Customer: ARRIYADH NEW MOBILITY

Address:
City:
EXEL S.r.l. Calculations and Checks Progetto INTEGRA

Circuit data table: LFPB-0

Circuit:

Downstream load general data: LFPB


Distribution system (neutral to earth connection) TN-S
No load rated voltage 400 [V]
Maximum perspective short circuit current Ik 1,56 [ kA ]
Maximum allowed voltage drop 5 [%]

Data relating to the load power supply circuit


Load Code LFPB-0
Cross Section ___ [ mm² ]
Lenght ___ [m]
Installation mode ___

Protection device data


Type - Brand OT160EV04 - ABB
Poles number 4 x 160
Rated current 160 [A]
Brc ___ [ kA ]
Residual current ___ [A]
I protection tripping current 352 [A]

Electrical data of selected circuit


Max end of line Ik 1.564 [A]
I earth fault Phase-PE end of line 575 [A]
Max I²t start of the line / K²S² phase ___ / ___ [ A²S ]
Max I²t start of the line / K²S² neutral ___ / ___ [ A²S ]
Max I²t start of the line / K²S² PE ___ / ___ [ A²S ]
Load current Ib 78 [A]
Current setting Ir 160 [A]
Current carrying capacity Iz ___ [A]
Effective operation current If 192 [A]
1,45 Iz value ___ [A]
Voltage drop with Ib 4,6 [%]
Max protected length ___ [m]
Max protected length SPD ___ [m]

Final evaluation

Ik less than or equal IC check is OK


Voltage drop is less than maximum allowed value
Indirect contact protection is OK
Tripping I less than or equal Ik is OK
In less than or equal Size is OK
No feeder
Customer: ARRIYADH NEW MOBILITY
Address:
City:
EXEL S.r.l. Calculations and Checks Progetto INTEGRA

Circuit data table: LFPB-1

Circuit: FIRE PUMP PANEL FP.3

Downstream load general data: LFPB


Distribution system (neutral to earth connection) TN-S
No load rated voltage 400 [V]
Maximum perspective short circuit current Ik 1,56 [ kA ]
Maximum allowed voltage drop 5 [%]

Data relating to the load power supply circuit


Load Code LFPB-1
Cross Section 4(1x70)+(1G70) [ mm² ]
Lenght 5 [m]
Installation mode 143/F113_/40/0,655

Protection device data


Type - Brand OT160EV04 - ABB
Poles number 4 x 160
Rated current 160 [A]
Brc ___ [ kA ]
Residual current ___ [A]
I protection tripping current 352 [A]

Electrical data of selected circuit


Max end of line Ik 1.548 [A]
I earth fault Phase-PE end of line 569 [A]
Max I²t start of the line / K²S² phase 504.302 / 100.200.100 [ A²S ]
Max I²t start of the line / K²S² neutral 144.828 / 100.200.100 [ A²S ]
Max I²t start of the line / K²S² PE 145.278 / 100.200.100 [ A²S ]
Load current Ib 78 [A]
Current setting Ir 160 [A]
Current carrying capacity Iz 176 [A]
Effective operation current If 192 [A]
1,45 Iz value 255 [A]
Voltage drop with Ib 4,66 [%]
Max protected length 38 [m]
Max protected length SPD 0 [m]

Final evaluation

Ik less than or equal IC check is OK


Voltage drop is less than maximum allowed value
Indirect contact protection is OK
Tripping I less than or equal Ik is OK
In less than or equal Size is OK
Overload protection is OK
Maximum allowed cable temperature is OK
I²t less than or equal K²S² is OK
Customer: ARRIYADH NEW MOBILITY
Address:
City:
EXEL S.r.l. Calculations and Checks Progetto INTEGRA

Circuit data table: LFPB-2

Circuit: FIRE PUMP PANEL FP.4

Downstream load general data: LFPB


Distribution system (neutral to earth connection) TN-S
No load rated voltage 400 [V]
Maximum perspective short circuit current Ik 1,56 [ kA ]
Maximum allowed voltage drop 5 [%]

Data relating to the load power supply circuit


Load Code LFPB-2
Cross Section 4(1x70)+(1G70) [ mm² ]
Lenght 5 [m]
Installation mode 143/F113_/40/0,655

Protection device data


Type - Brand OT160EV04 - ABB
Poles number 4 x 160
Rated current 160 [A]
Brc ___ [ kA ]
Residual current ___ [A]
I protection tripping current 352 [A]

Electrical data of selected circuit


Max end of line Ik 1.548 [A]
I earth fault Phase-PE end of line 569 [A]
Max I²t start of the line / K²S² phase 504.302 / 100.200.100 [ A²S ]
Max I²t start of the line / K²S² neutral 144.828 / 100.200.100 [ A²S ]
Max I²t start of the line / K²S² PE 145.278 / 100.200.100 [ A²S ]
Load current Ib 0 [A]
Current setting Ir 160 [A]
Current carrying capacity Iz 176 [A]
Effective operation current If 192 [A]
1,45 Iz value 255 [A]
Voltage drop with Ib 4,6 [%]
Max protected length 296 [m]
Max protected length SPD 0 [m]

Final evaluation

Ik less than or equal IC check is OK


Voltage drop is less than maximum allowed value
Indirect contact protection is OK
Tripping I less than or equal Ik is OK
In less than or equal Size is OK
Overload protection is OK
Maximum allowed cable temperature is OK
I²t less than or equal K²S² is OK