any time without notice
and without obligation to notify any person of such changes.
GEA-12853-(E)