CIVIL TEST HOUSE

VELCITI CONSULTING ENGINEERS PVT. LTD.


#22, Thiruvalluvar 1st Street, Thiruvengadam Nagar, Kandanchavadi, Chennai - 96
Phone: 91 - 9384033283 / 84, E-mail: [email protected]:www.velciti.com
GST No: 33AADCV3520A 1Z2
ULR No. : TC942025000002865F Date:-25-06-2025
Report No. : VEL/CTH/2025/1225-006

TEST REPORT ON WATER FOR CONSTRUCTION PURPOSE (CHEMICAL)


INDIAN OIL CORPORATION LIMITED..,
Customer Name & Address :(Marketing Division) Vallur Top Project Kondakkarai Village, SR Palayam Post,
Chennai-600 120

Customer reference No. :IOCL/VALLUR/NRP/24,Dated:-14-06-2025

SRF No. & Date :VEL/CTH/2024-25/0237,Date:-16-06-2025

Material / Brand * :Water for Construction Purpose Condition of Sample : Good


Anirudh Infrastructure Pvt Ltd.RMS Batching Plant. Burma Nagar Main Road,
Source Of Sample* :
Manali,Chennai.
Testing Of Materials For Fabrication,Erection,Testing and Commissioning Of Petroleum
Product & Fire Hydrant Piping, Supply,Installation,Testing & Commissioning Of
Project* :Effluent Treatment Plant,Construction Of plant/Non-Plant Sheds (Pump Houses &
Manifold,TLF/TLD Sheds etc.) at the Proposed Grass Root Petroleum Terminal at
Vallur.
Testing Commenced &Completed on :16-06-2025 to 23-06-2025 Temperature : 26.1°C

Sample ID No. :VEL/CTH/2024-25/0237/006 Group/Discipline : Water / Chemical


Sl. Requirements as per
Test Conducted Test Method Results
No. IS 456 : 2000, reaff 2021
1 pH Value IS 3025 (part 11) : 2022 7.50 Min 6.00

Max 500 mg/L -RCC work,


2 Chlorides as Cl (mg/L) IS 3025 (part 32) : 1988, reaff 2019 171.0
Max. 2000 mg/L -PCC work

3 Sulphates as SO3 (mg/L) IS 3025 (part 24/Sec 1) : 2022 37.0 Max 400 mg/L

4 Inorganic Solids (mg/L) IS 3025 (part 18) : 2022 555.0 Max 3000 mg/L

5 Organic Solids (mg/L) IS 3025 (part 18) : 2022 120.0 Max 200 mg/L

6 Total Suspended Solids (mg/L) IS 3025 (part 17) : 2022 <1 Max 2000 mg/L

Quantity of 0.02N NaOH required


7 to neutralise 100ml of water using IS 3025 (part 22) : 1986, reaff 2019 0.3 Max 5ml
phenolphthalein as an indicator
Quantity of 0.02N H2SO4 required
8 to neutralise 100ml of water using IS 3025 (part 23) : 1986, reaff 2019 12.1 Max 25ml
mixed indicator, ml
Remarks: The tested sample meet the requirements as per IS 456 : 2000 reaff 2021 with respect to the parameters tested
* As furnished bythe customer
Notes:
1) The above test report results relates only to the samples tested in this laboratory.
2) This test report shall not be reproduced except in full, without the written approval of this laboratory.

Reviewed By Authorized Signatory


(C.Thangamuthu Muneeswaran) (J. Ramesh) Page No : 01 of 01
********************** END OF REPORT ***********************