RDF-EARTHING RESISTENCE CALCULATION GRID-1 (MAIN EARTH GRID)
A) CALCULATION OF EARTHING ELECTRODES Grid-1
(20 Rod)
REROD = ρE SOIL
x ln 4L R
E
ROD : Earthing resistivity for one [Link] (Ω)
2.π.LR d E : Total Earthing resistivity for 20 earth. rod (Ω)
R TROD
200 4x3 LR : Length of eathing rod (m) = 3
E
R ROD = 2.π.3 x ln 0,.016 d : Diameter value of earthing rod (inch),(mm) =3/4, 16
R
E
= ln
ρE SOIL :Spesific Soil resistivity, 200 (Ω.m) accepted.
ROD 10.6 x 750
E
R ROD = 70.2 Ω (for 1 earthing rod)
E
E R ROD 70.2
R TROD = n = 20 3.5 Ω
B) CALCULATION OF COPPER CONDUCTOR
FOR 120mm2 cable
ρE SOIL 3L 3L
E
R RING = 0,366 x L log 2d + log 8H
200 3x100 3x100
E
R RING = 0,366 x log + log
100 2x0,0124 8x0,6
E
R RING = 4.3 Ω
RDF-EARTHING RESISTENCE CALCULATION GRID-1 (MAIN EARTH GRID)
n : Number of earthing rods = 20 ρESOIL :Spesific Soil resistivity, 200 (Ω.m) accepted.
L : Length of embedded conductor (m) = 100
H : Depth of embedded conductor (m) 0,6
2)
s : Section Cross of copper conductor (mm = 120
2 2
RERING : Earthing resistivity for 120 mm ring (Ω) d : Raduis value of 120 mm copper conductor 0,0124
. (m) =
TOTAL PROTECTIONAL EARTHING CALCULATION
1 1 1
E E E
R TOTAL = R RING + R TROD RETOTAL : Total earthing resistivity (Ω)
1 1 1
= +
E
R TOTAL 4.3 3.5
1
E
R TOTAL
E
R TOTAL = 1.9 Ω 1.9 Ω < 2 Ω ; acceptable value