Final Book
Final Book
Faculty of Engineering
Under Supervision
Dr. Mohamed Shams
Dr. Mohamed Hassan
Prepared by
• Alaa Maher Mohamed Ali • Mahmoud Sherif
• Alaa Ibrahim Awad • Mena Allah Sherif
• Ibrahim Ahmed El-Sayed • Nour El-Deen Medhat Shokry
• Seif El-Deen Amr Hussein • Youssef Mohamed Kamel
Sponsored by
ACKNOWLEDGEMENT
First of all we would like to thank Allah for the accomplishment of our graduation
project The final step in our long academic journey and thank our families for their
continuous support.
One behalf of our team we want to express our grateful for whom supported us with
their valuable experience and provided us extensive personal and professional
guidance.
for their valuable efforts during our site visit to the Capital Gardens Substation.
Page | 2
Table of Contents
Chapter (1) Introduction ................................................................................. 11
1.1 Overview ................................................................................................................................... 11
1.2 Substations Classification ......................................................................................................... 11
1.2.1 Based on Insulation Medium ............................................................................................. 11
1.2.2 Based on Voltage Level ...................................................................................................... 13
1.2.3 Based on Application ......................................................................................................... 13
1.2.4 Based on Equipment Layout .............................................................................................. 14
1.2.5 Based on Busbar Arrangement Configuration ................................................................... 14
1.3 Main Substation Equipment ...................................................................................................... 18
1.3.1 Surge arrestors .................................................................................................................... 18
1.3.2 Disconnect switch (Isolator)............................................................................................... 19
1.3.3 Earth switch (Grounding Switch) ....................................................................................... 19
1.3.4 High Speed Earth Switch ................................................................................................... 20
1.3.5 Current Transformer (CT) .................................................................................................. 20
1.3.6 Voltage Transformers (VT)........................................................................................... 21
1.3.7 Circuit Breakers.................................................................................................................. 22
1.4 Electrical Engineer Roles in substations ................................................................................... 23
1.4.1 Primary Engineer................................................................................................................ 23
1.4.2 Secondary Engineer............................................................................................................ 24
Chapter (2) Project scope ................................................................................ 26
2.1 General Technical Specification ............................................................................................... 26
2.2 Single Line Diagram (SLD) ................................................................................................. 26
2.2.1 Overview ............................................................................................................................ 26
2.2.2 Important studies performed on a Single Line Diagram .................................................... 26
2.2.3 When to update Single Line Diagram ................................................................................ 26
2.2.4 How to design the SLD ...................................................................................................... 27
2.2 Transformer Sizing .................................................................................................................... 30
2.2.1 Three windings transformer ............................................................................................... 30
2.2.2 Two windings transformer.................................................................................................. 32
2.2.3 Auxiliary Transformer ........................................................................................................ 32
2.3 Busbar Sizing ............................................................................................................................ 33
2.3.1 Busbar (66KV) ................................................................................................................... 33
Page | 3
2.3.2 Busbar (13.8KV) ................................................................................................................ 34
2.4 Circuit Breaker Sizing ......................................................................................................... 34
2.4.1 Normal Capacity Calculation ............................................................................................. 34
2.4.2 Breaking Capacity Calculation ( SC Capacity ) ................................................................. 35
2.5 Circuit Breaker Selection .......................................................................................................... 35
2.5.1 For the 66 KV ( After the grid and before the transformers ) ............................................ 35
2.5.2 For the 66 KV ( Before three windings transformers ) ...................................................... 36
2.5.3 For the 66 kV (Before two winding transformer) .............................................................. 36
2.5.4 For the 3.3 kV (After three winding transformer) .............................................................. 37
2.5.5 For the 13.8 kV (After two windings transformer) ............................................................ 37
2.5.6 For the 13.8 kV (Booster Motor bay) ................................................................................. 38
Chapter (3) Cable Sizing .................................................................................. 40
3.1 Cable Layers ............................................................................................................................. 40
3.1.1 Conductor ........................................................................................................................... 40
3.1.2 Conductor Screen ............................................................................................................... 40
3.1.3 Insulation ............................................................................................................................ 40
3.1.4 Insulation Shield ................................................................................................................. 40
3.1.5 Metallic Sheath ................................................................................................................... 40
3.1.6 Filler (Bedding) .................................................................................................................. 40
3.1.7 Armour ............................................................................................................................... 40
3.1.8 Outer Jacket ........................................................................................................................ 40
3.2 Cable Routing ........................................................................................................................... 41
3.2.1 Cable trays .......................................................................................................................... 41
3.2.2 Pipes ................................................................................................................................... 41
3.2.3 Underground Cables ........................................................................................................... 41
3.3 Cable Design ............................................................................................................................. 42
3.3.1 Current Carrying Capacity check ....................................................................................... 42
3.3.2 Voltage Drop check ........................................................................................................... 44
3.3.3 Short Circuit check ............................................................................................................. 44
3.4 MV Cable Design in scope of project ....................................................................................... 46
3.4.1 Cables sizing after two windings transformer:................................................................... 46
3.4.2 Cables sizing after three windings transformer:................................................................. 49
3.4.3 Cable sizing from 3.3kV switchgear to Motor : ................................................................. 51
Page | 4
3.4.4 Cable sizing from 13.8kV switchgear to Motor : ............................................................... 52
Chapter (4) AC and DC Auxiliary .................................................................. 54
4.1 Introduction ............................................................................................................................... 54
4.2 Panel Arrangements .................................................................................................................. 54
4.3 AC Auxiliary System ................................................................................................................ 55
4.3.1 AC SLD ........................................................................................................................ 57
4.4 DC Auxiliary System ................................................................................................................ 58
4.4.1 DC SLD .............................................................................................................................. 59
4.5 Batteries ................................................................................................................................. 60
4.5.1 Battery Room Safety .......................................................................................................... 61
4.5.2 Battery Chargers ................................................................................................................. 61
Chapter (5) Grounding System ....................................................................... 63
5.1 Introduction ............................................................................................................................... 63
5.2 Objective ................................................................................................................................... 63
5.3 Parts of the Substation’s Grounding System............................................................................. 63
5.3.1 The Grounding Network .................................................................................................... 64
5.3.2 The Connection to the Earth ............................................................................................... 64
5.4 Limits of Current Tolerable by the Human Body ..................................................................... 65
5.6 Tolerable Voltages ..................................................................................................................... 65
5.6.1 Metal to metal voltage (Emm) ........................................................................................... 65
5.6.2 Step voltage 𝑬𝒔 .................................................................................................................. 65
3.1.5.c Touch voltage (𝑬𝒕) .......................................................................................................... 65
3.1.5.d Mesh voltage 𝑬𝒎 ............................................................................................................ 65
3.1.5.e Transferred voltage (𝑬𝐭𝐫𝐚𝐧𝐬𝐟𝐞𝐫𝐫𝐞𝐝)............................................................................. 65
5.7 Overview on our Substation...................................................................................................... 66
5.7.1 Earth Grid Specifications ................................................................................................... 66
5.7.2 Earthing Transformers ........................................................................................................ 67
5.7.3 Neutral Grounding.............................................................................................................. 67
5.8 Grounding Design Steps : ......................................................................................................... 68
5.9 Soil Resistivity Measurement Methods .................................................................................... 69
5.9.1 Wenner Four Pin Method ................................................................................................... 69
5.9.2 Schlumberger Method ........................................................................................................ 70
5.9.3 Driven Rod (3 Pins) Method .............................................................................................. 70
Page | 5
5.10 Grounding System in our Substation Using Excel ................................................................. 71
5.10.1 Calculation of conductor cross section according to IEEE std 80 ................................... 71
5.10.2 calculation of ground resistance according to IEEE std 80 ............................................. 72
5.10.3 Maximum permissible value of step and touch voltage according to IEEE std 80 ......... 72
5.10.4 mesh and step voltage calculations according to IEEE std/80 ......................................... 73
5.11 Grounding System In the Substation Using CYMGrd : ......................................................... 73
Chapter (6) Protection...................................................................................... 75
6.1 Protective Relays ...................................................................................................................... 75
6.1.1 Distance Relay.................................................................................................................... 75
6.1.2 Differential Relay ............................................................................................................... 81
6.1.3 Over Current Relay ............................................................................................................ 84
6.2 Types of Substation ................................................................................................................... 87
6.2.1 Conventional Substation .................................................................................................... 87
6.2.2 SCADA Based Substation .................................................................................................. 87
6.2.3 SAS (Substation Automation System) ............................................................................... 88
6.3 Protection Schemes and Associated Control & Metering Panels in Substations...................... 89
6.3.1 Local Control Panel (+W) .................................................................................................. 89
6.3.2 Remote Control Panel (+P) ................................................................................................ 91
6.3.3 Protection Unit ................................................................................................................... 91
6.3.4 Metering Unit ..................................................................................................................... 92
6.3.5 Busbar Protection ............................................................................................................... 93
6.4 Types of Bays in a Substation ................................................................................................... 95
6.4.1 Line Bay ............................................................................................................................. 95
6.4.2 Transformer Bay ................................................................................................................. 97
6.4.3 Coupler Bay...................................................................................................................... 101
Chapter (7) CT and VT Sizing ...................................................................... 102
7.1 Current Transformer................................................................................................................ 102
7.1.1 Functions .......................................................................................................................... 102
7.1.2 Types ................................................................................................................................. 102
7.1.3 Metering CT & protection CT .......................................................................................... 103
7.1.4 Specifications of CT ......................................................................................................... 104
7.1.5 CT sizing..................................................................................................................... 106
7.1.6 CTs Cores in our substation ............................................................................................. 107
Page | 6
7.2 Voltage Transformer ................................................................................................................ 125
7.2.1 Introduction to Voltage Transformers ............................................................................... 125
7.2.2 Types of Voltage Transformers ................................................................................... 125
7.2.3 VT Sizing.......................................................................................................................... 126
Chapter (8) Relay Coordination ................................................................... 131
8.1 The importance of overcurrent protection .............................................................................. 131
8.1.1 Coordination procedure .................................................................................................... 131
8.1.2 Principles of Time/Current grading .................................................................................. 131
8.1.3 Points affecting this method ............................................................................................. 133
8.1.4 Discrimination by both Time and Current ....................................................................... 134
8.2 Relay coordination Using ETAP: ............................................................................................ 135
8.2.1 Three phase Fault at Booster Motor ................................................................................. 137
8.2.2 Fault at 13.8 kV bus ......................................................................................................... 138
8.2.3 Fault at VFD Motor .......................................................................................................... 139
8.2.4 Fault at 3.3 kV bus ........................................................................................................... 140
8.2.5 Fault at primary side of three windings transformer ........................................................ 141
8.2.6 Fault at 66kV bus ............................................................................................................. 141
8.3 Protection Star Views .............................................................................................................. 142
Chapter (9) Lightning Protection and surge arrestor ................................ 146
9.1 Lightning Protection ............................................................................................................... 146
9.1.1 Selected factors ................................................................................................................ 146
9.1.2 Selected Protection Level ................................................................................................. 148
9.1.3 Design Phase .................................................................................................................... 149
9.2 Surge Arrester Sizing .............................................................................................................. 152
9.2.1 Introduction ...................................................................................................................... 152
9.2.2 Determination of Minimum Rated Voltage ...................................................................... 153
9.2.3 Verification Using Temporary Overvoltage (TOV) Capability ........................................ 153
9.2.4 Selection of Surge Arrester Type and Class ..................................................................... 154
9.2.5 Determination of Protection Levels (𝑼𝒑𝒍 and 𝑼𝒑𝒔) ....................................................... 154
9.2.6 Calculation of Protection Margins ................................................................................... 155
9.2.7 Selection of Final Surge Arrester Rating.......................................................................... 156
9.2.8 Conclusion ........................................................................................................................ 157
Page | 7
Table of Figures
Figure 1 Air Insulated Substation ....................................................................................................... 11
Figure 2 Gas Insulated Substation ...................................................................................................... 12
Figure 3 Single bus Configuration ...................................................................................................... 15
Figure 4 Main Bus and Transfer Bus Configuration .......................................................................... 15
Figure 5 Double Bus Double Breaker Configuration ......................................................................... 16
Figure 6 Double Bus Single Breaker Configuration .......................................................................... 16
Figure 7 Ring Bus Configuration ....................................................................................................... 16
Figure 8 Breaker and Half Configuration ........................................................................................... 17
Figure 9 Surge arrestors ...................................................................................................................... 18
Figure 10 Valve type arrestor ............................................................................................................. 18
Figure 11 Metal oxide arrestor ........................................................................................................... 18
Figure 12 Disconnect switch .............................................................................................................. 19
Figure 13 Grounding Switch .............................................................................................................. 19
Figure 14 GIS High Speed Earth Switch ............................................................................................ 20
Figure 15 Current Transformer ........................................................................................................... 20
Figure 16 : Single Line Diagram ........................................................................................................ 28
Figure 17: K-Factors ........................................................................................................................... 30
Figure 18: Transformer derating factor .............................................................................................. 31
Figure 19 : Busbar 66kV..................................................................................................................... 33
Figure 20 : Busbar 13.8kV ................................................................................................................. 34
Figure 21 : Layout .............................................................................................................................. 39
Figure 22 : Cable Layers..................................................................................................................... 40
Figure 23 : Ladder cable tray .............................................................................................................. 41
Figure 24: Air Temperature derating factor ....................................................................................... 42
Figure 25 : Ground Temperature derating factor................................................................................ 42
Figure 26 :Burial depth derating factor .............................................................................................. 43
Figure 27: Soil thermal resistivity derating factor .............................................................................. 43
Figure 28: Grouping derating factor ................................................................................................... 44
Figure 29: Short circuit current in kA for copper and XLPE insulation ............................................ 45
Figure 30 :Two windings transformer Bay......................................................................................... 46
Figure 31 : Selected MV Cable for two winging transformer ............................................................ 47
Figure 32 : Three windings transformer Bay...................................................................................... 49
Figure 33 : Selected MV Cable for three winging transformer .......................................................... 49
Figure 34: AC Auxiliary Loads .......................................................................................................... 56
Figure 35 : AC Auxiliary SLD ........................................................................................................... 57
Figure 36 220v chargers ..................................................................................................................... 59
Figure 37: DC Auxiliary SLD ............................................................................................................ 60
Figure 38 :Grounding Network .......................................................................................................... 64
Figure 39 : Basic shock situations ...................................................................................................... 66
Figure 40 : Design Procedures flow chart ......................................................................................... 68
Figure 41 : Wenner Four Pin Method ................................................................................................. 69
Figure 42 : Schlumberger Method ...................................................................................................... 70
Figure 43 : Driven Rod (3 Pins) Method ............................................................................................ 70
Figure 44: Grid of Grounding Grid 2D View ..................................................................................... 73
Figure 45 :Grid of Grounding Grid 3D View ..................................................................................... 74
Figure 46 : The Potential Profile Plot ................................................................................................. 74
Figure 47 : Permissible vs Actual Ground Potential Values .............................................................. 74
Figure 48: Grounding Resistance ....................................................................................................... 74
Page | 8
Figure 49 : Operation mechanism and Torque characteristic for Impedance Relay .......................... 75
Figure 50 : Drawbacks of Impedance Relay Characteristic ............................................................... 76
Figure 51 : Directional Impedance Characteristic .............................................................................. 76
Figure 52 : Self-Polarized Mho (Admittance) Characteristic............................................................. 77
Figure 53: Third Zone and Busbar Back-up Zone characteristic ....................................................... 78
Figure 54 : Carrier Starting Unit in Distance Schemes with Carrier Blocking .................................. 79
Figure 55 : Quadrilateral Characteristic ............................................................................................. 79
Figure 56 : Reactance Type Characteristic ......................................................................................... 79
Figure 57: Lenticular Characteristic .................................................................................................. 80
Figure 58 :Typical high impedance differential scheme .................................................................... 81
Figure 59 : Distributed busbar protection ........................................................................................... 82
Figure 60 :Transformer Differential Relay Protection ....................................................................... 83
Figure 61 : Schematic Diagram of Differential Protection Scheme ................................................... 84
Figure 62: Instantaneous Action ......................................................................................................... 84
Figure 63 : time delayed action ......................................................................................................... 85
Figure 64 : Numerical relay time vs current c/cts .............................................................................. 85
Figure 65: Operating time vs current (multiples of pick-up SETTING) ............................................ 86
Figure 66: Line Bay ............................................................................................................................ 95
Figure 67 : Protection Scheme of Line Feeder ................................................................................... 97
Figure 68 : Transformer Bay .............................................................................................................. 97
Figure 69 : Buchholz Relay ................................................................................................................ 99
Figure 70 : Pressure Relief Device ..................................................................................................... 99
Figure 71 : Protection scheme of three windings transformer ......................................................... 100
Figure 72 : Protection Scheme of two windings transformer ........................................................... 100
Figure 73 : Coupler Bay ................................................................................................................... 101
Figure 74 : Protection Scheme of Coupler ....................................................................................... 101
Figure 75 :CT magnetization curve .................................................................................................. 103
Figure 76 : Equivalent circuit of CT ................................................................................................. 103
Figure 77: Knee Point Voltage Definition for CT ............................................................................ 105
Figure 78 : Inductive Voltage Transformers .................................................................................... 125
Figure 79 : Capacitive Voltage Transformers Circuit ...................................................................... 125
Figure 80 : Double Frequency Meter ............................................................................................... 130
Figure 81 :Synchroscope .................................................................................................................. 130
Figure 82 : Relay characteristics for different settings ..................................................................... 134
Figure 83 : CT specs in ETAP .......................................................................................................... 135
Figure 84 : Relay Chosen in ETAP .................................................................................................. 135
Figure 85 : Relay Settings ................................................................................................................ 136
Figure 86 : star view for Booster motor and its protective relay ...................................................... 142
Figure 87 :Star view for the selected relays at 13.6 KV level .......................................................... 143
Figure 88:3Star view for relays of 3 winding bay ............................................................................ 144
Figure 89:Star view of LVCB and cable connected to lambed load ................................................ 145
Figure 90: Lightning Protection Level ............................................................................................. 148
Figure 91 : Air Termination arrangement......................................................................................... 151
Figure 92: Flowchart for selection of surge arresters ....................................................................... 152
Page | 9
Tables
Table 1 : Comparison between GIS and AIS .......................................................................... 12
Table 2 : Comparison between Busbar Configurations .......................................................... 17
Table 3 : Grounding Resistance .............................................................................................. 24
Table 4: Equation of relay characteristic................................................................................. 85
Table 5: Equations of ANSI overcurrent relay ....................................................................... 86
Table 6:Different Accuracy Classes for CTs ........................................................................ 104
Table 7:Accuracy Class of protection CT ............................................................................. 105
Table 8 : Comparison between Inductive VT and Capacitive VT ........................................ 126
Table 9 : Relay Settings......................................................................................................... 136
Page | 10
Chapter (1) Introduction
1.1 Overview
The interconnection of various power system networks relies on a crucial infrastructure
component: the electrical substation. An electrical substation is a sophisticated assembly of
electrical equipment, including busbars, switchgear, power transformers, and auxiliary systems.
These components are organized in a structured sequence to facilitate both manual and automatic
control. During normal operation, substations enable circuits to be switched on and off through
manual commands, while in abnormal situations, such as short circuits, they provide automatic
protective responses to maintain system stability and safety.
An electrical substation consists of multiple incoming and outgoing circuits connected to a shared
busbar system. It receives electrical power from sources like generating stations through incoming
transmission lines and distributes this power through outgoing transmission lines to designated
areas.
Page | 11
• Gas Insulated Substation
A Gas Insulated Substation (GIS) is an
electric power substation where all live
components and busbars are enclosed within
grounded metal chambers filled with gas.
The gas commonly used is sulfur
hexafluoride (SF₆), known for its excellent
dielectric properties, which provides
insulation between phases and from phase to
ground at a moderate pressure. In GIS, high-
voltage conductors, circuit breakers,
switches, current transformers, voltage
transformers, and surge protectors are
encapsulated within SF₆-insulated chambers,
offering robust isolation.
The superior dielectric strength of SF₆ gas
allows for significantly reduced phase-to-
phase and phase-to-ground clearance, Figure 2 Gas Insulated Substation
making GIS particularly suitable for densely
populated urban areas where space is limited. The compact design of GIS can reduce the overall
footprint of a substation to approximately 10% of that required by traditional Air Insulated
Substations (AIS).
GIS is also equipped with a gas monitoring system to ensure proper gas pressure within each
compartment, typically maintained at around 3 kg/cm². If the pressure drops, the system
automatically activates gas containment, and in cases of further leakage, a low-pressure alarm or
automatic shutdown is triggered to ensure safety and reliability.
Page | 12
1.2.2 Based on Voltage Level
In Egypt, voltage transmission is classified into specific levels based on voltage intensity,
addressing the varying needs of large-scale transmission, regional distribution, and localized
delivery. Each level is defined by a standardized range that aligns with international best practices
for efficient energy distribution and network safety. The classifications are as follows:
• Distribution Substation
A distribution substation serves as the link between the high-voltage transmission system and the
lower-voltage distribution system of a specific area. Directly connecting most electricity consumers
to the high-voltage transmission network is generally inefficient and costly unless they have
substantial power demands. Instead, the distribution substation reduces the transmission voltage to
levels suitable for local distribution, making it safe and economical for widespread residential and
commercial use.
The substation’s output is channeled through multiple feeders, each supplying power to a distinct
part of the local distribution network. Distribution voltages typically range from 2.4 to 33 kV,
depending on the geographic area covered and the standards of the local utility. This intermediate
voltage level is carefully selected to balance efficiency in power delivery with the cost and
infrastructure requirements of the distribution system.
Maintenance of any circuit breaker requires shutdown of the corresponding circuit/line and
maintenance of the bus requires a complete shutdown of the bus. A bypass switch across the breaker
should be used for maintenance of the corresponding breaker. Circuit protection is disabled in this
case.
Page | 14
The single bus substation configuration is the simplest and
least expensive of all configurations. This configuration
requires less installation area, and it can be easily expanded.
Single bus configurations are not considered reliable
systems, and they should only be implemented in
substations where high reliability is not required, such as
large transmission yards. Reliability and availability of this
system can be improved by expanding and sectionalizing the
bus.
Page | 15
• Double Bus Double Breaker
• Ring Bus
The ring bus configuration arranges circuit breakers in a ring,
with isolators on each side, allowing each circuit to be fed from
both directions. This design provides high operational flexibility
and reliability, as any circuit breaker can be isolated for
maintenance without disrupting service.
In the event of a fault, two breakers on either side of the affected
circuit trip, isolating only the faulted circuit while keeping all
other circuits in operation. However, a fault also splits the ring,
potentially creating two isolated sections. This may lead to an
imbalance if source and load circuits are not optimally arranged Figure 7 Ring Bus Configuration
side by side.
While the ring bus can be expanded to support additional circuits, it generally functions best with a
maximum of six. Careful planning is recommended to manage future expansion limitations
effectively.
Page | 16
• Breaker and Half
When substation expansion is needed, the ring bus can be
upgraded to the "one-and-a-half breaker" configuration. This
setup features two main buses, both energized, with three
breakers arranged between them for every two circuits hence
the "one-and-a-half" designation. Each circuit has a dedicated
breaker and shares a middle breaker with an adjacent circuit,
like the dual-feed design of a ring bus.
This configuration allows any breaker to be taken out for
maintenance without disrupting power to other circuits, and
either main bus can be maintained without affecting circuit Figure 8 Breaker and Half Configuration
service. In case of a middle breaker failure, adjacent breakers
trip to isolate the affected circuits, while a failure in an adjacent breaker does not interrupt service to
the remaining circuit.
The one and a half breaker scheme is highly reliable, flexible, and more economical than the double
bus double breaker design, though it requires additional space and a complex protective relay setup
due to shared breakers.
Double Bus Double Breaker Very High Very High Very Large
Page | 17
1.3 Main Substation Equipment
1.3.1 Surge arrestors
Surge arresters protect substation equipment from harmful
voltage surges caused by lightning strikes or switching
operations. They safely redirect excess voltage to the ground,
shielding sensitive equipment from potential damage. Surge
arresters are especially important in overhead transmission lines
(OHTL), where they play a key role in ensuring reliable power
transfer.
Page | 18
1.3.2 Disconnect switch (Isolator)
Disconnect switches are used to isolate and disconnect substation
equipment from the power grid, creating a visible open gap in the
electrical circuit to ensure safety during maintenance and repair
work. This clear separation helps prevent accidental energizing of
equipment, providing a secure environment for personnel working
on the system.
• Types Of Disconnect Switch
✓ Center Break Disconnect Switch
Center break disconnect switches feature a symmetrical design,
with a center gap that opens to separate contacts, ensuring clear
isolation. These switches are widely used in high-voltage
applications and are typically motor-operated or manually operated.
Page | 20
Importance of CT
➢ Current Measurement
Current Transformers (CTs) are primarily used to measure the current flowing through power
lines with precision. They provide a scaled-down version of the primary current, enabling
instruments and devices to safely and accurately measure and monitor current levels in high-
voltage environments.
➢ Protection and Control
CTs are essential in protection and control systems within substations. They connect to
protection relays and devices that monitor current conditions for abnormalities, such as
overcurrent or fault currents. When a fault or abnormal condition is detected, the protection
system isolates the affected section to protect the equipment and ensure operational safety.
➢ Voltage Current Relationship
CTs operate on the principle of electromagnetic induction. They contain a primary winding
connected in series with the power line carrying the measured current and a secondary
winding connected to measuring or protection devices. The secondary winding has fewer
turns than the primary winding, creating a reduced current in the secondary that is
proportional to the primary current, thus making it manageable for measurement and
protection purposes.
VTs are crucial for protection and control systems in high voltage substations. They connect to
protective relays and other devices that monitor for abnormal voltage conditions, such as
overvoltage or undervoltage. These protective relays rely on VTs to detect and respond to
voltage irregularities by isolating faulty sections of the power system, ensuring system
stability and protecting equipment.
Circuit breakers are electrical devices designed to interrupt or disconnect an electrical circuit,
offering protection against overcurrent, short circuits, and other electrical faults. In high-voltage
(HV) systems, circuit breakers play a critical role in maintaining system safety and reliability. Their
operation is typically managed by protective relays, which monitor the circuit for abnormal
conditions. When a fault is detected, the relay signals the circuit breaker to open, isolating the faulty
section and preventing damage to equipment and reducing the risk of outages in the power system.
Page | 23
Facility Type Permissible Resistance (Ohms)
Power Stations 0.5
Extra-High Voltage (EHV) Substations 1
33 kV Stations 2
Distribution/Transmission Centers 5
Tower Foot Resistance 10
Table 3 : Grounding Resistance
Generating stations and transformer stations, which experience high fault currents, require very low
ground resistance. This is achieved by creating a ground mesh network of electrodes, distributing
the fault current and reducing dangerous voltage levels on grounding conductors.
Primary engineers play a foundational role in ensuring that each design element within the
substation meets operational, safety, and maintenance requirements, creating a reliable and resilient
power infrastructure.
Page | 24
• Battery System Sizing: The DC battery system plays a crucial role in substations by
providing a reliable power source for key systems:
• Protection Systems: Many protective relays and fault-detection devices rely on DC power to
operate independently of the AC system, ensuring continuous operation even during AC
faults.
• Control and Monitoring: DC power enables precise control and monitoring of substation
equipment, such as switchgear and circuit breakers, ensuring efficient coordination and stable
operation.
• Alarm and Indication Systems: Alarms and indicators within protective relays rely on DC
power to alert operators of faults or abnormal conditions. DC-powered signals help operators
identify fault locations quickly and take corrective action.
• Telecommunication and Signaling: Communication systems, including data transmission
and control equipment, are powered by DC to ensure reliable and uninterrupted
communication across the substation for effective monitoring and control.
• Insulation Coordination: Insulation coordination is a technique for ensuring the electrical
strength of various substation components matches system requirements and expected
voltage levels. The goal is to reduce the likelihood of failures caused by insulation
breakdowns to an acceptable operational and economic level.
• Protection Scheme : Protection scheme coordination involves designing and configuring
protection devices so they respond selectively to faults. The secondary engineer ensures that
each protective device activates only under specific conditions, isolating faults in a targeted
manner to prevent unnecessary system-wide outages. Proper coordination minimizes service
interruptions, limits equipment damage, and maintains overall system reliability.
• Cable Sizing : Cable sizing is crucial to ensure that cables can safely and efficiently handle
the electrical load. The secondary engineer calculates the appropriate cable size based on
factors such as current-carrying capacity, voltage drop, thermal limits, and short-circuit
conditions. Correct cable sizing prevents overheating, maintains voltage stability, and
extends the lifespan of both the cable and connected equipment, ensuring safe and reliable
operation.
• Grid Impact Studies: Grid impact studies assess the potential effects of new substation
installations or modifications on the larger electrical grid. The secondary engineer analyzes
how changes in load, generation, and protection settings will impact grid stability, voltage
levels, and fault behavior. These studies ensure that the integration of new infrastructure does
not compromise grid performance or reliability, enabling safe and efficient operation within
the broader network.
Page | 25
Chapter (2) Project scope
2.1 General Technical Specification
This chapter focuses on the design and engineering considerations for a substation that steps down
power from a primary voltage level of 66kV to secondary levels of 13.8kV and 3.3kV. The design
prioritizes compactness, reliability, and efficiency, making it suitable for urban or space-constrained
environments. The substation incorporates advanced Gas Insulated Substation (GIS) technology to
optimize space usage and ensure operational safety.
Key highlights include:
• Primary Voltage Level: 66kV, used for power transmission into the substation.
• Secondary Voltage Levels: 13.8kV for industrial and utility-scale applications, and 3.3kV
for high capacity motor loads and auxiliary systems.
• Auxiliary Voltage Support: 0.4kV for control systems, lighting, and auxiliary equipment.
• Layout Design: The entire substation fits within a 150x100 meter area, showcasing a space-
efficient layout.
• GIS Technology Integration: Enhances safety, minimizes maintenance, and ensures robust
performance in limited spaces.
Page | 26
2.2.4 How to design the SLD
It is the arrangement of the documents according to the priority in case of confliction as follows:
1) Price List
2) Guarantee Schedule
3) S-Schedule
4) PTS
3) Guarantee Schedule:
It is a document which consists of a group of tables specifying each equipment parameters, similar
to S-Schedule but the parameters in the tables are filled by the manufacturer (therefore, each
equipment in the table has an empty space for the parameters to be filled)
It’s provided by the Manufacturer
Containing the actual parameters (these parameters may be included in the SLD)
May be deviated from the S-Schedule
4) Price List:
It is a document which consists of the BOQ of the substation which containing item description,
also the price and quantity of each equipment
It’s provided by the Contractor
It has the most priority (according to the POD) over the above documents in case of confliction
Page | 27
Figure 16 : Single Line Diagram
Page | 28
Page | 29
2.2 Transformer Sizing
Transformers play a pivotal role in stepping down voltage levels from the high voltage (66kV)
transmission system to medium voltage (13.8kV) and medium voltage (3.3kV) distribution
systems. Their sizing is determined by the load requirements, efficiency, and operational
flexibility.
Load Requirements and Transformer Capacity
To size the transformers, the total load on the substation and individual voltage levels must be
considered. This includes:
Assumptions
• Diversity Factor (Div. F): 0.8
This accounts for the likelihood that not all loads operate at full capacity simultaneously,
optimizing transformer capacity and sizing for practical operation scenarios.
• Demand Factor (D.F): 1
This assumes the load operates at its full capacity under specific conditions, ensuring the
system is designed to handle peak loads without overloading.
• According to NEMA :Transformer is loaded with 80% of full load capacity
• According to 𝑵 − 𝟏 Criteria :Each transformer is designed to withstand the full load
capacity
Page | 30
Figure 18: Transformer derating factor
• Three windings transformer its rating is 25 MVA feed two VFD motor
• For secondary side, the primary MVA is divided on both secondary delta sides therefore their
ratings are 12.5 MVA
• Transformer Type:
Choose the appropriate transformer type based on the specific application and requirements.
The common type for power substations is oil-filled transformer
• Cooling Method:
We select the cooling method based on the substation's operating conditions and available
resources. We selected (ONAF)
• Vector Group:
YNd5d5
✓ YN – Primary winding (High Voltage side): Connected in star (wye), with a neutral
point available.
✓ d5 – Secondary winding (Medium Voltage side): Connected in delta, with a neutral
point derived artificially (i.e., through grounding transformer or zigzag).
The '5' indicates a 150° phase shift (5 × 30° lagging of secondary with respect to
primary).
✓ d5 –Second Secondary winding (Medium Voltage side):
Page | 31
2.2.2 Two windings transformer
Booster Motor Load (13.8kV):
✓ Rated Power: 2200 kW
✓ Power Factor: 0.84
✓ Rated Current 𝐼𝑟𝑎𝑡𝑒𝑑 = 110.1𝐴
✓ Efficiency : 95.9%
• Transformer Type
Choose the appropriate transformer type based on the specific application and requirements.
The common type for power substations is oil filled transformer.
• Cooling Method
We select the cooling method based on the substation's operating conditions and available
resources. Common cooling methods include oil-immersed (ONAN), forced air (ONAF)
• Vector Group:
YNd5
✓ Y – The primary winding is connected in star (wye).
✓ N – The star point on the primary is neutral-connected, typically grounded.
✓ d – The secondary winding is connected in delta.‘5’ The phase displacement between
primary and secondary is 150° (clock notation 5 o'clock)
Page | 32
2.3 Busbar Sizing
When selecting busbars for substations, we should consider:
2.3.1 Busbar (66KV)
• Rated Current
25000 30000
𝐼𝑟𝑎𝑡𝑒𝑑 = (4 + 1(𝑠𝑝𝑎𝑟𝑒)) ∗ ( )+( ) = 1355.9 ≈ 𝟐𝟎𝟎𝟎 𝐀 To the nearest standard
√3∗66 √3∗66
Conductor type: CU
• Voltage Level
Based on the voltage level of the substation, we select bus bars with the rated voltage of 66 kV
• Configuration
Double Bus Single Breaker
Page | 33
2.3.2 Busbar (13.8KV)
• Rated Current
1000
𝐼𝑟𝑎𝑡𝑒𝑑 = ((8 + 2(𝑠𝑝𝑎𝑟𝑒)) ∗ 110.1) + 2 ∗ ( ) = 1184.7 ≈ 𝟏𝟐𝟓𝟎 𝐀 To the nearest
√3∗13.8
standard
Conductor type: CU
• Voltage Level
Based on the voltage level of the substation, we select bus bars with the rated voltage of
17.5kV approximately to the nearest standard rating
Page | 34
2.4.2 Breaking Capacity Calculation ( SC Capacity )
• Firstly, we will obtain the Maximum Short-Circuit Current using short-circuit study results
we got from ETAP.
• Apply the safety margin ( 10 – 25 ) % :
• Choose a breaker with a rated breaking capacity greater than or equal to the adjusted fault
current.
• After that we will check the Rated Voltage level
• Then we will choose the suitable one which matches with the normal Capacity specifications
2.5.1 For the 66 KV ( After the grid and before the transformers )
• Normal Capacity Calculation
25000 30000
𝐼𝑟𝑎𝑡𝑒𝑑 = (4 + 1(𝑠𝑝𝑎𝑟𝑒)) ( )+( ) = 1355.9 𝐴
√3 × 66 √3 × 66
𝐼𝐶𝐵 = 1.25 𝐼𝑟𝑎𝑡𝑒𝑑 = 1.25 × 1355.9 = 1694.9 we select nearest standard 𝟐𝟎𝟎𝟎 𝑨
• Breaking Capacity Calculation
𝐼𝑏𝑟𝑒𝑎𝑘𝑖𝑛𝑔 = 1.25 × 𝐼𝑠𝑐 = 1.25 × 5.69 = 7.11 𝑘𝐴
• Making Current Calculation
𝐼𝑚𝑎𝑘𝑖𝑛𝑔 = 2.55𝐼𝑏𝑟𝑒𝑎𝑘𝑖𝑛𝑔 = 18.13 𝑘𝐴
✓ We chose the Siemens 8VM3 Blue GIS Circuit
Breaker.
✓ Rated voltage 66 kV
✓ Max. system voltage 72.5 kV
✓ SF₆-insulated, compact, maintenance friendly.
✓ Highly dependable for medium to high voltage
GIS stations.
✓ Rated normal current 1500 A
✓ Rated short circuit current up to 40 kA for 1 sec.
Page | 35
2.5.2 For the 66 KV ( Before three windings transformers )
• Normal Capacity Calculation
25000
𝐼𝑟𝑎𝑡𝑒𝑑 = ( ) = 218.69 𝐴
√3 × 66
𝐼𝐶𝐵 = 1.25 𝐼𝑟𝑎𝑡𝑒𝑑 = 1.25 × 218.69 = 273.4 we select 𝟏𝟐𝟓𝟎 𝑨
Page | 36
2.5.4 For the 3.3 kV (After three winding transformer)
Load Flow
Short circuit
Page | 38
Figure 21 : Layout
Page | 39
Chapter (3) Cable Sizing
3.1 Cable Layers
Page | 40
3.2 Cable Routing
Ways of cable routing could be classified as :
3.2.1 Cable trays
•
• Ladder cable tray
• Perforated cable tray
• Solid bottom type
• Wire mesh cable tray
• Channel cable tray
Cable trays can be specified by their : Width, Height, Thickness,
Cover, Material, Length
Figure 23 : Ladder cable tray
3.2.2 Pipes
• PVC hoses
Used inside walls and floors
• UPVC (Unrecycled Poly Vinyl Chloride)
They are similar to PVC pipes, but do not contain any recycled components. These pipes are
of higher quality than PVC, but they are more expensive and are used above a dropped or
suspended ceiling.
• Flexible spiral pipes
• Electrical Metallic Tube
Page | 41
3.3 Cable Design
While making a cable design, we must ensure that 3 conditions are met as follows:
• Current carrying capacity.
• Voltage drop.
• Short circuit.
• If the cable is buried in the ground, the correction is made according to the soil temperature so
the temperature de-rating factor is chosen from the following table
Page | 42
3.3.1b Effect of burial depth
If the cable is buried underground, the burial depth de-rating factor will be chosen from this table
Page | 43
3.3.1d Effect of grouping
Reduction factors for groups of more than one circuit of single-core cables (note 2) to be applied
to the current carrying capacity for one circuit of single-core cable in free air
Page | 44
Determination of the short circuit capacity of a cable
3.3.3a Using manufacturers' tables: theses tables show the relationship between the cable
cross-section and the maximum short circuit it can withstand in a certain period as shown in
this table
Figure 29: Short circuit current in kA for copper and XLPE insulation
From the following equations we can get max short circuit current can cable withstand.
✓ 𝐴𝑟𝑒𝑎 = 9.1 × √𝑡𝑠𝑐 × 𝐼𝑠𝑐 for copper.
✓ 𝐴𝑟𝑒𝑎 = 14.2 × √𝑡𝑠𝑐 × 𝐼𝑠𝑐 for aluminum.
Page | 45
3.4 MV Cable Design in scope of project
At our station, we have designed medium voltage cables for the following portions :
3.4.1 Cables sizing after two windings transformer:
Cables from each Secondary of 30MVA transformer to MV
switchgear.
All values in this catalogue are at 30 °C , so the first derating factor is for temperature :
➢ Choosing XLPE is suitable for insulation requirements in this level
➢ 50 °C is the nearest value in our country So 𝑫. 𝑭𝟏 = 𝟎. 𝟕𝟖
in free air
➢ So 𝑫. 𝑭𝟑 = 𝟎. 𝟖𝟔
1255.2
➢ So 𝐼𝐶𝐶𝐶 = = 2033.911𝐴
0.78∗0.92∗0.86
Page | 47
➢ Based on our voltage level 13.8KV we chose this category of cables with its line voltage till
15KV
➢ Single core due to the high current drawn
➢ Existence of these cables in our situation in ducts make us choose these cables unarmored
➢ Existing in duct bank so we chose these cables laid in free air
➢ We chose to eliminate the effect of total magnetic field in these cables
➢ Based on our ampacity we chose cable 𝟑 ∗ (𝟏𝑪) 𝟑𝟎𝟎 𝒎𝒎² 𝑪𝑼/𝑿𝑳𝑷𝑬/𝑷𝑽𝑪 / 𝑷𝒉𝒂𝒔𝒆
100
2033.911 ( ) (0.0792𝑐𝑜𝑠(14.488) + 011287𝑠𝑖𝑛(14.488))
𝑽. 𝑫 = √3 × ( ) × 1000
3 13800
= 𝟎. 𝟎𝟖𝟗% < 𝟎. 𝟓% ( 𝒂𝒄𝒄𝒆𝒑𝒕𝒆𝒅 )
Page | 48
3.4.2 Cables sizing after three windings transformer:
Cables from each Secondary of 25MVA transformer to MV switchgear.
The substation includes four 3-winding transformers, each feeding two VFD-driven motors, resulting
in a total of eight identical outgoing cables. Since all cables have the same specifications, length,
installation method, and loading conditions, the design and calculations were performed for a single
representative cable. The same results and parameters are applicable to the remaining seven cables.
Page | 50
3.4.3 Cable sizing from 3.3kV switchgear to Motor :
The system includes four 3 winding transformers, each of
which feeds two VFD driven motors through medium voltage
switchgear, resulting in a total of eight identical MV cables.
Since all cables share the same specifications, length,
installation method, and loading conditions, the design
calculations have been carried out for one representative cable
only. The results and design parameters are equally applicable
to the remaining seven cables.
3.4.3a Current carrying capacity check :
The same of previous sizing
𝟑 ∗ (𝟏𝑪) 𝟖𝟎𝟎 𝒎𝒎² 𝑪𝑼/𝑿𝑳𝑷𝑬/𝑷𝑽𝑪 / 𝑷𝒉𝒂𝒔𝒆
Given that the load current drawn by each motor is relatively low, the
short-circuit withstand capacity of the cable becomes the primary
design criterion. Therefore, the cable selection was initially based on
its ability to withstand the maximum short-circuit current at the
motor terminals. Once a suitable cable was identified for short-circuit
performance, its continuous current carrying capacity was verified to
ensure adequacy under normal operating conditions.
Page | 52
3.4.4b Current carrying capacity check :
Page | 53
Chapter (4) AC and DC Auxiliary
4.1 Introduction
Auxiliary systems are a fundamental part of any substation, as they ensure the continuous and
reliable operation of various critical components. These systems provide the necessary support
infrastructure required for both the primary power transmission functions and the control,
protection, and communication functions within the substation.
Auxiliary systems are responsible for the following key roles:
• Powering internal station loads including all equipment and services that operate on both
AC and DC power, such as lighting, air conditioning, control panels, and protection relays.
• Supplying the protection and measurement systems which must always remain powered
to detect electrical faults, measure system parameters, and trigger protective actions in case
of abnormal conditions.
• Supporting the control, monitoring, and communication infrastructure including
SCADA systems, remote terminal units (RTUs), and Intelligent Electronic Devices (IEDs),
all of which rely on stable auxiliary power to function and to ensure real-time supervision of
substation status.
• Maintaining safety and emergency systems such as firefighting equipment, alarm systems,
and emergency lighting, which must function reliably during both normal operation and fault
conditions.
In this chapter, we provide a comprehensive overview of the auxiliary systems implemented in the
Substation, covering AC and DC auxiliary systems, communication infrastructure, and
monitoring/control systems, along with the relevant single-line diagrams (SLDs).
4.2 Panel Arrangements
Page | 54
4.3 AC Auxiliary System
The AC auxiliary system is designed to supply alternating current (AC) power to all essential station loads.
This is accomplished through a dedicated auxiliary transformer, which steps down the medium voltage of
13.8 kV to a low voltage level of 400 V. The low-voltage output feeds into the Main Distribution Board
(MDB), which then distributes power to various load centers within the facility.
The capacity of the auxiliary transformer is determined based on the total power requirements of the
station loads. In this case, the transformer is rated at 1 MVA. Additionally, a backup auxiliary
transformer is installed to ensure redundancy and maintain uninterrupted operation in case of
failure or maintenance of the main unit.
This system ensures the reliable operation of all AC-powered equipment necessary for the substation's
functionality, safety, and control.
Typical AC Loads:
• Power Distribution Boards (Buildings) General supply for electrical systems within the buildings.
• HVAC Distribution Boards Support for heating, ventilation, and air conditioning systems.
• Lighting Distribution Boards Interior and exterior lighting systems.
• Firefighting System Power for pumps, alarms, and fire safety controls.
• Other Loads Includes miscellaneous systems such as communication equipment, control room
panels, and auxiliary services.
• Dc Chargers (220V & 48V)
Page | 55
Figure 34: AC Auxiliary Loads
Page | 56
4.3.1 AC SLD
Page | 57
4.4 DC Auxiliary System
The DC auxiliary system plays a crucial role in maintaining protection, control, and communication
functions, especially during power outages or emergencies. Each station is equipped with a battery
room and a charger room, which together ensure continuous DC power supply to critical systems.
The system typically includes:
• Emergency Lighting
• Cables Protection Panels
• Transformer Protection Panels
• Bus Coupler Protection Panels
• Bus Bar Protection Panels
• Remote Control Panels
• Protection Panels Provide power to protection relays and associated devices.
• GIS Control Panels Power for Gas Insulated Switchgear control operations.
This setup ensures that the station’s most vital components remain operational during loss of AC
power, enabling safe shutdown procedures, fault detection, and continued communication with
supervisory systems.
Page | 58
4.4.1 DC SLD
Page | 59
4.5 Batteries
A battery is an electrochemical energy storage device that stores energy in chemical form and
releases it as electrical energy through an electrochemical reaction. In substations, batteries serve
as a reliable and uninterrupted DC power source for critical systems, especially during loss of
AC supply or emergency conditions.
Batteries are typically installed in dedicated rooms, with environmental and safety considerations
such as ventilation, temperature control, and insulation from electrical interference. They are
connected to battery chargers that keep them continuously charged and ready to supply power
when needed.
• Sufficient autonomy: the duration for which the battery can supply power without external
input, typically ranging from 1 to 8 hours depending on system requirements.
• Nickel-Cadmium (Ni-Cd) are preferred for high temperature tolerance and longer life in
harsh environments.
The proper sizing, maintenance, and monitoring of battery systems are essential to guarantee the
availability and performance of the substation’s critical control and protection infrastructure.
Page | 60
4.5.1 Battery Room Safety
As batteries are continuously charged in the station, the charging process results in the emission of
hydrogen gas, which poses a significant explosion risk if its concentration exceeds 14% within the
battery room. Therefore, strict safety measures must be implemented to ensure personnel safety and
system integrity.
The battery room must comply with the following safety conditions:
• Adequate ventilation using mechanical extractors to expel accumulated gases and ensure
proper air circulation.
• Acid-resistant thermal ceramic flooring to withstand electrolyte spills and maintain
cleanliness and durability.
• Explosion-proof lighting switches, which must be located outside the room whenever
possible. If installed inside, switches must be certified for hazardous environments.
• Metal doors that open outward, allowing quick and safe exit in case of emergency; wooden
doors are prohibited due to flammability.
• Emergency water basin with a foot-operated faucet, installed inside the room. In case of
accidental exposure to battery acid or alkali, operators can rinse affected areas especially the
face and hands, without using their hands to activate the water flow.
These safety precautions help minimize risks associated with chemical exposure and hydrogen
accumulation, ensuring a safe environment for personnel working with battery systems.
• 48 V chargers
Page | 61
Each charger is connected to its respective DC distribution panel, which supplies a group of
designated DC loads. Every panel includes a built-in meter that displays both the output voltage
and the load current, allowing operators to monitor charger performance in real time.
Batteries can be charged through one of two methods:
• Float Charging (Charging During Operation):
The battery remains continuously connected to the charger. This method compensates for
natural self-discharge and ensures the battery remains fully charged and ready at all times.
• Equalizing Charge (Fast Charging):
A higher-than-normal voltage is applied to the battery to ensure full activation. This method
is typically used during:
o Initial commissioning
o Post-maintenance procedures
The equalizing charge usually lasts 8 hours or more, depending on battery type and
condition.
Proper operation and maintenance of the charger system are critical for ensuring the reliability of
the DC auxiliary power supply and the long-term health of the battery bank.
Page | 62
Chapter (5) Grounding System
5.1 Introduction
A grounding system is an essential part of any electric system. It interconnects the equipment
neutrals, equipment housings, lightning masts, surge arresters, overhead ground wires, and
metallic structures, placing them at Earth’s potential.
The subject of grounding systems in substations made up of a network of conductors
interconnecting the metallic parts of equipment and structures, and an arrangement of buried
conductors providing an electrical connection to the earth.
5.2 Objective
The objective of a grounding system may be summarized as follows:
• To provide safety to personnel during normal and fault conditions by limiting step and touch
potential.
• To assure correct operation of electrical devices.
• To prevent damage to electrical apparatus.
• To dissipate lightning strokes.
• To stabilize voltage during transient conditions and therefore minimize the probability of
flashover.
Page | 63
5.3.1 The Grounding Network
The grounding network contains the conductors responsible for offering a low impedance path
between the equipment frames or metallic structures and the connection to the earth. This network
should have high reliability because the breaking of a ground connection can cause safe equipment
to become dangerous.
The usual practice is connecting the equipment frames and metallic structures individually to the
ground electrode with copper conductors or straps.
The equipment 4, located at another substation, has a separate connection to the earth. By using
the grounding conductor, the ground connections of the two substations work in parallel; this is
generally beneficial as it reduces the return of current through the ground, lessening the surface
potential gradients.
Without the grounding conductor, all ground fault current from equipment 4 will return through
the earth. The connection to the earth in both substations should have low impedance, so that the
ground fault current magnitude will be large enough to activate the overcurrent protection system,
clearing the fault, and the generated surface potential gradients will be safe.
5.3.2b Ring
The ring system consists of a conductor placed around the area occupied by the substation
equipment and structures and connected to each one by short links. It is an economical and efficient
system that reduces the significant distances of the radial system. The surface potential gradients
decrease because the ground-fault current travels through several prearranged paths.
Page | 64
5.3.2c Grid
The grid system is usual. It consists of a grid of horizontally arranged copper conductors,
embedded a little below grade, and connected to the substation equipment and metallic structures;
grounding rods can be added to reach layers of lower resistivity at a greater depth. This system is
the most effective but also the most expensive.
A special case of the touch voltage where a voltage is transferred into or out of the substation from
a remote or external substation site is called the transferred voltage.
Page | 65
Figure 39 : Basic shock situations
Page | 66
5.7.2 Earthing Transformers
Used at 3.3 kV and 13.8 kV levels to:
• Provide a ground reference point for ungrounded systems.
• Allow zero sequence current flow during line to ground faults.
• Typically connected in zig zag Transformer.
• Rated around 800 A.
Page | 67
5.8 Grounding Design Steps :
The Flowchart Describes the Design Procedures of Substation Grounding:
Page | 68
5.9 Soil Resistivity Measurement Methods
Soil resistivity measurement is a critical step in designing grounding systems for substations, as it
directly influences ground resistance, ground potential rise (GPR), and safety parameters like touch
and step voltages.
5.9.1 Wenner Four Pin Method
• The most widely used technique.
• Involves placing four equally spaced probes in a straight line, injecting current through the
outer two probes, and measuring voltage between the inner two probes.
• Soil resistivity is calculated using the formula 𝜌 = 2𝜋𝑎𝑅, where a is the probe spacing and
R is the measured resistance.
• By varying probe spacing, resistivity at different depths is obtained, enabling the
development of a soil resistivity profile or multilayer soil model.
• Measurements are taken along multiple profiles and orientations to ensure accuracy and
detect anomalies.
• Depth of measurement corresponds approximately to the probe spacing, so increasing
spacing probes deeper layers.
• This method is mandated by standards such as those used by National Grid Electricity
Distribution and IEEE.
Page | 69
5.9.2 Schlumberger Method
This method involves the inner probes to be placed closer together and the outer probes further
apart. Unlike the Wenner method where all of the probes need to be repositioned whenever testing
needs to be done at the particular location, the Schlumberger method only requires that outer probes
to be repositioned for varying measurements. As a result, measurements from the tests can be
performed quicker and economy of manpower is gained.
Page | 70
5.10 Grounding System in our Substation Using Excel
5.10.1 Calculation of conductor cross section according to IEEE std 80
Page | 71
5.10.2 calculation of ground resistance according to IEEE std 80
5.10.3 Maximum permissible value of step and touch voltage according to IEEE std
80
Page | 72
5.10.4 mesh and step voltage calculations according to IEEE std/80
Page | 73
Figure 45 :Grid of Grounding Grid 3D View
Page | 74
Chapter (6) Protection
6.1 Protective Relays
Distance protection, in its basic form, is a non-unit protection offering considerable
economic and technical advantages. Unlike overcurrent protection, the key advantage of
distance protection is that its fault coverage of the protected circuit is virtually independent
of source impedance variations. In the next example, overcurrent protection cannot be
applied satisfactorily. Also, it can provide both primary and remote backup functions in a
single scheme. It can easily be adapted to create a unit protection scheme when applied
with a signaling channel.
Page | 75
The operating characteristic of the impedance relay is shown by means of “Impedance
diagram’’ or the “R – X diagram”.
Any value of Z less than the radius of the circle will result in producing a positive torque.
Any value of Z greater than the radius of the circle will produce a negative torque
regardless of the phase angle between V & I.
• Reversal of current through the relay from IF1 to IF2 when C opens could then result
in incorrect tripping of the healthy line if the directional unit operates before the
impedance unit resets
Page | 76
• This is an example of the need to consider the proper coordination of multiple relay
elements to attain reliable relay performance during evolving fault conditions
• In older relay designs, the type of problem to be addressed was commonly referred
to as one of “contact race”.
Page | 77
6.1.1d Offset Mho Characteristic:
If the current bias is employed, the mho characteristic is shifted to cover the origin, so
that the measuring element can operate or close-up faults in both forward and reverse
directions.
The offset mho relay has two main applications:
• Third Zone and Busbar Back-up Zone.
✓ In this application it is used in conjunction with mho measuring units as a fault
detector and/or Zone 3 measuring unit.
✓ With the reverse reach arranged to extend into busbar zone.
✓ It will provide back-up protection for busbar faults. This facility can also be
provided with quadrilateral characteristics.
Page | 78
Figure 54 : Carrier Starting Unit in Distance Schemes with Carrier Blocking
✓ This is especially true for earth fault impedance measurement, where the arc
resistances and fault resistance to earth contribute to the highest values of fault
resistance.
✓ Quadrilateral characteristic is highly flexible in terms of fault impedance
coverage for both phase and earth faults.
✓ For this reason, most numerical distance relays now offer this form of characteristic.
Page | 79
6.1.1g Lenticular Characteristic
There is a danger that the offset mho relay may operate under maximum load transfer
conditions if Zone 3 of the relay has a large reach setting.
✓ A large Zone 3 reach may be required to provide remote back- up protection for
faults on the adjacent feeder.
✓ To avoid this, a shaped type of characteristic may be used, where the resistive
coverage is restricted.
𝒂
✓ With a lenticular characteristic, the aspect ratio of the lens is adjustable, enabling
𝒃
it to be set to provide the maximum fault resistance coverage consistent with non-
operation under maximum load transfer conditions.
✓ The figure shows how the lenticular characteristic can tolerate much higher degrees
of line loading than offset mho and plain impedance characteristics, while
reduction of load impedance from 𝑍𝐷3 to 𝑍𝐷1 will correspond to an equivalent
increase in load current.
✓ Numerical relays typically do not use lenticular characteristic, but instead use load
encroachment (load blinder) detection.
✓ This allows a full mho characteristic to be used, but with tripping prevented in the
region of the impedance plane known to be frequented by load
(𝑍𝐴 − 𝑍𝐵 − 𝑍𝐶 − 𝑍𝐷 )
Page | 80
6.1.2 Differential Relay
6.1.2a High Impedance for Busbar
High impedance protection system is a simple technique which requires that all CTs used in the
protection scheme have relatively high knee point voltage, similar magnetizing
characteristic and the same ratio.
These CTs shall be installed in all ends of the protected object. In order to make the
scheme, all CTs belonging to one phase shall be connected in [Link] high
impedance differential scheme is shown in the opposite figure. Note that only one phase
is shown in this figure. Due to the parallel CT connections the high impedance
differential relay can only measure the operating quantity.
That means that there is no any stabilizing quantity in such schemes. Therefore in order to
guaranty the stability of the relay during external faults the operating quantity must not
exceed the set pickup value.
For external faults, even with severe saturation of some of the current transformers, the
voltage across the CT paralleling point shall not rise above the relay pickup value.
To achieve that a suitable value for setting resistor Rs shall be selected in such a way that
the saturated CT provides a much lower impedance path as compared with the measuring
branch.
Thus, in case of an external fault causing current transformer saturation, the non-saturated
current transformers will drive most of the spill differential current through the secondary
winding of the saturated current transformer and not through the measuring branch. The
voltage drop across the saturated current transformer secondary winding will appear also
across the measuring branch; however it will typically be relatively small. Therefore, the
pick-up value of the relay has to be set above this false operating voltage.
In case of an internal fault, the fault current tries to flow through the measuring branch.
Due to high ohmic value of setting resistor this will result in a steep voltage increase
across the whole scheme and fast saturation of all current transformers. The differential
relay is designed to operate under such conditions.
To ensure reliable operation with internal faults, the knee-point voltage of the current
Page | 81
transformers used in the scheme must be about two times the set pickup voltage.
Often the non-linear resistors are required in order to limit the over voltages during
internal fault to less than 2kV peak value, which is standard insulation level for used for
secondary equipment and wiring.
Low-impedance bus differential relays are so named because the differential relay current
inputs have a low impedance to the flow of CT secondary current. This means that the
low- impedance bus differential relays can share the CTs with other relays, meters,
transducers, etc.
The low impedance bus differential scheme typically has one set of current inputs for
each phase from every set of CTs in the scheme.
Distributed busbar protection scheme, as shown in Figure, which uses Data Acquisition Units
(DAUs) installed in each bay to sample and pre-processes the signals and provides trip
rated output contacts. It uses a separate Central Unit (CU) for gathering and processing
all the information and fiber-optic communications between the CU and DAUs to deliver
the data.
The main advantages of this scheme is reduced wiring, however the architecture of this
scheme is less reliable due to complexity in data transfer.
Page | 82
6.1.2c Transformer Differential Relay Protection:
The Differential Protection of Transformer has many advantages over other schemes of
protection:
1) The faults occurring in the transformer inside the insulating oil can be detected by
Buchholz relay. But if any fault occurs in the transformer but not in oil then it
cannot be detected by Buchholz relay. Any flash over at the bushings are not
adequately covered by Buchholz relay. Differential relays can detect such type of
faults. Moreover, Buchholz relay is provided in transformer for detecting any
internal fault in the transformer but Differential. Protection schemes detect the
same in faster way.
2) The differential relays normally response to those faults which occur inside the
differential protection zone of the transformer. Differential Protection Scheme in a
Power Transformer. Principle of Differential Protection scheme is one simple
conceptual technique. The differential relay actually compares between primary
current and secondary current of power transformer, if any unbalance found in
between primary and secondary currents the relay will actuate and inter trip both
the primary and secondary circuit breaker of the transformer.
Suppose you have one transformer which has primary rated current Ip and secondary
current Is. If you install CT of ratio Ip/1A at the primary side and similarly, CT of ratio
Is/1A at the secondary side of the transformer. The secondaries of these both CTs are
connected together in such a manner that secondary currents of both CTs will oppose each
other.
In other words, the secondaries of both CTs should be connected to the same current coil
of a differential relay in such an opposite manner that there will be no resultant current in
that coil in a normal working condition of the transformer. But if any major fault occurs
Page | 83
inside the transformer due to which the normal ratio of the transformer disturbed then the
secondary current of both transformers will not remain the same and one resultant current
will flow through the current coil of the differential relay, which will actuate the relay
and inter trip both the primary and secondary circuit breakers. To correct phase shift of
current because of star-delta connection of transformer winding in the case of three-phase
transformer, the current transformer secondary should be connected in delta and star as
shown here.
At maximum through fault current, the spill output produced by the small percentage
unbalance may be substantial. Therefore, differential protection of transformer should be
provided with a proportional bias of an amount which exceeds in effect the maximum
ratio deviation.
• Instantaneous overcurrent relay operates without time delay, so they are called instantaneous
units. However, its operation can be delayed after a specified time according to the
application.
Page | 84
• Definite time relay operates with some time delay, and this delay is adjustable as well as the
pickup setting.
• Inverse time overcurrent relay has an operating time depending on the value of the current.
Generally, with an inverse characteristic, the operation time of the relay is smaller as
the current gets larger.
Page | 85
Where:
𝑰
• 𝑰𝒓 = , I is the measured fault current, and Is is the relay setting current (PS for
𝑰𝒔
electromechanical relay).
• 𝑇𝑀𝑆 is the time Multiplier setting, and T is the relay operating time in sec.
✓ ANSI Overcurrent relays also have different equations, as follow: TD is the time dial or
called time dial setting (TDS)
Characteristic Equation
𝑇𝐷 0.0515
IEEE Moderately Inverse 𝑡= [( ) + 0.114]
7 𝐼𝑟0.02 − 1
𝑇𝐷 19.61
IEEE Very Inverse 𝑡= [( ) + 0.491]
7 𝐼𝑟2 − 1
𝑇𝐷 28.2
IEEE Extremely Inverse 𝑡= [( ) + 0.1217]
7 𝐼𝑟2 − 1
𝑇𝐷 5.95
US CO8 Inverse 𝑡= [( ) + 0.18]
7 𝐼𝑟2 − 1
𝑇𝐷 0.02394
US CO8 Short Time Inverse 𝑡= [( ) + 0.01694]
7 𝐼𝑟0.02 − 1
Table 5: Equations of ANSI overcurrent relay
Page | 86
6.2 Types of Substation
There are different types of substations based on the level of automation and control systems
used. The three main types are:
• Conventional Substation.
• SCADA Based Substation.
• SAS (Substation Automation System).
Page | 87
✓ Each screen displays detailed
diagrams showing the complete
substation layout, status of breakers,
isolators, alarms, measurements, etc.
✓ Operators sit in front of these screens
and control the substation remotely.
Note:
The SCADA system can be used not only in substations but in any industrial or infrastructure
project, such as water plants, oil and gas facilities, or manufacturing factories. It is a general control
system, adapted according to the required protocols and applications.
Page | 88
• Current Practice in Egypt
In Egypt, it is common to find a combination of systems such as:
✓ Conventional + SCADA
✓ Conventional + SAS
Many existing substations still rely on conventional systems for basic operation but integrate
SCADA or SAS for enhanced monitoring, control, and reliability.
This hybrid approach helps in modernizing old substations without fully replacing their
traditional infrastructure.
6.3 Protection Schemes and Associated Control & Metering Panels in
Substations
Modern substations are equipped with various protection schemes and panel systems that
work together to ensure safe and reliable operation. These systems are essential for detecting
faults, isolating affected parts of the network, and maintaining overall system stability.
Control panels provide interfaces for local and remote operation of substation equipment,
while protection units monitor system conditions and trigger necessary actions during
abnormal events. Metering panels continuously measure electrical quantities, supporting
monitoring, diagnostics, and decision-making.
This section presents an overview of the main components involved in protection, control,
and metering schemes within substations. Each will be discussed in detail to highlight its
function, configuration, and role in the overall system.
6.3.1 Local Control Panel (+W)
• Each Local Control Panel is typically installed in front of each bay in the substation. -It
allows operators to locally monitor and control the equipment in that specific bay.
• The control can be done either through pushbuttons or using a mimic diagram with
discrepancy switches, which indicate the actual position of the equipment versus the
command position.
Page | 89
• Additionally, beside each primary
equipment (like circuit breakers,
disconnectors, or earthing
switches), there is a local box
mounted for field operations.
However, this box is mainly used
for maintenance and testing
purposes only, due to the noise and
high operating force required in
the field.
➢ multi-function meter
that displays electrical quantities such as:
✓ Voltage (V)
✓ Current (I)
✓ Active Power (P)
✓ Reactive Power (Q)
✓ Power Factor (Pf)
Instead of a multi-function meter, some LCPs might use a 7-position voltage selector switch,
which allows operators to monitor:
✓ Phase-to-earth voltages (R, Y, B)
✓ Line-to-line voltages (RY, YB, BR)
And an individual ammeter is usually installed for each phase to show the current values.
➢ alarming unit
✓ which provides visual and audible indications of abnormal conditions or faults,
helping operators quickly identify issues.
✓ There’s also a test pushbutton to check that all indicator lamps on the panel are
working correctly.
• Interlocking systems
✓ are also included to enhance operational safety. For example, a disconnector cannot
be opened or closed unless the circuit breaker is already open. This is enforced
through electrical or mechanical interlocks.
✓ in emergency situations, there is a feature called Interlock Bypass. It consists of a
selector switch with a key, and it allows authorized personnel to override the
interlocking logic — but only under special circumstances, and with extreme caution.
Page | 90
6.3.2 Remote Control Panel (+P)
The Remote Control Panel (RCP) is located in the substation control room and provides centralized
monitoring and control of bays and equipment. It contains several key components:
• Bay Control Unit (BCU)
✓ Acts as the brain of the panel.
✓ Performs the function of a multifunction
meter, displaying:
➢ Voltage (V)
➢ Current (I)
➢ Active and reactive power (P & Q)
➢ Power factor (Pf)
✓ Can serve as a backup control unit,
especially in 66 kV substations.
• Alarm Unit
✓ Provides visual and audible alerts for faults or abnormal conditions.
✓ Helps operators quickly detect and respond to system issues.
➢ 66 kV Systems:
Page | 91
− Use Main + Backup Relays.
− Power levels are lower, so one main protection and one backup are sufficient.
− In the substation studied (66 kV), the backup relay can either be a separate
physical device Or integrated inside the BCU.
✓ Test Plug
➢ Used during relay testing and commissioning.
➢ Allows the engineer to inject current or voltage into the relay.
➢ Simulates real fault conditions to check:
− Whether the relay detects the fault properly.
− Whether it sends the correct trip signal.
Page | 92
✓ Energy Meter
➢ Measures active energy (kWh), reactive
energy (kVARh), and sometimes apparent
energy (kVAh).
➢ Very high accuracy (Class 0.2S or 0.5S).
➢ Used for billing and auditing purposes.
• When a fault occurs on the busbar, it is crucial to trip all the circuit breakers connected to the
affected section in order to isolate the fault as quickly as possible.
• Busbar Differential Protection detects internal faults by comparing currents entering and
leaving the busbar using Kirchhoff’s Current Law.
Page | 93
High Impedance Scheme connects
CTs in parallel with a high-impedance
relay; it detects faults based on voltage
rise caused by unbalanced currents.
Low Impedance Scheme uses a
modern relay that measures each CT
input separately, compares them
digitally, and applies restraint logic for
accurate fault detection.
Choosing between distributed and centralized busbar protection depends on the size of the
substation, complexity, and reliability requirements. While distributed systems offer
flexibility and scalability, centralized systems provide simplicity and centralized control.
Both aim to detect faults rapidly and isolate the busbar to prevent damage and maintain
power system stability
Page | 94
6.4 Types of Bays in a Substation
In a substation, a bay refers to a distinct section or unit that contains all the necessary equipment
for a specific function in the power system. Bays are typically categorized based on their role and
the type of equipment they connect to. The main types include:
Line Bay
Connects the substation to overhead transmission lines, underground cables, or mixed lines.
Transformer Bay
Connects power transformers to the substation’s busbars, enabling voltage level changes between
transmission and distribution systems.
Bus Coupler Bay
Connects two busbars together and allows flexibility in load sharing, maintenance, and fault
isolation.
Protection Schemes
The protection system varies depending on the line type:
✓ Overhead Transmission Line (OHTL):
Protected primarily using Distance Protection which detects faults
based on the impedance seen by the relay.
✓ Cable Line:
Protected using Differential Protection, as cables have low and
Figure 66: Line Bay
consistent impedance, making differential protection highly
effective.
✓ Mixed Line (OHTL + Cable):
Also typically protected using Distance Protection, although special coordination is needed
due to the differing characteristics of the cable and overhead line segments.
✓ Current Transformers (CTs)
For a 66 kV Line Bay, the typical CT arrangement includes 3 cores per phase:
➢ Measurement Core:
Used for feeding signals to the Multifunction Meter (MF), Bay Control Unit (BCU), and
Energy Meter (EM).
➢ Protection Core:
Dedicated to Main and Backup Protection Relays, ensuring accurate and reliable fault
detection.
➢ Busbar Protection Core:
Page | 95
Utilized for Busbar Protection, which safeguards the entire busbar zone against internal
faults.
-These relays operate based on the residual current. If a neutral is present, it is monitored
directly. If not, the sum of the three-phase currents (𝐼𝑎 + 𝐼𝑏 + 𝐼𝑐 ) is calculated. Under normal
conditions, this sum should be zero. If it exceeds a certain threshold, it indicates a ground fault.
Page | 96
Figure 67 : Protection Scheme of Line Feeder
• Protection Schemes
✓ The main protection scheme for power transformers is the
Differential Protection. This protection method operates based Figure 68 : Transformer Bay
on the principle of Kirchhoff’s Current Law, which states that
the current entering the transformer should be equal to the current leaving it (after accounting
for the turns ratio).
✓ Current Transformers (CTs) are installed on both the primary and secondary sides of the
transformer. Under normal conditions, the differential current (the difference between
primary and secondary currents, adjusted by the CT ratio) is nearly zero. However, if an
internal fault occurs within the transformer (such as winding short-circuit or insulation
failure), a significant differential current appears, which triggers the protection relay to
isolate the transformer.
✓ It is important to note that while Transformer Differential Protection compares currents
locally at the transformer terminals, the Line Differential Protection, especially in cable
connections, operates differently. Line differential schemes require real-time communication
between both ends of the line to exchange current measurements. This ensures accurate fault
detection along the length of the cable by comparing the current entering and exiting the line.
• Current transformers(CTs)
Page | 97
For the primary side (66kv), the typical CT arrangement includes 4 cores per phase:
✓ Measurement Core:
Used for feeding signals to the Multifunction Meter (MF), Bay Control Unit (BCU), and
Energy Meter (EM).
✓ Protection Core:
Dedicated to Main and Backup Protection Relays, ensuring accurate and reliable fault
detection.
Page | 98
the transformer windings, specifically in the zone between the phase CTs and the neutral
point. It works by summing the currents of all three phases and comparing them to the
current flowing through the neutral CT.
− Under normal conditions, the sum of the phase currents should equal the neutral current.
However, in case of an internal winding fault, such as a short circuit between a few turns, a
portion of the fault current will flow through the neutral, causing an imbalance. This
imbalance is detected by the REF relay, which then issues a trip signal.
− REF is more sensitive than the main differential protection, as it is focused on a smaller
zone and can detect low-magnitude internal faults that might not trigger the main
differential relay.
Page | 99
All these mechanical devices are connected to the main protection relay using auxiliary contacts,
allowing centralized monitoring, alarming, and tripping functions. This integration ensures that
both electrical and mechanical conditions are effectively supervised and acted upon.
Page | 100
6.4.3 Coupler Bay
• The Coupler Bay in a substation plays a key role in
enhancing operational flexibility and system reliability. It
is used to interconnect two busbars (typically in a double
busbar scheme), allowing the transfer of loads or feeders
from one busbar to another without interruption. This bay
provides switching flexibility during maintenance, fault
isolation, or load balancing between bus sections.
• Protection Schemes
✓ The protection of the Coupler Bay must strike a balance between speed, selectivity, and
coordination with surrounding bays and the overall busbar protection system.
▪ Busbar protection is the main protection for the coupler bay.
▪ 51 / 51N act as backup protections for abnormal current flow.
✓ Measurement Core:
Used for feeding signals to the Multifunction Meter (MF), Bay Control Unit (BCU), and
Energy Meter (EM).
✓ Protection Core:
Dedicated to Main and Backup Protection Relays, ensuring accurate and reliable fault
detection.
✓ Busbar Protection(2 Cores):
Utilized for Busbar Protection, which safeguards the entire busbar zone against internal
faults.
Page | 101
Chapter (7) CT and VT Sizing
7.1 Current Transformer
A current transformer is defined as “as an instrument transformer in which the secondary current
is substantially proportional to the primary current (under normal conditions of operation) and
differs in phase from it by an angle which is approximately zero for an appropriate direction of the
connection.
7.1.1 Functions
Adapting the current value at the primary to the characteristics of the metering or protection
devices by supplying a secondary current with a reduced, but proportional current value.
Isolating power circuits from the metering and/or protection circuit.
7.1.2 Types
• High remanence type CT.
• Low remanence type CT.
• Non remanence type CT.
Page | 102
Figure 75 :CT magnetization curve
• Protection CT
This requires good accuracy at high currents and will have a higher precision limit (linearity
zone) for protection relays to detect the protection thresholds that they are meant to be
monitoring.
✓ 𝐼1 : primary current.
✓ 𝐼2 : primary current divided by the turns ratio for a perfect CT.
✓ 𝐼𝑠 : secondary current actually flowing through the circuit.
✓ 𝐼𝑚 : magnetizing current.
✓ 𝐿𝑚 = magnetization inductance equivalent to the CT
✓ 𝑉𝑆 = Voltage across secondary of transformer
✓ 𝑅𝑐𝑡 = resistance at the CT secondary
✓ 𝑅𝑝 = burden resistance
Page | 103
7.1.4 Specifications of CT
• Rated Primary Current
This is referring to the value of primary current which appears in the designation of the
transformer, and on which the performance of the current transformer is based.
• Rated Burden
This is referring to the apparent power of the secondary circuit in Volt-amperes expressed at
the rated secondary current and at a specific power factor (0.8 for almost all standards).
• Accuracy Class
In the case of metering CT s, accuracy class is typically, 0.2, 0.5, 1 or 3.
This means that the errors have to be within the limits specified in the standards for that
particular accuracy class.
The metering CT has to be accurate from 5% to 120% of the rated primary current, at 25%
and 100% of the rated burden at the specified power factor.
In the case of protection CTs, the CTs should pass both the ratio and phase errors at the
specified accuracy class, usually 5P or 10P, as well as composite error at the accuracy limit
factor of the CT.
Page | 104
Table 7:Accuracy Class of protection CT
Page | 105
7.1.5 CT sizing
7.1.5a Determine CT ratio
Get the operating current of the line which subjected to put the CT on it and multiply it by
1.2 as safety factor.
Then Get the secondary operating current from the relay that will be used if the input
current is 5A or 1 A.
MVA ∗ 103
𝐼𝑟𝑎𝑡𝑒𝑑 = , 𝐼 ≥ 1.2 𝐼𝑟𝑎𝑡𝑒𝑑
√3 ∗ 𝐾𝑉
7.1.5c CT Burden
• CT burden is an impedance of secondary circuit expressed in ohms.
• CT Burden can be expressed in two terms as example: 0.5 ohm impedance 10 VA at
5A. (British method) here 5A is rated secondary current and 2Volt across secondary.
• 𝐶𝑇𝐵𝑢𝑟𝑑𝑒𝑛 = 𝑅𝑒𝑙𝑎𝑦1 𝐵𝑢𝑟𝑑𝑒𝑛 + 𝑅𝑒𝑙𝑎𝑦2 𝐵𝑢𝑟𝑑𝑒𝑛 + 𝑅𝑒𝑙𝑎𝑦3 𝐵𝑢𝑟𝑑𝑒𝑛 + ⋯ + ⋯
Page | 106
7.1.6 CTs Cores in our substation
7.1.6a Protective Core for incoming lines
Page | 107
7.1.6b Measurement Core for incoming lines
Page | 108
7.1.6c Protective Core for 3 winding transformer (3.3KV)
Page | 109
7.1.6d Measurement Core for 3 winding transformer (3.3KV)
Page | 110
7.1.6e Protective Core for 3 winding transformer(66KV)
Page | 111
7.1.6f Measurement Core for 3 winding transformer (66KV)
Page | 112
7.1.6g Protective Core for 2 winding transformer(13.8kV)
Page | 113
7.1.6h Measurement Core for 2 winding transformer(13.8kV)
Page | 114
7.1.6i Protective Core for 2 winding transformer(66KV)
Page | 115
7.1.6j Measurement Core for 2 winding transformer(66KV)
Page | 116
7.1.6k Protective Core for motors (13.8kV)
Page | 117
7.1.6l Measurement Core for motors (13.8KV)
Page | 118
7.1.6m Protective Core for Aux.
Page | 119
7.1.6n Measurement Core For Aux.
Page | 120
7.1.6o Protective Core for Coupler(13.8kV)
Page | 121
7.1.6p Measurement Core for Coupler(13.8kV)
Page | 122
7.1.6q Protective Core for Coupler (66kV)
Page | 123
7.1.6r Measurement Core for Coupler(66kV)
Page | 124
7.2 Voltage Transformer
7.2.1 Introduction to Voltage Transformers
Voltage Transformers (VTs), also known as potential transformers (PTs), are a type of
instrument transformer used to step down high voltages to lower, standardized voltages for
metering, protection, and control in power systems. They allow measurement and monitoring
equipment to safely operate with high voltage levels indirectly.
Figure 78 : Inductive
7.2.2b Capacitive Voltage Transformers (CVTs) Voltage Transformers
Page | 125
Feature Inductive VT Capacitive VT
Frequency response Better for protection Suitable for high voltage metering
7.2.3 VT Sizing
• Voltage ratio (ex: 220KV/100V or 110V).
• Total burden of devices + VT Cores + Cables < VT burden.
• Accuracy class (ex: 3P for protection and 0.5M for measurement).
Page | 126
7.2.3a VT for 66KV Bus
Page | 127
7.2.3b VT for 13.8KV Bus
Page | 128
• Accuracy Class of Voltage Transformers
The accuracy class defines the permissible error limits of a VT under specified conditions. It
is important in ensuring the correct operation of measuring and protection devices.
Page | 129
✓ Double Frequency Meter
In a substation, the double frequency meter ensures that the
power system operates at a consistent frequency. It monitors and
displays the frequency of two sources, which is essential when
interconnecting different parts of the grid or integrating power
from multiple generators.
✓ Synchroscope
The synchroscope is critical for safely synchronizing generators
and linking separate network segments within the substation. It
provides a visual indication of the phase difference between two
voltage sources, ensuring that they are in sync before connecting
them.
Figure 81 :Synchroscope
• Conclusion
In a substation setting, these devices serve as crucial components for monitoring and controlling
power flow, ensuring system stability, and protecting equipment:
Page | 130
Chapter (8) Relay Coordination
The Fundamentals of protection relay co ordination and time/current graphing
principles:
8.1 The importance of overcurrent protection
Transmission and distribution systems are exposed to overcurrent flow into their elements. In an
electric power system, overcurrent or excess current is a situation where a larger than intended
electric current exists through a conductor, leading to excessive generation of heat, and the risk of
fire or damage to equipment.
Possible causes for overcurrent include short circuits, excessive load, transformer inrush current,
motor starting, incorrect design, or a ground fault.
Therefore, for normal system conditions, some tools such as demand – side management, load
shedding, and soft motor starting can be applied to avoid overloads. In order for the relay to operate,
it needs to be energized. This energy can be provided by battery sets (mostly) or by the monitored
circuit itself.
This chapter deals with co-ordination between protection relays in general and principles of
Time/Current grading used to achieve correct relay co-ordination.
1) Coordination procedure
2) Principles of Time/Current grading
3) Discrimination by Time
4) Discrimination by Current
5) Discrimination by both Time and Current.
Page | 131
give correct discrimination. Each one must isolate only the faulty section of the power system
network, leaving the rest of the system undisturbed.
• Discrimination by Time:
In this method, an appropriate time setting is given to each of the relays controlling the circuit
breakers in a power system to ensure that the breaker nearest to the fault opens first. A simple
radial distribution system is shown in the following figure, to illustrate the principle.
Overcurrent protection is provided at B, C, D and E, that is, at the infeed end of each section of the
power system.
Each protection unit comprises a definite-time delay overcurrent relay in which the operation of the
current sensitive element simply initiates the time delay element. Provided the setting of the current
element is below the fault current value, this element plays no part in the achievement of
discrimination.
For this reason, the relay is sometimes described as an ‘independent definite-time delay relay’, since
its operating time is for practical purposes independent of the level of overcurrent.
It is the time delay element, therefore, which provides the means of discrimination. The relay at B is
set at the shortest time delay possible to allow the fuse to blow for a fault at A on the secondary side
of the transformer.
After the time delay has expired, the relay output contact closes to trip the circuit breaker. The relay
at C has a time delay setting equal to t1 seconds, and similarly for the relays at D and E.
If a fault occurs at F, the relay at B will operate in t seconds and the subsequent operation of the
circuit breaker at B will clear the fault before the relays at C, D and E have time to operate.
The time interval t1 between each relay time setting must be long enough to ensure that the
upstream relays do not operate before the circuit breaker at the fault location has tripped and cleared
the fault.
The main disadvantage of this method of discrimination is that the longest fault clearance time
occurs for faults in the section closest to the power source, where the fault level (MVA) is highest.
Page | 132
• Discrimination by Current:
Discrimination by current relies on the fact that the fault current varies with the position of the fault
because of the difference in impedance values between the source and the fault.
Page | 134
8.2 Relay coordination Using ETAP:
Page | 135
Figure 85 : Relay Settings
Overcurrent instantaneous
Relay ID
Pickup time pickup time
Relay158 1.75 0.54 30.95 0.35
incomers Relay370 1.2 0.05 7.86 0.015
Relay347 0.7759 0.23 12.05 0.125
Relay259 0.99 0.35 17.45 0.265 Directional
Relay325 1.083 0.05 10.29 0.015 Directional
Load Side
Relay134 0.826 0.05 6.75 0.04 Directional
Relay18 0.733 0.2 6.475 0.085 Directional
Relay9 1.75 0.39 24.46 0.19
Coupler
Relay373 0.7759 0.25 12.05 0.18
Primary Relay23 2.88 0.32 25.57 0.265
side of
trans. Relay57 1.2 0.05 7.86 0.015
Table 9 : Relay Settings
Page | 136
8.2.1 Three phase Fault at Booster Motor
Page | 137
8.2.2 Fault at 13.8 kV bus
Page | 138
8.2.3 Fault at VFD Motor
Page | 139
8.2.4 Fault at 3.3 kV bus
Page | 140
8.2.5 Fault at primary side of three windings transformer
Page | 141
8.3 Protection Star Views
Figure 86 : star view for Booster motor and its protective relay
Page | 142
Figure 87 :Star view for the selected relays at 13.6 KV level
Page | 143
Figure 88:3Star view for relays of 3 winding bay
Page | 144
Figure 89:Star view of LVCB and cable connected to lambed load
Page | 145
Chapter (9) Lightning Protection and surge arrestor
9.1 Lightning Protection
Before starting the lightning protection design, it is a routine step to assess whether the building
actually requires lightning protection or not.
This is done through an Excel sheet where several factors are entered to determine the need for
protection.
9.1.1 Selected factors
● Building Dimensions:
As shown in the attached image, for our substation case, we need to enter the dimensions of
buildings like the Control Building, GIS Building, and MV Switchgear Building.
● Factor 𝑪𝟏 :
20.0
30
● This relates to whether the building is isolated or surrounded by tall objects like trees.
● Factor 𝑪𝟐 :
This relates to the building material whether it is metallic or non-metallic.
Page | 146
● Factor 𝑪𝟑 :
This concerns the importance of the building contents — whether they are critical or involve
flammable materials.
● Factor 𝑪𝟒 :
This factor depends on the occupancy type of the building.
• Factor 𝑪𝟓 :
This relates to the consequences of a lightning strike whether it would impact the surrounding
environment
Page | 147
Where
✓ 𝑁𝑔 : Average Flash Density
✓ 𝐴𝑒 : Collective Area
✓ 𝐶1 : Location Factor
If 𝑁𝑑 is less than 𝑁𝑐 , then lightning protection is optional.
If 𝑁𝑑 is greater than 𝑁𝑐 , lightning protection becomes mandatory.
In our substation case, it is expected that we will definitely need to implement lightning protection.
Afterward, we determine the required Class of Protection based on the calculated 𝑁𝑑 and 𝑁𝑐
values.
Since lightning strikes in a substation are considered very critical and dangerous, the Class of
Protection is confirmed to be Class I
9.1.2 Selected Protection Level
𝑵𝒄
𝑬≥𝟏−
𝑵𝒅
Page | 148
9.1.3 Design Phase
9.1.3a Air Termination System
In the design stage, a mesh system is created on the rooftop of the building, and air terminal rods
are installed at specific intervals.
The Protection Class determined earlier is used to refer to standard tables to decide:
✓ How far apart the rods should be.
✓ The mesh dimensions (spacing between conductors).
Page | 149
9.1.3c Down Conductors
A down conductor is used to transfer the lightning current from the mesh or rods down to the
ground through the nearest concrete column.
According to the standard:
● For every 10 meters of building perimeter, a down conductor must be installed.
● Each down conductor is connected to the nearest concrete column.
Note:
If using the station grounding system, it is recommended to have circuit breakers that disconnect
loads during a lightning event.
However, the best practice is to separate the two grounding systems.
2.4 Implementation Example
Below is an AutoCAD excerpt showing the actual application on the project site:
Page | 150
● Air Termination Rods have been installed on perimeter walls and fire walls separating
transformers, to ensure coverage across most of the substation.
● Access Roads that are not yet covered are being equipped with poles carrying air termination
rods, to cover the entire station including the roadways.
Page | 151
9.2 Surge Arrester Sizing
9.2.1 Introduction
Surge arresters play a crucial role in protecting electrical equipment from overvoltage transients
caused by switching operations or lightning strikes.
This document outlines the step by step methodology used to determine the appropriate surge
arrester rating for our system.
A standard flowchart is followed for the sizing process:
Page | 152
9.2.2 Determination of Minimum Rated Voltage
The first step is to determine the Maximum System Voltage (Us). According to IEC standards, a
margin of 10% is considered when selecting surge arresters.
For a 66 kV system: Us ≈ 42 kV
To determine the minimum rated voltage, we refer to a standard IEC table that requires the
following inputs:
● System Earthing Type (Effectively Grounded or Non-Effectively Grounded)
● Fault Duration (In our case, 1 second)
From the table, we select the minimum rated voltage corresponding to the system earthing type.
Since our system is effectively grounded (solidly earthed, without neutral resistance), we use the
first row in the table.
Page | 153
capability of the arrester for different time durations, the following curve is an example for TOV
curve for a surge arrester :
● Step 1: Enter the curve using the fault duration (1 second).
● Step 2: Read the corresponding TOV capability value.
The selected surge arrester must withstand the maximum expected temporary overvoltage for
the given fault duration.
If this condition is not met, a higher rated surge arrester must be selected.
Page | 154
𝑼𝒑𝒍 𝑼𝒑𝒔
From the selected arrester family, we use the following table to extract the values of and
𝑼𝒓 𝑼𝒓
Page | 155
9.2.7 Selection of Final Surge Arrester Rating
From the PEXLIM R-Y family catalog, we determine the required arrester specifications:
● The maximum system voltage is ~42 kV.
● The corresponding Rated Voltage (Ur) is selected as 42 kV.
The Maximum Continuous Operating Voltage (MCOV) is chosen as 52 kV, based on IEC
selection criteria.
Page | 156
9.2.8 Conclusion
Correct surge arrester selection is essential to prevent overvoltage damage to electrical equipment.
This process involves:
1. Determining the Maximum System Voltage and selecting an arrester with an appropriate
rated voltage.
2. Verifying the TOV withstand capability for system stability.
3. Choosing the appropriate arrester class based on IEC standards.
4. Ensuring that the protection levels (Upl and Ups) are within system insulation withstand
limits.
5. Calculating the protection margin to confirm safe operation.
By following this methodology, we have successfully selected a PEXLIM R-Y surge arrester with
a 42 kV rated voltage and 52 kV MCOV, ensuring adequate protection against lightning and
switching overvoltage in our system
Page | 157