ZP120 N
online
UPS
1,2,3,6,10,20 kVA
• LOCAL AREA NETWORKS (LAN) • INTERNET CENTERS (ISP/ASP/POP) • ELECTROMEDICAL DEVICES
• SERVERS • INDUSTRIAL PLCS • TELECOMMUNICATION DEVICES
• DATA CENTERS • EMERGENCY DEVICES (LIGHTS, ALARM) • INDUSTRIAL APPLICATION
series
ZP120 N
G-TEC is proud to introduce the upgraded superior ZP120N UPS that can deliver clean, safe and regulated power
supply to protect your critical mission equipment, so as to safeguard your valuable equipment and critical data from
any abnormal power disturbances, such as surges, blackouts and lightning strikes. ZP120N UPS power capacity
is available from 1kVA to 3kVA 1/1 (1/1 stands for single phase input and single phase output); from 6kVA to
10kVA 1/1 and from 10kVA to 20kVA 3/1 (3/1 stands for three phase input and single phase output).
COMMON FEATURES:
• Digital Signal Processor (DSP) Control
• Cold Start Function
• Strongest performance
• High Power Density
• Flexible Settings
• Internal components designed for stressing
environment
• Highest efficiency with low heat dissipation
1-3kVA 1/1 6-10kVA 1/1 10-20kVA 1/1-3/1
• Long run time Model with optional battery and dedicated
super charger (KS Version)
1kVA to 3kVA 1/1
Strongest performance High Power Density
• DSP technology fully controlled • Wide input voltage range
• Self monitoring and fault diagnosis • 0.8 output power factor
• Dual internal communications bus • Input power factor correction and
• Lowest output voltage distortion lowest current distortion
USB
EPO
Intelligent
Slot
Flexible Settings
Ext
Battery
• Selectable configuration via LCD:
online, eco-mode, frequency/voltage converter
Fan AC Output mode (CVCF)
• EPO connector for remote emergency power off
Breaker • Standard external battery connector
AC Output
AC Input • Simplified installation
RJ45
menU: • Operation Mode • Input measures
• Mimic • Battery capacity
• Settings • Output measures
• Status/alarm code
6kVA to 10kVA 1/1
Strongest performance Flexible Settings
• DSP technology fully controlled • Selectable configuration via LCD: online, parallel,
• LCD display multi language eco-mode and frequency/voltage converter
• Real time event logs mode (CVCF)
• Dual internal communications bus • Parallelable up to 4 units with optional parallel kit
• Reduced audible noise • Standard mechanical maintenance bypass
• Optional internal insulation transformer
High Power Density • EPO connector for remote emergency power off
• 0,9 output power factor • Standard external battery connector
• Minimum acceptable input voltage 110 Vac • Back-feed protection
USB
EPO
Dry Contact menU:
Intelligent • Input information
Slot
Parallel • Operating status
Port • Battery information
Fan • Load information
• Output information
10kVA to 20kVA 3/1
The 10-20kVA threephase input and single phase output is an upgrade of the ZP120N-10K-11. They have
the same technical performance with the following advantages:
• Input voltage autosensing (3ph or 1ph)
• Large cabinet suitable for more internal battery strings
• Dual inputs with separate bypass line as standard Parallel Port (Optional)
RS232
USB EPO
EPO
Dry Contact USB Intelligent
Intelligent Slot
Slot
Parallel Port
Fan
Fan
Back Feed
Maintenance Connector
Switch Maintenance
Input Switch
Breaker
Neutral Terminal
Input Switch Cover Blocks
Breaker Cover
Terminal
Blocks
Cover
ZP120N-10K-11 ZP120N-20K
INPUT SWITCHBOARD
POWERSUPPLY
OUTPUT SWITCHBOARD
LOAD LOAD LOAD LOAD
ETHERNETNETWORK
ZP120N 6kVA to 20kVA UPS with optional parallel kit fitted
in parallel configuration, can meet most demanding power
requirement. Increase power availability and flexibility.
Parallel Redundancy feature provides economic power solution
for system integration. Furthermore, parallel redundancy feature
equally shares the load to maximize UPS performance, and more
secure UPS continuous operation.
Communication and Power Management Solutions
WinPower CD is packed with UPS, and can also be downloaded from the internet. It has the function to remote
monitor and control UPS, warning notifications through broadcast and mobile phone, multi-shutdown PCs, and
schedule UPS self-test. This unique software provides complete power protection for computer system during po-
wer failure. The software supports lots of O/S including Windows family, Linux, Sun Solaris 7/8/9, FreeBSD, IBM Aix
4.3x, 5.1x, and HP-UX 11.x. More than that, to offer increased benefits for our customers, we have also released
USB version MAC version on the internet.
INTERFACE OPTION:
SNMP CARD RELAY CARD/AS400 MODBUS INTERFACE
• Power flow display for monitoring UPS status • Multi-language versions: English, Germanic, French,
• Scheduled system shutdown/restart Italian,Spanish, Portuguese and Chinese
• Scheduled UPS test • Selectable User Interface (Background)
• Warning notification via E-mail / Pager • UPS Parameter setting
• Warning notification via Broadcast • Record logs for analysis
• Password security protection • SNMP Network card allows management of UPS across
• Remote Monitor / Control via LAN LAN using any of the main network communication
protocols – TCP/IP and network interface via SNMP.
ZP120 N 1kVA to 3kVA
Technical Specification
Model ZP120N-1K ZP120N-1K-KS* ZP120N-2K ZP120N-2K-KS* ZP120N-3K ZP120N-3K-KS*
Power Rating 1000VA/800W 2000VA/1600W 3000VA/2400W
INPUT
Rated Voltage 220Vac/230Vac/240Vac
Voltage Tolerance 110Vac-300Vac
110Vac-300Vac (± 3 %) at 50% load
Voltage Range 165Vac-300Vac (± 3 %) at 75% load
176Vac-300Vac (± 3 %) at 100% load
Frequency Range 50Hz or 60Hz auto sensing, 45-55Hz / 54-66Hz
THDi % <5% with full load
Power Factor ≥0.99 (I/P:220V, FULL RCD LOAD)
IEC 320, C13 10A/ IEC 320, C19 16A/
Input connection Connectors
250V power cord 250V power cord
OUTPUT
Rated voltage 200VAC**/208VAC**/220VAC/230VAC/240VAC
Voltage regulation ±2%
Rated Frequency (free running) 50/60 Hz ± 0.2 Hz
Crest Ratio 3:1
Harmonic distortion < 3% THD, linear load
Output Waveform Pure Sinewave
Overload Capability 105%-110%: 1 min; 110%-125%: 30 sec ; 125%-150%: 10 Sec; >150%: 1 sec
Power factor 0,8
3 x IEC320, C13 10A/ 4 x IEC320, C13 10A/ 4 x IEC320, C13 10A/
Output connection
250V output receptacles 250V output receptacles 250V output receptacles
BATTERIES
Type Sealed lead acid battery, maintenance free
Rating 12V/7Ah Depend on 12V/7Ah Depend on 12V/7Ah Depend on
Numbers of batteries 3 external 8 external 8 external
Back-up Time (typical load) >10 minutes battery >18 minutes battery >10 minutes battero
Recharge time < 5 hours
General Characteristics
Transfer Time 0 ms
Efficiency
88% / up to 94%
(online mode / Eco-mode)
LCD Mimic Panel Status & Information: Battery Status / UPS status & alarm / Load status
Information Measurement: Battery voltage & current, Input / Output voltage, current & frequency
4 Buttons: UPS ON / UPS OFF / SELECT / ENTER for selection of UPS voltage, Bypass
Control
(enable or disable) CVCF mode
Dimensions (mm) L x D x H 145x400x220 192x460x347
Net Weight (kg) 13 7 31 13 31 13
Operating Temperature 0°C ~ 45 °C
Noise Level (@ 1m) 50dB
Humidity 0-95% (no condensing)
Support Windows family; Linux; Sun Solaris; IBM AIX;
Interface standard via Smart USB
Compaq True 64; SGI IRIX; Free BSB; HP-UX; MAC
Interface for Intelligent Slot SNMP / RS485 / AS400 Card/ ModBus
IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5,
Compliance
IEC 62040-1-1, IEC 62040-2, IEC 60950-1
* ks version are provided with battery extra charger
** Derate to 90% with 208Vac output voltage. Derate to 80% with 200Vac output voltage, derate to 60% automatically when at converter mode
Note: product specifications are subject to change without further notice.
ZP 120 N 6kVA to 10kVA
Technical Specification
Model ZP120N-6K ZP120N-6K-KS* ZP120N-10K-11 ZP120N -10K-11-KS*
Power Rating 6000VA/5400W 10000VA/9000W
INPUT
Rated Voltage 220Vac/230Vac/240Vac
Voltage Tolerance 110Vac-276Vac
110Vac-276Vac (± 3 %) at 50% load
Voltage Range
176Vac-276Vac (± 3 %) at 100% load
Frequency Range 45-55Hz / 54-66Hz
THDi % <5% with full load
Power Factor ≥0.99 (I/P:220V, FULL RCD LOAD)
OUTPUT
Rated voltage 208Vac**/220Vac/230Vac/240Vac
Voltage regulation ±1%
Rated Frequency AC Mode 50/60 Hz ± 0.05 Hz
Crest Ratio 3:1
Harmonic distortion < 0,2% THD, linear load
Output Waveform Pure Sinewave
105%-125%: 10 mins ; 125%-150%: 1 min ;
Overload Capability
150%-170%: 10 sec ; >170%: 100 ms
Parallel (with optional parallel kit) Up to 4
Power factor 0,9
BATTERY
Type Sealed lead acid battery, maintenance free
Rating 12V/7Ah 12V/9Ah
***Depend on ***Depend on
Numbers of batteries 20 20
external battery external battery
Back-up Time (typical load) > 10 minutes >10 minutes
Recharge time < 5 hours
General Characteristics
Transfer Time (Inverter to bypass) 0 ms
Efficiency (online mode / Eco-mode) >92% / >96%
Information: Battery Status / UPS status & alarm / Load status
LCD Mimic Panel Status &
Measurement: Battery voltage & current, Input / Output voltage,
Information
current & frequency
4 Buttons: UPS ON / UPS OFF / SELECT / ENTER for selection of UPS voltage,
Control
Bypass (enable or disable) CVCF mode
Dimensions (mm) LxDxH 260x560x708
Net Weight (kg) 86 34 92 37
Operating Temperature 0°C ~ 45 °C
Noise Level (@ 1m) < 50dB
Humidity 0-95% (no condensing)
Support Windows family; Linux; Sun Solaris; IBM AIX;
Interface standard via Smart USB
Compaq True 64; SGI IRIX; Free BSB; HP-UX; MAC
Interface for Intelligent Slot SNMP / RS485 / AS400 Card/ USB / ModBus
IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5,
Compliance
IEC 62040-1-1, IEC 62040-2, IEC 60950-1, ETS 300019-2-2
* ks version are provided with battery extra charger
** Derate to 90% with 208Vac output voltage, derate to 60% automatically when at converter mode
*** Optional external battery cabinet with or without battery is available upon request
Note: product specifications are subject to change without further notice.
ZP 120 N 10kVA to 20kVA
Technical Specification
Model ZP120N-10K-31 ZP120N-10K-31-KS* ZP120N-20K-31 ZP120N-20K-31-KS*
Power Rating 10000VA/9000W 20000VA/18000W
INPUT
Rated voltage 220VAC/230VAC/240VAC 1ph or 380/400/415 3ph (autosensing)
110Vac-276Vac (± 3%) at 50% load
1 phase input voltage range
176Vac-276Vac (± 3%) at 100% load
190Vac-478Vac (± 3%) at 50% load
3 phase input voltage range
322Vac-478Vac (± 3%) at 100% load
Frequency Range 45-55Hz / 54-66Hz
THDi % <5% with full load
Power Factor ≥0.99 (FULL LOAD)
OUTPUT
Rated voltage 208VAC**/220VAC/230VAC/240VAC
Voltage regulation ±1%
Rated Frequency (free running) 50/60 Hz ± 0.05 Hz
Crest Ratio 3:1
Harmonic distortion ≤ 2% THD, linear load
Output Waveform Pure Sinewave
Overload Capability 100%-110%: 5 min; 110%-130%: 1 min ; 130%-150%: 10 sec; >150%: 2 sec
Parallel (with optional parallel kit) Up to 4
Power factor 0,9
BATTERY
Type Sealed lead acid battery, maintenance free
Rating 12V/9Ah 12V/9Ah
Numbers of batteries in-built 24 + 24(optional) ***Depend on 24 + 24 ***Depend on
> 12 minutes + 12 external battery external battery
Back-up Time (typical load) > 12 minutes
minutes(optional)
Recharge time < 5 hours
General Characteristics
Transfer Time (Inverter to bypass) 0 ms
Efficiency
>93% / up to 97%
(online mode / Eco-mode)
Dimensions (mm) LxDxH 350x650x890
Net Weight (kg) 127 37 188 39
Operating Temperature 0°C ~ 45 °C
Noise Level (@ 1m) 55dB
Humidity 0-95% (no condensing)
Support Windows family; Linux; Sun Solaris; IBM AIX;
Interface standard via Smart USB
Compaq True 64; SGI IRIX; Free BSB; HP-UX; MAC
Interface for Intelligent Slot SNMP / RS485 / AS400 Card/ USB / ModBus
IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5,
Compliance
IEC 62040-1-1, IEC 62040-2, IEC 60950-1
* ks version are provided with battery extra charger
** Derate to 90% with 208Vac output voltage
*** Optional external battery cabinet with or without battery is available upon request
Note: product specifications are subject to change without further notice.
G-Tec Companies are also present worldwide with Business Partners in several countries.
G-Tec Asia Pacific Pte Ltd
60 Kaki Bukit Place, #03-05, Eunos Techpark II, Singapore 415979
Tel. +65 6555.5014 - Fax +65 6555.4105
info@[Link]
G-Tec Europe srl
Strada Marosticana, 81/13 - 36031 Povolaro (VI), Italia
Tel. +39 0444.361321 - Fax +39 0444.365191
info@[Link]
Rev. 30.12.2012
[Link]