Vessel Samco Taiga ü New Avtivity/Hazard
Date of Assessment 21/02/2013 Place of Assessment At sea
New Activity Pressure testing of Fire hose
New Hazard Hose parting
CONSEQUENCE SEVERITY OF HARM
LIKELIHOOD SLIGHT HARM MODERATE HARM EXTREME HARM
Very Unlikely (1) Very Low Risk (1) Very Low Risk (1) High Risk (4)
Unlikely (2) Very Low Risk (1) Medium Risk (3) Very High Risk (5)
Likely (3) Low Risk (2) High Risk (4) Very High Risk (5)
Very Likely (4) Low Risk (2) Very High Risk (5) Very High Risk (5)
Initial Risk
SEVERITY LIKELIHOOD RISK LEVEL
Moderate harm Very Likely Very High Risk (5)
Additional Control Measures
[Link] of hoses every month.
[Link] test hoses every 3 months.
[Link] strong enough for the working capacity of fire pump.
[Link] approved type hoses to be used.
[Link] clear off sharp objects.
[Link] clear off chemicals & adhesives.
[Link] at clean & dry places.
[Link] with fresh water after use/pressure testing.
Residual Risk
SEVERITY LIKELIHOOD RISK LEVEL
Slight Harm Unlikely Very Low Risk (1)
Vessel Samco Taiga ü New Avtivity/Hazard
Date of Assessment 21/02/2013 Place of Assessment At sea
New Activity Pressure testing of Fire hose
New Hazard Nozzle coming off the hose
CONSEQUENCE SEVERITY OF HARM
LIKELIHOOD SLIGHT HARM MODERATE HARM EXTREME HARM
Very Unlikely (1) Very Low Risk (1) Very Low Risk (1) High Risk (4)
Unlikely (2) Very Low Risk (1) Medium Risk (3) Very High Risk (5)
Likely (3) Low Risk (2) High Risk (4) Very High Risk (5)
Very Likely (4) Low Risk (2) Very High Risk (5) Very High Risk (5)
Initial Risk
SEVERITY LIKELIHOOD RISK LEVEL
Moderate harm Likely High Risk (4)
Additional Control Measures
[Link] Inspection of nozzles.
[Link] test hoses every 3 months.
[Link] of nozzles.
[Link] approved type to be used.
[Link] the nozzle is properly attached with the hose coupling.
[Link] coupling & nozzle have appropriate size of rubber washer.
Residual Risk
SEVERITY LIKELIHOOD RISK LEVEL
Slight Harm Very Unlikely Very Low Risk (1)
Vessel Samco Taiga ü New Avtivity/Hazard
Date of Assessment 21/02/2013 Place of Assessment At sea
New Activity Pressure testing of Fire hose
New Hazard Coupling slipping off the hose
CONSEQUENCE SEVERITY OF HARM
LIKELIHOOD SLIGHT HARM MODERATE HARM EXTREME HARM
Very Unlikely (1) Very Low Risk (1) Very Low Risk (1) High Risk (4)
Unlikely (2) Very Low Risk (1) Medium Risk (3) Very High Risk (5)
Likely (3) Low Risk (2) High Risk (4) Very High Risk (5)
Very Likely (4) Low Risk (2) Very High Risk (5) Very High Risk (5)
Initial Risk
SEVERITY LIKELIHOOD RISK LEVEL
Moderate harm Unlikely Medium Risk (3)
Additional Control Measures
[Link] coupling to hose with copper wire.
[Link] testing of hoses.
[Link] of couplings.
[Link] of couplings should be raised as per the size of hoses.
[Link] approved types of couplings are to be used.
[Link] with fresh water after use/pressure testing.
Residual Risk
SEVERITY LIKELIHOOD RISK LEVEL
Slight Harm Very Unlikely Very Low Risk (1)
Vessel Samco Taiga ü New Avtivity/Hazard
Date of Assessment 21/02/2013 Place of Assessment At sea
New Activity Pressure testing of Fire hose
New Hazard Hose slipping from hand and lashing around
CONSEQUENCE SEVERITY OF HARM
LIKELIHOOD SLIGHT HARM MODERATE HARM EXTREME HARM
Very Unlikely (1) Very Low Risk (1) Very Low Risk (1) High Risk (4)
Unlikely (2) Very Low Risk (1) Medium Risk (3) Very High Risk (5)
Likely (3) Low Risk (2) High Risk (4) Very High Risk (5)
Very Likely (4) Low Risk (2) Very High Risk (5) Very High Risk (5)
Initial Risk
SEVERITY LIKELIHOOD RISK LEVEL
Moderate harm Very Likely Very High Risk (5)
Additional Control Measures
[Link] carried out for hose handling.
[Link] PPE to be used.
[Link] person to always assist the hose handler.
[Link] person to be always stands by at the hydrant.
[Link] on the hose line to be increased gradually.
Residual Risk
SEVERITY LIKELIHOOD RISK LEVEL
Slight Harm Unlikely Very Low Risk (1)
Vessel Samco Taiga ü New Avtivity/Hazard
Date of Assessment 21/02/2013 Place of Assessment At sea
New Activity Pressure testing of Fire hose
New Hazard Injury to personnel
CONSEQUENCE SEVERITY OF HARM
LIKELIHOOD SLIGHT HARM MODERATE HARM EXTREME HARM
Very Unlikely (1) Very Low Risk (1) Very Low Risk (1) High Risk (4)
Unlikely (2) Very Low Risk (1) Medium Risk (3) Very High Risk (5)
Likely (3) Low Risk (2) High Risk (4) Very High Risk (5)
Very Likely (4) Low Risk (2) Very High Risk (5) Very High Risk (5)
Initial Risk
SEVERITY LIKELIHOOD RISK LEVEL
Moderate harm Likely High Risk (4)
Additional Control Measures
[Link] Training carried out for hose handling.
[Link] PPE to be used.
[Link] person to always assist the hose handler.
[Link] person to be always stands by at the hydrant.
[Link] valve to be opened slowly.
[Link] fire pump is running before opening the valve.
[Link] additional hydrants are kept open to reduce pressure.
Residual Risk
SEVERITY LIKELIHOOD RISK LEVEL
Slight Harm Unlikely Very Low Risk (1)
Vessel Samco Taiga ü New Avtivity/Hazard
Date of Assessment 21/02/2013 Place of Assessment At sea
New Activity Pressure testing of Fire hose
New Hazard Possible back lash during starting the water
CONSEQUENCE SEVERITY OF HARM
LIKELIHOOD SLIGHT HARM MODERATE HARM EXTREME HARM
Very Unlikely (1) Very Low Risk (1) Very Low Risk (1) High Risk (4)
Unlikely (2) Very Low Risk (1) Medium Risk (3) Very High Risk (5)
Likely (3) Low Risk (2) High Risk (4) Very High Risk (5)
Very Likely (4) Low Risk (2) Very High Risk (5) Very High Risk (5)
Initial Risk
SEVERITY LIKELIHOOD RISK LEVEL
Moderate harm Unlikely Medium Risk (3)
Additional Control Measures
[Link] Training carried out for hose handling.
[Link] PPE to be used.
[Link] person to always assist the hose handler.
[Link] person to be always stands by at the hydrant.
[Link] valve to be opened slowly.
[Link] fire pump is running before opening the valve.
[Link] additional hydrants are kept open to reduce pressure.
Residual Risk
SEVERITY LIKELIHOOD RISK LEVEL
Slight Harm Very Unlikely Very Low Risk (1)