Pneumatic and Hydraulic Symbols Guide
Pneumatic and Hydraulic Symbols Guide
PNEUMATIC SYMBOLS
ACTUATORS
Table 1 - Actuator Symbols.
Double-acting cylinder.
Double-acting cylinder (with end damping)
course, without adjustment).
Double-acting cylinder (with end cushioning)
adjustable course)
Double cylinder.
Oscillator.
Pneumatic Motor.
Hydraulic Motor.
DIRECTIONAL VALVES
Valves are elements that control, regulate, direct, and block the flow in a circuit.
The understanding of its symbolism is the basic premise for the analysis of pneumatic and hydraulic diagrams.
electro-hydraulics and electropneumatics. They are categorized into five major groups, according to their function:
a) directional;
b) of pressure;
c) of flow (flow);
d) of blocking;
e) of closure.
Among these, the main group is that of directional valves, that is, valves that
interfere in the trajectory of the flow, diverting it to where it is most convenient in a
certain moment. We will present in the next items, the usual symbols, remembering
that the description of other symbols and additional definitions should be consulted in the standards
ABNT NBR 8896 and following, DIN 24300 and ISO 1219.
IDENTIFICATION OF CONNECTIONS
NOTE: When specifying the symbol of a directional valve, they must be perfectly
defined:
The number of ports of the valve;
The number of management positions;
The normal position of the valve (when applicable);
Method of actuation (both for switching and for returning to the normal position).
The change between the positions of a directional valve depends on external actuation, which
the indication is incorporated adjacent to the valve symbol. These actuations are often grouped according to their
type in: muscular action, mechanical action, pressure, electric or a combination between these (Table 4).
Lever.
Pedal.
Stepper motor.
Pneumatic flow.
Hydraulic flow.
Compressor.
Hydraulic pump.
5
Accumulator (generic).
ELECTRICAL SYMBOLS
The conventions presented below are based on the DIN 40713 and DIN standards.
40718, already mentioned, and are commonly used in LAB-SIM for the subjects related to the area
of automation. The illustrations presented here are part of a 'bank' of drawings, being
made available via the internet, on the homepage of the automation laboratory, for download.
SHEETFORELECTRO-ELECTRONICCIRCUITANDCONNECTIONDIAGRAMS
A3 sheet (297mm x 420mm), standardized and with company logo, preferably with
15 upper divisions (28 mm/division) where the column address should be placed (figure 1).
6
DIAGRAMCREATION SHEETFORFUTUREEXPANSIONS
The creation of the diagrams and other information Provide blank sheets during the project
it must be done on standard sulfite paper, with pencil or (addressed) in places where there may be
pencil avoiding the use of rulers, templates or others future implementation. These blank sheets must
materials, in order to carry out this work in the most counter in the bottom left corner the note: 'SHEET
practical and quick. The final documentation may be in RESERVED FOR IMPLEMENTATION
vegetal paper or plotted sulfite. FUTURE. When proceeding this way, the sheet
the front must have the following on its right side
SYMBOLISM observation A NEXT LEAF ESTA
RESERVED FOR IMPLEMENTATION
The dimensions and shape of the electro-symbols FUTURE.
electronics must meet the requirements of the DIN standards
40713 and 40718. Tables 4.1 and 4.3 present the IDENTIFICATION OFCOMPONENTS
most commonly used symbols in electro-electronic circuits.
Contactors, fuses, transformers, power supplies
WRITING AND TECHNICAL LINES rectifiers and all and any electrical components
Electronics must be identified by uppercase letters
The technical lines and the characters used in the followed by the number or code of the reference sector
the preparation of electro-electronic schemes must meet (column). In practice, it is found that up to 9 elements
A
e,hB
sdN
trT
N
adfnoaN
B
sdnoR
a3B
t048iR
s2048tpircserpeht can be addressed in the same column. The order
respectively. the numeric value of the least significant digit in this encoding is
from bottom to top.
LEGEND
TERMINALSANDCONDUCTORSCONNECTEDTOC.L.P's
They must be observed, at a minimum:
In the top right corner, the drawing number. The dimensions and shape of the electro symbols
Electronics must comply with the prescriptions of the DIN standards.
Count the name of the Project. 40713 and 40718. The respective addresses must be
Generic content of the sheet. identified (byte number of the PLC or its module)
of expansion). The terminals and conductors of the branches of
LINESOFFORCEANDCOMMAND Voltage feeding is identified as follows:
LETTERSFORIDENTIFICATIONOFCOMPONENTS
Table 6 shows the letters used in the identification of the main circuit components.
REFERENCESECTORS POSITIONOFCOMPONENTANNOTATION
The electrical schematics are encoded from The code annotation position of the
of a "reference sector", which is provided by the address
components must be:
from the respective column. Each page contains 15 sectors
components in the horizontal part
references, numbered from left to right,
superior
in ascending order and having numerical continuity
in the remaining part of the scheme, also having, explicit, the contactor/relay coils, on the side
address 'where it comes from' and 'where it goes'. bottom right
sensors/buttons on the left side;
IDENTIFICATION OFCONTACTORSAND RELAYS solenoids of the solenoid valves, on the side
lower right;
All contactors and relays must have the electrical/electronic modules, in the middle of
indication, below your drive coil module
respective, the address of their closing contacts
(NA) and openers (NF). Note: The position of the annotation of the nominal value of
IDENTIFICATIONOFTHECONDUCTORGAUGE fuses, disconnection switches, range of action of
thermal relays, current limiters and circuit breakers
Every conductor must have its gauge indicated on the It should be right below the component code.
diagram, preceded by the gauge symbol: "#".
8
EXAMPLES