SCHEDULE OF LOADS:
CKT NO. DESCRIPTION L.O. C.O. WATTS VOLTS AMP. SIZE OF
BREAKER
SIZE OF WIRES & CODUITS LEGEND:
12 WATTS CIRCULAR LIGHTING
CKT - 1 GROUND FLOOR LIGHTING 10 1,000 220 V 4.55
INTERNAL CONSEALED PIN LIGHT
CKT - 2 GROUND FLOOR LIGHTING 12 1,200 220 V 5.45
15 AMP. / AT 2.0 mm.2 TW WIRE - 13 MM. DIA. PVC CONDUIT EXTERNAL DOWN LIGHT
CKT - 3 SECOND FLOOR LIGHTING 7 700 220 V 3.18
CKT - 4 SECOND FLOOR LIGHTING 7 700 220 V 3.18
WALL LIGHTING OUTLET
CKT - 5 GROUND FLOOR POWER 6 1,080 220 V 4.91 GARDEN SPOT LIGHT
CKT - 6 GROUND FLOOR POWER 7 1,260 220 V 5.73
20 AMP. / AT 3.5 mm.2 TW WIRE - 20 MM. DIA. PVC CONDUIT CONVINIENCE OUTLET
CKT - 7 SECOND FLOOR POWER 5 900 220 V 4.09
WP
WATERPROOF CONV. OUTLET
CKT - 8 SECOND FLOOR POWER 6 1,080 220 V 4.91
ACU
AIRCON OUTLET
CKT - 9 M. BEDROOM SPLIT-TYPE ACU 1 2,000 220 V 9.09
CKT - 10 BEDROOM 1 ACU POWER 1.0Hp 1 1,200 220 V 5.45 WP WATER PUMP OUTLET
CKT - 11 BEDROOM 2 ACU POWER 1.0Hp 1 1,200 220 V 5.45 WATER HEATER OUTLET
WH
CKT - 12 GROUND FLR. T&B HOT WATER 1 3,800 220 V 17.27 30 AMP. / AT 5.5 mm.2 TW WIRE - 20 MM. DIA. PVC CONDUIT
H HOOD OUTLET
CKT - 13 SECOND FLR. T&B HOT WATER 1 3,800 220 V 17.27
IC INDUCTION COOKER OUTLET
CKT - 14 SECOND FLR. T&B HOT WATER 1 3,800 220 V 17.27
CKT - 15 INDUCTION COOKER OUTLET 1 2,000 220 V 9.09
Sa SINGLE GANG WALL SWICTH
SPARE Sab DOUGLE GANG WALL SWITCH
SPARE Sabc THREE GANG WALL SWITCH
T O T A L 36 32 25,720 S3w THREE WAY SWITCH
COMPUTATION OF LOADS: PB
MAIN PANEL BOARD
TOTAL WATTS: 25,780 X .80 DEMAND FACTOR = 20,624 WATTS CKT - 5 CIRCUIT LINE TO PANEL BOARD
20,624 WATTS / 220 VOLTS = 93.74 AMPERES
LIGTHING CIRCUIT LOOP LINE
USE: 125 AMP. MAIN BREAKER
38 mm.2 THW COPPER - 30 mm. DIA. RIGID STEEL CONDUIT POWER CIRCUIT LOOP LINE
SWITCH TO LIGHT LINE
SERVICE ENTRANCE
ELECTRICAL WIRE
SERVICE ENTRANCE CABLE
GENERAL NOTES:
38 mm.2 THW COPPER
30 mm. DIA. RIGID STEEL CONDUIT
1. ALL ELECTRICAL WORKS SHALL BE ACCORDING TO THE LATEST EDITION OF PHILIPPINE
ELECTRICAL CODE AND RULES AND REGULATIONS OF THE AUTHORITY CONCERNED AND
ELECTRICAL COMPANY.
2. ALL ELECTRICAL MATERIALS SHALL BE NEW AND APPROVED TYPE FOR BOTH LOCATION 125 AMP.
AND PURPOSE INTENDED.
3. THE TYPE OF POWER SUPPLY ON THE BUILDING SHALL BE 220V/60HZ ,SINGLE PHASE
CKT 1 CKT 2
15 AMP. 15 AMP.
4. ALL WIRES SHALL BE COPPER, SOFT-DRAWM AND ANNEALED, SHALL BE 98% CKT 4
CKT 3
CONDUCTIVITY. 15 AMP. 15 AMP.
CKT 5 CKT 6
5. ALL WIRES AND CABLES SHALL COMPLY WITH THE REQUIREMENTS AS TO THE PARTICULAR 20 AMP. 20 AMP.
USAGE. CKT 7 CKT 8
20 AMP. 20 AMP.
6. WIRES AND CABLES SHALL BE MOISTURE AND HEAT RESISTANT RUBBER OR THERMOPLASTIC
CKT 9 CKT 10
INSULATED. 30 AMP. 30 AMP.
CKT 11 CKT 12
7. ALL WIRING SHALL BE DONE IN RIGID STEEL CONDUIT AND PVC PIPES. 30 AMP. 30 AMP.
CKT 13 CKT 14
8. PROVIDE PULL BOXES IF NECESSARY EVEN NOT INDICATED IN THE PLAN. 30 AMP. 30 AMP.
CKT 15 CKT 16
9. WALL SWITCHES SHALL BE RATED AT 15 AMP., 220 VOLTS ONE WAY OR AS REQUIRED. 30 AMP. 30 AMP.
RECEPTACLES OUTLET SHALL BE DUPLEX RATED 10 AMP. 220 VOLTS. SPARE SPARE
10. PROVIDE INDIVIDUAL CIRCUIT BREAKER, SAFETY SWITCHES AND DISCONNECT SWITCHES
WHERE INDICATED. VOLTAGE RATING SHALL BE SUITABLE IN EACH CASE OF SERVICE
APPLICATION.
11. ALL ELECTRICAL INSTALLATION SHALL BE SUPERVISED BY LICENSED ELECTRICAL
ENGINEER OR MASTER ELECTRICIAN.
SINGLE LINE DIAGRAM
DESIGNED BY: REG NO. SEAL PROJECT TITLE: SIGNED BY: REVISION: SHEET NO.
ALVIN R. CASILAC PTR NO.
RAZEL JOY P. CANIESO MIDTERM PROJECT: PROPOSED 2 STOREY RESIDENTIAL LIAM JAKE L. NARISMA
DATE: BUILDING E-3
BACHELOR OF SCIENCE IN COMPUTER ENGINEERING PLACE: LOCATION: LABOGON, SLIDING HILLS, MANDAUE CITY ENGINEER