ER-5193*
LEGACY REPORT Reissued January 1, 2007
ICC Evaluation Service, Inc. Business/Regional Office # 5360 Workman Mill Road, Whittier, California 90601 # (562) 699-0543
Regional Office # 900 Montclair Road, Suite A, Birmingham, Alabama 35213 # (205) 599-9800
www.icc-es.org Regional Office # 4051 West Flossmoor Road, Country Club Hills, Illinois 60478 # (708) 799-2305
Legacy report on the 1997 Uniform Building Code™, the 2000 International Building Code® and the 2000
International Residential Code®
DIVISION: 04—MASONRY must be between 41°F and 70°F (5°C and 25°C). Hilti, Inc.,
Section: 04081—Masonry Anchorage should be contacted regarding suitability of adhesive for which
the storage history is unknown.
HILTI HIT HY-150 ADHESIVE ANCHOR SYSTEMS 2.2.2 Threaded Steel Rods: Threaded rods must be
manufactured from steel that complies with the mechanical
HILTI, INC. property requirements of ASTM A 36; ASTM A 193, Grade B7;
5400 SOUTH 122 EAST AVENUE AISI 304-SS, Group 1 CW; or ISO 898-1, Class 5.8, as shown
TULSA, OKLAHOMA 74146 in Table 2. Specification and installation parameters for
threaded rods are noted in Table 3.
1.0 SUBJECT 2.2.3 Grouted Concrete Masonry Units: Concrete masonry
Hilti Hit HY-150 Adhesive Anchor Systems. construction must be fully grouted and have a minimum prism
strength of 1,500 psi (9.58 MPa) at the time of anchor
2.0 DESCRIPTION installation. Concrete masonry units must be Grade N, Type
2.1 General 1, in accordance with UBC Standard 21-4 or ASTM C 90-99
(IBC or IRC). Mortar must be Type N (minimum) in
The Hilti HIT HY-150 Adhesive Anchor Systems consist of accordance with Section 2103.3 of the UBC, Section 2103.7
HY-150 hybrid adhesive mortar used in conjunction with of the IBC, or Section R607 of the IRC. Grout shall comply
threaded steel rod or deformed steel reinforcement bars. This with Section 2103.4 of the UBC, Section 2103.10 of the IBC,
evaluation report recognizes the use of HIT HY-150 in fully or Section R609.1.1 of the IRC.
grouted, concrete masonry construction. Table 1 provides
general application descriptions for use of the Hilti HY-150 2.3 Design:
adhesive. The anchor system is an alternative to cast-in-place 2.3.1 General: Hilti HIT HY-150, in conjunction with
anchors described in Section 2107.1.5 of the 1997 Uniform threaded steel rod or rebar, is permitted to resist dead loads,
Building Code™ (UBC), and Section 2107 of the 2000 live loads, and short-term loads, such as those resulting from
International Building Code® (IBC). The anchor systems may wind or earthquake. The allowable tension and shear loads for
also be used where an engineered design is submitted in threaded rod in masonry are given in Tables 4, 5 and 6.
accordance with Section R301.1.2 of the 2000 International The allowable bond or masonry tension and shear values in
Residential Code® (IRC). this report must be adjusted in accordance with Figure 1 for in-
2.2 Materials: service base material temperatures in excess of 100/F (38/C).
Allowable loads for anchors subjected to combined shear
2.2.1 Hilti HIT HY-150 Adhesive: Hilti HIT HY-150 adhesive and tension forces are determined by the following formula:
is a hybrid adhesive mortar combining urethane methacrylate
resin, hardener, portland cement, and water. The resin and (Ps /Pt) + (Vs /Vt) # 1
cement are kept separate from the hardener and water by where:
means of a dual cartridge that allows for multiple uses. An Ps = Applied service tension load.
injection nozzle, equipped with an internal helical mixing Pt = Allowable service tension load.
element, is attached to the manifold, and the adhesive
components are dispensed through the injection nozzle to Vs = Applied service shear load.
ensure proper mixing of the separate adhesive components. Vt = Allowable service shear load.
The injection nozzle may be replaced to permit multiple uses 2.3.2 Short-term Loading: The allowable short-term
of the refill cartridges. The shelf life of the adhesive is at least seismic or wind shear load with threaded rod is the lower of
nine months when it is stored in a dry, dark environment. Each the steel shear strength calculated in Section 2.3.2.1 or the
cartridge is stamped with an adhesive expiration date. bond or masonry shear strength given in Tables 4, 5 and 6,
Temperatures during short-term (less than 48 hours) storage and may be increased in accordance with Section 1612.3.2 of
of the adhesive must be between 23°F and 95°F (-5°C and the UBC or Section 1605.3.2 of the IBC, for wind or
35°C). Temperatures during long-term storage of the adhesive earthquake loading conditions.
*Corrected January 2007 and Revised January 2008
ICC-ES legacy reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed as an
endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, Inc., express or implied, as to any
finding or other matter in this report, or as to any product covered by the report.
Page 1 of 5
Copyright © 2007
Page 2 of 5 ER-5193
The allowable short-term seismic or wind tension load with 2.6 Identification:
threaded rod (Tables 4, 5 and 6) is the lower of the tabulated
steel or bond or masonry strength given in the tables, and may The Hilti HY-150 adhesive is identified by labels on or in the
be increased by 331/3 percent in accordance with Section packaging that include the manufacturer’s name (Hilti),
1612.3.2 of the UBC or Section 1605.3.2 of the IBC, for short- product name, lot number, expiration date, evaluation report
term loading conditions. number (ER-5193), and installation instructions.
As an alternative, the applied loads may be reduced in 3.0 EVIDENCE SUBMITTED
accordance with Section 1612.3.1 of the UBC or Section
1605.3.1.1 of the IBC, for wind or earthquake loading. Data in accordance with the ICC-ES Acceptance Criteria for
Adhesive Anchors in Concrete and Masonry Elements (AC58),
2.3.2.1 Short-term Seismic or Wind Shear Based on dated November 2001, including test reports for the following
Steel Strength: Allowable short-term shear capacities may be optional tests: axial tension testing of single anchors,
based on steel strength and must be calculated as follows and establishing minimum edge distance, c = cmin (AC58 Test
then compared to the corresponding concrete/masonry or Series 5); axial tension testing of a group of two anchors,
bond value as described in Section 2.3.2: establishing minimum spacing distance, s = smin (AC58 Test
• Grouted concrete masonry units: Series 9); shear testing of single anchors, establishing critical
edge distance, c = ccr (AC58 Test Series 13); shear testing of
– The allowable steel shear strength is limited to A 36 single anchors, establishing minimum edge distance, c = cmin
threaded rod values, regardless of the actual type of (AC58 Test Series 14); creep testing (AC58 Test Series 17);
steel used. dampness testing (AC58 Test Series 19); freezing and thaw
2.4 Installation: testing (AC58 Test Series 20); and seismic shear and tension
testing of threaded rods (AC58 Test Series 21).
Installation of the Hilti HIT HY-150 System must conform to
the manufacturer’s published installation instructions included 4.0 FINDINGS
in each unit package, and the requirements of this evaluation
report. Installation parameters are summarized further in That the Hilti HY-150 Adhesive Anchor Systems described
Tables 2 and 3, and the corresponding load data tables. Holes in this report comply with the 1997 Uniform Building
for installation of the threaded rod or reinforcement bar must Code™ (UBC), the 2000 International Building Code®
be drilled using a drill that is set in roto-hammer mode and that (IBC), and the 2000 International Residential Code® (IRC),
has a carbide-tipped bit that complies with ANSI B212.15- subject to the following conditions:
1994. Holes must be cleaned of dust and debris, using a wire
brush and compressed air as required to remove particulate 4.1 The HIT HY-150 Adhesive Anchor Systems with
debris and to achieve a relatively dust-free surface. Holes are threaded rod are permitted to be used to resist dead
permitted to be damp, but all standing water must be removed loads, live loads and short-term loads, such as
in accordance with Section 4.11 of this evaluation report. those resulting from wind or earthquake forces.
The dual cartridge is self-opening, and the adhesive is 4.2 When anchors are used to resist short-term loads,
dispensed through an injection nozzle equipped with an such as wind or seismic, allowable loads must be
internal helical mixing element that is attached to the cartridge calculated in accordance with Section 2.3.2 of this
manifold to ensure proper mixing of the components. Material report.
from the first two “trigger pulls” must be discarded to ensure
that only properly mixed product is used. The injection nozzle 4.3 The anchors are installed in accordance with the
may be replaced to permit multiple uses of the cartridge. The manufacturer’s instructions and this report.
injection nozzle must always be equipped with the internal
4.4 The HIT HY-150 Adhesive Anchor Systems are
helical mixing element. The injection nozzle must be as
installed in holes predrilled using a carbide-tipped
manufactured by Hilti for the HIT HY-150 Adhesive Anchor
System. Holes are filled approximately two-thirds full with the masonry drill bit manufactured within the range of
mixed adhesive, injecting from the bottom of the hole towards the maximum and minimum dimensions of ANSI
the top. The threaded rod or deformed bar is twisted as it is B212.15-1994.
inserted into the hole to the required embedment depth. The 4.5 Special inspection in accordance with Section 2.5 of
anchor position may be adjusted only during the gel time this report is provided for all anchor installations.
shown in Table 3. Anchors are permitted to be loaded to the
design load only after the cure time shown in Table 3 has 4.6 Calculations and details demonstrating compliance
passed. See Section 4.12 of this evaluation report for with this report must be submitted to the building
limitations on base-material temperature during installation. official for approval.
2.5 Special Inspection: 4.7 Anchors are not permitted for use in conjunction
Adhesive anchor installations require special inspection in with fire-resistive construction. Exceptions are:
accordance with Section 1701 of the UBC or Section 1704 of • Anchors resist wind or seismic loading only.
the IBC. The special inspector must record product description
(including product name), adhesive expiration date, masonry • For other than wind or seismic loading, special
type and strength, anchor diameter and steel grade, consideration is given to fire exposure conditions.
compliance of the drill bit with this report, hole diameter and
location, cleanliness of hole and anchor, adhesive application, 4.8 Adhesive anchors may be used to resist tension and
and anchor embedment. Additionally, the special inspector shear forces in wall installations only if
must state in the report supplied to the building official whether consideration is given to the effects of elevated
the anchor installation is in accordance with the temperature conditions on anchor performance.
manufacturer’s published instructions and this evaluation Figure 1 describes load reduction factors for
report. elevated temperatures.
Page 3 of 5 ER-5193
4.9 Since an ICC-ES acceptance criteria for evaluating achieve an equivalent damp surface condition prior
data to determine the performance of adhesive to anchor installation.
anchors subjected to fatigue or shock loading is
unavailable at this time, the use of these anchors 4.13 HIT HY-150 may be used in base materials having
under these conditions is beyond the scope of this interior temperatures between 23°F (-5°C) and 110°F
report. (43°C) at the time of installation. Installation of HIT
HY-150 in base materials having interior
4.10 Since an ICC-ES acceptance criteria for evaluating temperatures outside this range is beyond the scope
the performance of adhesive anchors in cracked of this report. The temperature of the HY-150
masonry is unavailable at this time, the use of adhesive must be between 41°F (5°C) and 95°F
anchors is limited to installation in uncracked (35°C) at the time of installation.
masonry. Cracking occurs when ft > fr due to service
loads or deformations. 4.14 When anchors are located where the interior base-
material temperature may exceed 100°F (38°C),
4.11 Use of the HIT HY-150 Adhesive Anchor System in allowable tension and shear loads in this report
conjunction with unprotected carbon steel threaded must be adjusted for in-service temperatures in
rods is limited to interior exposure. Installations accordance with Figure 1. The use of HIT HY-150 in
exposed to severe, moderate and negligible exterior base materials having interior temperatures
weathering conditions, as defined in Figure 21-1-1 of exceeding 248°F (120°C) during their service life is
UBC Standard 21-1 (Table 1 of ASTM C 62-97a), are beyond the scope of this report.
permitted where stainless steel (AISI 304 or 316 SS)
threaded rod anchors are used. 4.15 The HIT HY-150 adhesive is manufactured by Hilti
GmbH at their facilities in Kaufering, Germany, with
4.12 Standing water must be removed from drilled holes. quality control inspection by Underwriters
In applications where the masonry has been Laboratories Inc. (AA-668).
exposed to water for extended periods, drilled holes
must be blown dry with oil-free compressed air for This report is subjection to re-examination in one year.
a minimum of one minute, or otherwise prepared to
TABLE1—STEEL SPECIFICATIONS FOR ROD, NUT AND WASHER
ALL-THREAD ROD NUT SPECIFICATION WASHER SPECIFICATION
Description Specification fy (ksi) fu (ksi)
Standard HAS Rod ASTM A 36 36.0 58.0 ASTM A 563, Grade A ANSI B18.22.1, Type A, plain
Standard HAS-E Rod ISO 898, Class 5.8 58.0 72.5 ASTM A 563, Grade DH ASTM F 436
Super HAS Rod ASTM A 193 B7 105.0 125.0 ASTM A 563, Grade DH ASTM F 436
304/316 Stainless
65.0 100.0
HAS Rod (3/8" - 5/8")
ASTM F 593, CW ASTM F 594, Alloy Group 1 ANSI B18.22.1, Type A, plain
304/316 Stainless
45.0 85.0
HAS Rod (3/4" - 11/4")
For SI: 1 inch = 25.4 mm, 1 psi = 6.894 kPa.
TABLE 2—SPECIFICATIONS FOR INSTALLATION OF THREADED RODS IN CONCRETE USING HILTI HIT HY-150 ADHESIVE
THREADED ROD DIAMETER
11/4
3 1 5 3 7
PROPERTY /8 inch /2 inch /8 inch /4 inch /8 inch 1 inch inches
Anom = Nominal area of threaded rod (inch2) 0.1105 0.1963 0.3068 0.4418 0.6013 0.7854 1.2272
7 9 11 13 15
BD = Nominal bit diameter (inches) /16 /16 /16 /16 /16 11/16 11/2
Embedment # Standard 15 20 50 105 125 165 280
T = Maximum torque (ft.-lbf)
Embedment > Standard 18 30 75 150 175 235 400
Standard embedment depth (inches) 31/2 41/4 5 65/8 71/2 81/4 12
For SI: 1 inch = 25.4 mm, 1 ft.-lb. = 1.4 N-m, 1 inch2 = 645 mm2.
TABLE 3—HILTI, INC.’S, RECOMMENDED GEL AND CURE TIMES FOR HILTI HIT HY-150 ADHESIVE
MINIMUM BASE-MATERIAL TEMPERATURE GEL TIME CURE TIME
23°F 25 minutes 6 hours
32°F 18 minutes 3 hours
41°F 13 minutes 90 minutes
68°F 5 minutes 50 minutes
86°F 4 minutes 40 minutes
104°F 2 minutes 30 minutes
For SI: t°C = (t°F - 32)/1.8.
Page 4 of 5 ER-5193
TABLE 4—ALLOWABLE TENSION AND SHEAR VALUES FOR THREADED ROD INSTALLED USING HILTI
HIT HY-150 ADHESIVE IN GROUT-FILLED CONCRETE MASONRY CONSTRUCTION (pounds)1,2,3,4,5,8,9,10
PARAMETER VALUES
3 1 5 3
Anchor diameter (inches) /8 /2 /8 /4
5 1 1
Embedment (inches) 3 /2 4 /4 5 65/8
Minimum anchor spacing, smin (inches) 7 81/2 10 131/4
7 7 7
Load direction Tension Shear Tension Shear Tension Shear Tension Shear7
6
4-inch edge distance, c min 1,610 1,610 1,610 1,610
6
1,240 1,430 1,810 2,995
Edge distance $ 12 inches 1,875 3,335 4,495 4,495
For SI: 1 inch = 25.4 mm, 1 lbf = 4.48 N.
1
Anchors are limited to one per masonry cell.
2
Anchors may be installed at any location in the face of the masonry wall (cell, web, head joint, bed joint, etc.).
3
Allowable load values are for use in any masonry construction complying with Section 2.2.3 of this report.
4
When anchors are used to resist short-term loads, allowable loads must be calculated in accordance with Section 2.3.2 of this report.
5
Embedment depth is measured from the outside face of the masonry.
6
Edge distances of less than 4 inches are beyond the scope of this report. Linear interpolation for edge distances between 4 inches and 12 inches
is allowed.
7
Allowable extension loads must be the lesser of the adjusted masonry or bond tabulated steel tension values given in Table 6.
8
Allowable shear loads must be the lesser of the adjusted masonry or bond tabulated values and the steel shear values given in Table 6.
9
The tabulated allowable loads have been calculated based on safety factor of 5.0. These values may be increased by 25% (safety factor of 4)
under the UBC only.
10
Masonry thickness must be equal to or greater than 1.5 times the anchor embedment depth.
EXCEPTION: The 3/4-inch-diameter anchors may be installed in minimum nominal 8-inch-thick masonry.
TABLE 5—ALLOWABLE LOADS FOR SILL PLATES AND OTHER ITEMS ATTACHED TO TOPS OF
GROUT-FILLED MASONRY WALLS AT MINIMUM EDGE DISTANCES AND USING HILTI HY-150 ADHESIVE1,2,3,4,5
SHEAR (pounds)
EMBEDMENT
ANCHOR EDGE DISTANCE Load Applied
DEPTH TENSION (pounds) Load Applied
DIAMETER (inch) (inches) Perpendicular to
(inches) Parallel to Edge
Edge
1
13/4 1,395 560 1,425
/2 41/4
23/4 1,795 1,110 2,085
5
13/4 1,840 705 1,800
/8 5
23/4 2,035 1,110 3,070
For SI: 1 inch = 25.4 mm, 1 lbf = 4.45 N, 1 psi = 6.89 kPa.
1
Loads in this table are for threaded rod complying with Section 2.2.2 installed in the masonry at the edge distance listed in this table. No reductions
for edge distance are required when anchors are installed with the minimum edge distance specified in the table. Capacity of attached sill plate
or other material to resist loads in this table must comply with the applicable code.
2
Edge distances are given in this table. Anchor spacing shall conform to the dimensions given in Table 4.
3
When anchors are used to resist short-term loads, allowable loads should be calculated in accordance with Section 2.3.2 of this report.
4
Masonry thickness must be equal to or greater than 1.5 times the embedment depth.
5
The tabulated values are for anchors installed in any masonry complying with Section 2.2.3 of this report.
TABLE 6—ALLOWABLE TENSION AND SHEAR LOADS FOR THREADED RODS1
ANCHOR ALLOWABLE TENSION LOAD BASED ON STEEL ALLOWABLE SHEAR LOAD BASED ON STEEL
DIAMETER STRENGTH STRENGTH
(inches) (pounds) (pounds)
ASTM ISO 898 ASTM AISI ASTM ISO 898 ASTM AISI
A 36 Class 5.8 A 193 304/316 A 36 Class 5.8 A 193 304/316
Grade B7 SS Grade B7 SS
3
/8 2,115 2,640 4,555 3,645 1,090 1,360 2,345 1,875
1
/2 3,775 4,700 8,100 6,480 1,935 2,420 4,170 3,335
5
/8 5,870 7,340 12,655 10,125 3,025 3,780 6,520 5,215
3
/4 8,455 10,570 18,255 12,390 4,355 5,445 9,390 6,385
7
/8 11,510 14,385 24,805 16,865 5,930 7,410 12,780 8,690
1 15,030 18,790 32,400 22,030 7,745 9,680 16,690 11,350
11/4 23,490 29,360 50,620 34,425 12,100 15,125 26,080 17,735
For SI: 1 inch = 25.4 mm, 1 lbf = 4.45 N, 1 psi = 6,89 kPa.
1
When anchors are used to resist short-term loads, allowable loads must be calculated in accordance with Section 2.3.2 of this report.
Page 5 of 5 ER-5193
For SI: t/C = (t/F – 32)/1.8.
FIGURE 1—INFLUENCE OF BASE-MATERIAL TEMPERATURE ON THE TENSION OR SHEAR BOND CAPACITY
OF THE HILTI HY-150 ADHESIVE ANCHOR FOR INSTALLATIONS IN BASE MATERIAL AT 23°F OR GREATER