Refrigeration and Air Conditioning Basics
Refrigeration and Air Conditioning Basics
CONDITIONING
Presented By:
Vijay Malik
Lech in Mech. Engg.
Govt Polytechnic Jhajjar
Refrigeration
QR
Work Input
Heat
Pump
QR
Cold Space
Terminologies of Refrigeration
Refrigerating Effect (N): It is defined as the
quantity of heat extracted from a cold body or
space to be cooled in a given time.
N= Heat extracted from the cold space
Time taken
Specific Heat of water and ice : It is the quantity of
heat required to raise or lower the temperature of
one kg of water (or ice), through one kelvin or (10
c) in one second.
Specific heat of water, Cpw = 4.19 kJ/kg K
Specific heat of ice, Cpice = 2.1 kJ/kg K.
Terminologies of Refrigeration
Capacity of a Refrigeration Unit :
Capacity of a refrigerating machines are expressed by their
cooling capacity.
The standard unit used for expressing the capacity of
refrigerating machine is ton of refrigeration.
One ton of refrigeration is defined as, “the quantity of heat
abstracted (refrigerating effect) to freeze one ton of water
into one ton of ice in a duration of 24 hours at 0o c”.
Heat extracted from at 0o c = latent heat of ice
Latent heat of ice = 336 kJ/kg
i.e., 336 kJ of heat should be extracted from one kg of water at
0o C to convert it into ice.
Terminologies of Refrigeration
Working :
1. The low pressure refrigerant vapour coming out of the
evaporator flows into the compressor.
2. The compressor is driven by a prime mover.
3. In the compressor the refrigerant vapour is compressed.
4. The high pressure refrigerant vapour from the
compressor is then passed through the condenser.
5. The refrigerant gives out the heat it had taken in the
evaporator (N)
Vapour Compression Refrigeration System
- Working
Working :
6. The heat equivalent of work done on it (w) on the
compressor.
7. This heat is carried by condenser medium which may be
air or water.
8. The high pressure liquid refrigerant then enters the
expansion valve.
9. This valve allows the high pressure liquid refrigerant to
flow at a controlled rate into the evaporator.
10. While passing though this valve the liquid partially
evaporates.
Vapour Compression Refrigeration System
- Working
Working :
[Link] of the refrigerant is vapourised only in the
evaporator, at a low pressure.
12. In the evaporator the liquid refrigerant absorbs
its latent heat of vapourisation from the material
which is to be cooled.
13. Thus the refrigerating effect (N) is obtained.
14. Then the low pressure refrigerant enters the
compressor and the cycle is repeated.
Vapour Absorption Refrigeration system
Construction:
The vapour absorption system consists of a
condenser, an expansion valve and an
evaporator.
They perform the same as they do in vapour
compression method.
In addition to these, this system has an absorber,
a heat exchanger, an analyser and a rectifier.
Vapour Absorption Refrigeration system –
Working
Working:
1. Dry ammonia vapor at low pressure passes in to the
absorber from the evaporator.
2. In the absorber the dry ammonia vapor is dissolved in
cold water and strong solution of ammonia is formed.
3. Heat evolved during the absorption of ammonia is
removed by circulating cold water through the coils kept
in the absorber.
4. The highly concentrated ammonia (known as Aqua
Ammonia) is then pumped by a pump to generator
through a heat exchanger.
Vapour Absorption Refrigeration system -
Construction
Working:
5. In the heat exchanger the strong ammonia
solution is heated by the hot weak solution
returning from the generator to the absorber.
6. In the generator the warm solution is further
heated by steam coils, gas or electricity and the
ammonia vapour is driven out of solution.
7. The boiling point of ammonia is less than that of
water.
8. Hence the vapours leaving the generator are
mainly of ammonia.
Vapour Absorption Refrigeration system -
Construction
Working:
9. The weak ammonia solution is left in the
generator is called weak aqua.
10. This weak solution is returned to the absorber
through the heat exchanger.
11. Ammonia vapours leaving the generator may
contain some water vapour.
12. If this water vapour is allowed to the condenser
and expansion valve, it may freeze resulting in
chocked flow.
13. Analyser and rectifiers are incorporated in the
system before condenser.
Vapour Absorption Refrigeration system -
Construction
Working:
14. The ammonia vapour from the generator passes
through a series of trays in the analyser and ammonia is
separated from water vapour.
15. The separated water vapour returned to generator.
16. Then the ammonia vapour passes through a rectifier.
17. The rectifier resembles a condenser and water vapour
still present in ammonia vapour condenses and the
condensate is returned to analyser.
18. The virtually pure ammonia vapour then passes
through the condenser.
Vapour Absorption Refrigeration system -
Construction
Working:
19. The latent heat of ammonia vapour is rejected to
the cooling water circulated through the
condenser and the ammonia vapour is
condensed to liquid ammonia.
20. The high pressure liquid ammonia is throttled
by an expansion valve or throttle valve.
21. This reduces the high temperature of the liquid
ammonia to a low value and liquid ammonia
partly evaporates.
22. Then this is led to the evaporator.
23. In the evaporator the liquid fully vaporizes.
Vapour Absorption Refrigeration system -
Construction
Working:
24. The latent heat of evaporation is obtained from
the brine or other body which is being cooled.
25. The low pressure ammonia vapour leaving the
evaporator again enters the absorber and the
cycle is completed.
26. This cycle is repeated again to provide the
refrigerating effect.
Applications of refrigeration system
1 This system has more wear and Only moving part in this system is
tear and produces more noise an aqua pump. Hence the quieter
due to the moving parts of the in operation and less wear and
compressor. tear
2. Electric power is needed to Waste of exhaust steam may be
drive the system used. No need of electric power
3. COP is more COP is less
4. At partial loads performance is At partial loads performance is not
poor. affected.
5. Mechanical energy is supplied Heat energy is utilised
through compressor
6. Energy supplied is ¼ to ½ of Energy supplied is about one and
the refrigerating effect (less) half times the refrigerating effect
(more)
Comparison between Vapour compression &
Vapour Absorption refrigeration systems
Insulation materials:
Fiber glass, k= 0.032 W/m °C
Urethane foam, k= 0.019 W/m °C
Wall thickness for foam
For freezer section reduced from 90 to 48 mm
For refrigeration section reduced from 70 to 40 mm
Works better up to the environment of 43°C
Ice maker (2 to 3 kg/day)
Vapor absorption is more expensive and less
efficient
Domestic refrigerator……
AIR CONDITIONING:
Presented By:
Vijay Malik
Lech in Mech. Engg.
Govt Polytechnic Jhajjar
Vapor-Compression
Refrigeration Cycle
►Most common refrigeration cycle in use today
►There are four principal
control volumes involving
these components:
►Evaporator
►Compressor
►Condenser
►Expansion valve Two-phase
liquid-vapor mixture
State 2
State1 kJ
h 238.41 Compressor exit kJ
Compressor inlet 1
kg h2 s 278.23
P2 s P2 900 kPa kg
T1 20o C s 0.9456 kJ kJ T2 s 43.79 C
o
x1 1.0 1 kg K s2 s s1 0.9456
kg K
State 3 kJ State 4
h 101.61 x4 0.358
Condenser exit 3
kg Throttle exit
kJ
P3 900 kPa kJ T4 T1 20o C s4 0.4053
s3 0.3738 kg K
x3 0.0 kg K h4 h3
8
Q&L m&(h1 h4 ) h1 h4
COPR
Wnet , in m&(h2 h1 ) h2 h1
&
kJ
(238.41 101.61)
kg
kJ
(278.23 238.41)
kg
3.44
The tons of refrigeration, often called the cooling load or refrigeration effect, are
Q&L m&(h1 h4 )
kg kJ 1Ton
3 (238.41 101.61)
min kg 211 kJ
min
1.94 Ton
TL
COPR , Carnot
TH TL
(20 273) K
(43.79 (20)) K
3.97 9
Another measure of the effectiveness of the refrigeration cycle is how much input
power to the compressor, in horsepower, is required for each ton of cooling.
W&net , in 4.715
&
QL COPR
4.715 hp
3.44 Ton
hp
1.37
Ton
10
Features of
Actual Vapor-Compression Cycle
►Heat transfers between refrigerant and cold and
warm regions are not reversible.
►Refrigerant temperature
in evaporator is less than
TC.
►Refrigerant temperature
in condenser is greater
than TH.
►Irreversible heat
transfers have negative
effect on performance.
Features of
Actual Vapor-Compression Cycle
►The COP decreases – primarily due to increasing
compressor work input – as the
►temperature of the
refrigerant passing Trefrigerant ↑
through the evaporator is
reduced relative to the
temperature of the cold
region, TC.
►temperature of the
refrigerant passing Trefrigerant ↓
(Eq. 6.48)
kg kJ 1 kW
Wc 0.08 (280.15 241.35) 3.1 kW
s kg 1 kJ/s
(b) The refrigeration capacity is
Qin m
(h1 h4 )
kg kJ 1 ton 60 s
Qin 0.08 (241.35 91.49) 3.41 tons
s kg 211 kJ/min min
Actual Vapor-Compression Cycle
State 1 2s 2 3 4
h (kJ/kg) 241.35 272.39 280.15 91.49 91.49
c
Wc / ms (h2 s h1 )
Wc / m (h2 h1 )
(272.39 241.35)kJ/kg
c 0.8 = 80%
(280.15 241.35)kJ/kg
p-h Diagram
►The pressure-enthalpy (p-h) diagram is a
thermodynamic property diagram commonly used
in the refrigeration field.
Other Refrigeration Cycles
20
Multistage compression refrigeration systems
21
Multipurpose refrigeration systems
22
Liquefaction of gases
23
Selecting Refrigerants
►Refrigerant selection is based on several
factors:
►Performance: provides adequate cooling
capacity cost-effectively.
►Safety: avoids hazards (i.e., toxicity).
►Environmental impact: minimizes harm to
stratospheric ozone layer and reduces
negative impact to global climate change.
Refrigerant Types and Characteristics
Global Warming Potential (GWP) is a simplified index that estimates the potential
future influence on global warming associated with different gases when released
to the atmosphere.
Refrigerant Types and Characteristics
►Chlorofluorocarbons (CFCs) and Hydrochlorofluorocarbons
(HCFCs) are early synthetic refrigerants each containing chlorine.
Because of the adverse effect of chlorine on Earth’s stratospheric
ozone layer, use of these refrigerants is regulated by international
agreement.
►Hydrofluorocarbons (HFCs) and HFC blends are chlorine-free
refrigerants. Blends combine two or more HFCs. While these
chlorine-free refrigerants do not contribute to ozone depletion, with
the exception of R-1234yf, they have high GWP levels.
►Natural refrigerants are nonsynthetic, naturally occurring
substances which serve as refrigerants. These include carbon
dioxide, ammonia, and hydrocarbons. These refrigerants feature
low GWP values; still, concerns have been raised over the toxicity
of NH3 and the safety of the hydrocarbons.
Vapour Absorption
System
Presented By:
Vijay Malik
Lech in Mech. Engg.
Govt Polytechnic Jhajjar
COP for Ideal Vapor Absorption Refrigeration System
Practical Vapor – Absorption Refrigeration System
•
Practical vapor – absorption refrigeration system