M/S.

RUNGTA MINES LIMITED


CHAIBASA, JHARKHAND, INDIA

SPECIFICATION NO.:
NO 1155/RML/TS/MEC
MECH-012
FOR
SUPPLY
OF
CENTRIFUGAL PUMPS
FOR
STEELMELT SHOP-2
AT
M/S. RUNGTA MINES LIMITED, CHALIYAMA STEEL PLANT

MAY, 2017

AE - 767, Sec - 1, Salt Lake City, Kolkata 700 064


Ph:+91 33 2337 5484/ 85
Fax: +91 33 2334 0083
E-mail:[Link]@[Link]
mail:[Link]@[Link]

Page 1 of 5
TECHNICAL SPECIFICATION
OF
CENTRIFUGAL PUMPS
M/S. RUNGTA MINES LTD. CHALIYAMA STEEL PLANT

1.0 INTRODUCTION

M/s. Rungta Mines Limited (RML) are operating a DRI based steel plant
at Chaliyama near Chaibasa, Jharkhand,
Jharkhand India.. Major facilities of the
plant consist of 8x100 tpd DR units along with WHRB based Power
Plants and a Steelmelt Shop (SMS-1)(SMS 1) having 4x15-ton
4x15 capacity
Induction Furnace and 1x3-strand,
1 6/11 m radius billet caster.
Construction of a Bar & Rod Mill is currently under progress.

RML now intend to set up another Steelmelt Shop (SMS-2)


(SMS and 2 x 350
tpd DR kilns along with WHRB based Power Plants to augment the
production of the Chaliyama
Chaliyam plant. SMS-2 2 will also have 4x15-ton
4x15
Induction Furnace and 1x3-strand,
1 strand, 6/11 m radius Billet Caster

Plant and equipment


pment covered under this specification shall suit the
purpose for which they are intended and shall be of sturdy and robust
construction fit for steel plant use.

This Technical Specification is issued for Supply and Testing of Thirty


Nine (39) nos. Centrifugal Horizontal & Vertical Pumps in Steelmelt
Shop-22 at Chaliyama Steel Plant, Chaibasa,, Jharkhand, India.

Page 2 of 5
2.0 QUANTITIES & TECHNICAL PARTICULARS

A. P1 x 4 nos. (2W+2S) – Induction Furnace PH (SW supply to furnace


coil), Flow 214 CMH, Head 55 MWC

B. P2 x 4 nos. (2W+2S) – Induction Furnace PH (SW supply to furnace


coil), Flow 214 CMH, Head 55 MWC

C. P3 x 1 no. (1W+1S) – Induction Furnace PH (SW supply to EOHT), Flow


170 CMH, Head 30 MWC. One set to be Electrical Pump, the other set
to be Diesel Pump

D. P4 x 2 nos. (1W+1S)
1W+1S) – Induction Furnace PH (SW
SW supply to LF
LF) – TBA
later when LF is finalised

E. P5 x 2 nos. (1W+1S) – Induction Furnace PH (SW


SW supply to LF
LF) – TBA
later when LF is finalised

F. P6 x 4 nos. (2W+2S) – Induction Furnace PH (SW supply to furnace


panel), Flow 231 CMH, Head 34 MWC

G. P7 x 4 nos. (2W+2S) – Induction Furnace PH (SW supply to furnace


panel), Flow 231 CMH, Head 34 MWC

H. P8 x 4 nos. (2W+2S) – Induction Furnace PH (SW supply to furnace


panel), Flow 69 CMH, Head 35 MWC

I. P9 x 4 nos. (2W+2S) – Induction Furnace PH (SW supply to furnace


panel), Flow 69 CMH, Head 35 MWC

J. P10 x 4 nos. (2W+2S) – Induction Furnace PH (SW supply to sinter &


transformer panel),
panel Flow 21 CMH, Head 35 MWC

K. P11 x 3 nos. (2W+1S)


(2W+1 – Caster PH (SW supply to mould & m/c cooling
cooling),
Flow 270 CMH, Head 70 MWC

L. P12 x 2 nos. (1W+


W+1S) – Caster PH (RW
W supply to Caster), Flow 565
CMH, Head 30 MWC

M. P13 x 2 nos. (1W+1


1W+1S) – Caster PH (RW supply to spray cooling),
cooling Flow
207 CMH, Head 120 MWC

N. P14 x 2 nos. (1W+


W+1S) – Caster PH (Contaminated
Contaminated water from Scale Pit
Pit),
Flow 207 CMH, Head 30 MWC

Page 3 of 5
For detailed technical specifications, including MOC, construction,
application, system details and accessories, please refer to attached
data-sheets
sheets for respective Pumps. All pumps must conform to ISO
9906:2012 and DIN 24256 standards.

Motors must be 415V, 3 Ph., 50 Hz. Squirrel Cage TEFC type, IP 55


protection, Class B/F, Non-flame
Non proof and of a reputed make
(KEC/ABB/CGL/Siemens/Bharat
C/ABB/CGL/Siemens/Bharat Bijlee etc.)

3.0 SUBMISSIONS
Bidder is to submit the following documents along with their price offer:
• GA Drawings and technical data sheets,, including performance
curves
• List of Exclusions
Bidders are also required to fill in the attached data-sheets
data with the
required information and submit accordingly with their offers.

4.0 SPARES
Bidder shall include the list of commissioning spares as well as
recommended spares list for Two
T (02) years.

5.0 PRICE
Bidder shall submit best delivery schedule and include additional
charges, if any, for supervision support and services during erection and
commissioning of the equipment.

Scope of supply must include, amongst others, the following :

• Pump
• Motor
• Diesel Engine (where applicable)
• Coupling
• Coupling Guard
• Base Frame
Page 4 of 5
6.0 GUARANTEE

The bidder shall provide guarantee for smooth operation of all items
supplied by them for Twelve
welve (12) months from the date of successful
commissioning, handover and acceptance by the client.