Document # RRPL-SG3-P13-ELE-QAP-10
D* M C
1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11.
IS-2062 Manufacturer
d) Mechanical Properties Mechanical/ Test V
Major Random IS 1079 √ P
Physical Certificate
(MTC)
a) Chemical composition IS – 613 (Copper) / V
Major Chemical Random IS - 613 / IS 5082 MTC/TR √ P
(Copper Purity) IS 5082(Al)
b) Check for mechanical
property (Bend test, IS – 613 (Copper) / V
Major Mechanical Random IS - 613 / IS 5082 MTC/TR √ P
Tensile strength, % IS 5082(Al)
1.3
Elongation)
Copper
Sampling 1
/Aluminium IS – 613(Copper) / V
c) Electrical conductivity Major Electrical No. per lot IS - 613 / IS 5082 MTC/TR √ P
(Busbar): IS 5082(Al)
per size
hard
d) Dimension check (Width Measuremen IS - 613 / IS 5082 / V
Major 100% Approved. Drawings ---do--- - P
& Thickness) t Approved Drg.
Free from blisters,
e) Visual check (Surface slivers, scale, fins, V
Major Visual 100% IS - 613 / IS 5082 ---do--- - P
defects) spills, cracks
and other defects.
a) Routine tests
1.4 Control Wires Manufacturer V
(Conductor resistance test Major Electrical 100% IS: 694 - 2010 IS: 694 - 2010 √ P
Type: PVC FRLS TC/BOM
& HV Test)
As per IS: 694 Manufacturer V
b) Acceptance Tests Major Electrical IS: 694 - 2010 IS: 694 - 2010 - P
- 2010 TC/BOM
a) Make, Rating, and Visual Approved Manufacturer V
1.5 Fuse & Fuse Base Major Visual 100% Approved Document - P
Checks. Document TC/BOM/COC
MCB / RCCB/
a) Mechanical operation V
1.6 MPCB (As Major Mechanical 100% IEC 60898 IEC 62271-100 ---do--- - P During Final Inspection
(ON / OFF)
applicable)
b) Dielectric withstand V
Major Electrical 100% IEC 60898 IEC 62271-100 ---do--- - P During final inspection
(2kV for 1 min)
Gaskets Smooth & free from Smooth & free from Manufacturer V
1.10 a) Surface finish Major Visual 100% - P
surface defects surface defects TC/COC
Lugs & Terminal Manufacturer Catalogue Free from cracks & Incoming QC -
1.11 a) Appearance Major Visual 100% - P
blocks / PS harmful damages record /COC
Shall be suitable to
Random Manufacturer's connect the size of
b) Dimensions, Type & Incoming QC -
Major Visual sample of Specification/ the wires - P
Model no. record /COC
each type Catalogue/ AD mentioned in
Approved document
Manufacturer The switches shall
V
1.12 Selector Switches a) Physical Checks Major Electrical 100% specifications /Approved be free from any --do-- - P
Document Physical Damages
b) Functional/Operational Approved Manufacturer V
Major Physical 100% Approved Documents TC/RTC/BOM - P During Final Inspection
Checks Documents
Rating, Type & Major Electrical 100% Approved drawing Approved Drawing Supplier TC
Functionality as Per Test
V
1.23 Roof Bushing Approved Scheme √ P
n) Primary Injection Test IEC 62271-200 Approved Drawing Routine test Internal 100% , Customer
with 100A AC for checking report witness 10%
Major Electrical 100% - P W
metering & Protection
circuit
IEC 62271-200 Approved Drawing Routine test Internal 100% , Customer
o) Functional Test
Major Electrical 100% report - P W witness 10%
including logic check
p) CT/PT Terminal IEC 62271-200 Approved Drawing Routine test Internal 100% , Customer
Major Electrical 100% report - P W witness 10%
marking, Ratio check
Approved Drawing Approved Drawing Routine test Customer witness 10%
report
q) Test on Galvanized
structure, Skid appearance Major Mechanical Random - P W
& DFT (if applicable)