Generator Health Check Report 2025

The health check report for a Stamford alternator (DG-1) was conducted on August 22, 2025, with all electrical test results indicating normal working conditions. Key measurements included insulation resistance values and resistance readings across various components, all within acceptable ranges. The report concludes with successful no-load and load tests, confirming the alternator's operational integrity.

Uploaded by

kaleempasha1989
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
58 views1 page

Generator Health Check Report 2025

The health check report for a Stamford alternator (DG-1) was conducted on August 22, 2025, with all electrical test results indicating normal working conditions. Key measurements included insulation resistance values and resistance readings across various components, all within acceptable ranges. The report concludes with successful no-load and load tests, confirming the alternator's operational integrity.

Uploaded by

kaleempasha1989
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

SILICON ELECTRICAL HUB

SERVICES, SPARES & RE-WINIDNG, FOR GENERATOR, MOTOR & HIRING OF DG SET
Off: 29, 2nd Cross, Raja Ram Mohan Roy Extension, Opp. Central Įibrary Double Road,
Bangalore- 560027, GSĪ: 29DPRPK7860B1ZE,
Email: siliconelectricalhub@[Link], Ph no: 98457 07226, 88847 07226

HEALTH CHECK REPORT


DATE: 25-08-2025
PURCHASE ORDER NUMBER:
DATE OF VISIT:22-08-2025 M/C. TYPE: ALTERNATOR
CUSTOMER: SITE:
CONTACT PERSON: NUMBER:
NAME PLATE DETAILS
MAKE : STAMFORD ALTERNATOR DG-1 M/C. NO: N10117960
FRAME : P1734C2 RATING:1500 SPEED :1500
VOLTAGE : 415 CURRENT:2086.8 [Link] [Link].6
AVR TYPE : MX321 ENGINE HRS : 1026.2

VISUAL INSPECTION

ELECTRICAL TEST RESULTS


RESISTANCE U-N V-N W-N U-V V-W W-U
(RANGE: 2Ω) .004Ω .004Ω .004Ω .008Ω .008Ω .008Ω
MAIN STATOR
INSULATION RESISTANCE VALUE 0.3MΩ
(USING: 1000 VOLTS MEGGAR)

RESISTANCE (RANGE: 2Ω) [Link].880Ω


MAIN-FIELD INSULATION RESISTANCE VALUE 20MΩ
( USING: 1000 VOLTS MEGGAR)
U-V V-W W-U
RESISTANCE (RANGE: 2Ω ) 142Ω 142Ω 142Ω
EXCITOR ROTOR
INSULATION RESISTANCE VALUE 30MΩ
( USING: 1000 VOLTS MEGGAR):

RESISTANCE (RANGE: 20Ω ) [Link].92Ω


EXCITOR STATOR INSULATION RESISTANCE VALUE 30MΩ
( USING: 1000 VOLTS MEGGAR

ALL DIODES WERE CHECKED BY MULTIMETER AND VALUES ARE FOUND EQUAL
RRA UNIT

OBSERVATIONS GENERAL INSPECTION OF THE ALTERNATOR HAS BEEN DONE.

REMARKS NO-LOAD AND LOAD TEST CONDUCTED ALL PARAMETERS ARE WITHIN NORMAL WORKING CONDITION

CHECK BY

KALEEM PASHA

SPECIALIST FOR GENERATORS AND MOTORS: