0% found this document useful (0 votes)
67 views12 pages

RS 2001 Protective Relay Manual

The document provides operating instructions for the Protective Relay RS 2001, detailing its design, installation, commissioning, and response mechanisms. It emphasizes safety precautions and proper usage to prevent equipment damage and personal injury. Additionally, it includes technical specifications and options for special designs of the relay.

Uploaded by

sherif elmayergy
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
67 views12 pages

RS 2001 Protective Relay Manual

The document provides operating instructions for the Protective Relay RS 2001, detailing its design, installation, commissioning, and response mechanisms. It emphasizes safety precautions and proper usage to prevent equipment damage and personal injury. Additionally, it includes technical specifications and options for special designs of the relay.

Uploaded by

sherif elmayergy
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

[Link].

com
Protective relay RS 2001
Operating Instructions BA 59
Contents

Contents

1 General ......................................................................................................................................................................................... 4
1.1 Safety instructions ....................................................................................................................................................... 4
1.2 Designated application ............................................................................................................................................... 4
1.3 Function ......................................................................................................................................................................... 4

2 Design ........................................................................................................................................................................................... 5
2.1 Housing ........................................................................................................................................................................... 5
2.2 Relay ................................................................................................................................................................................. 5

3 Mode of operation .................................................................................................................................................................. 5

4 Installation instructions .......................................................................................................................................................... 6


4.1 Assembly ........................................................................................................................................................................... 6
4.2 Electrical connection ..................................................................................................................................................... 7

5 Commissioning ............................................................................................................................................................................ 8

6 Response of the protective relay ......................................................................................................................................... 8


6.1 Flap valve in position "IN SERVICE" .......................................................................................................................... 8
6.2 Flap valve in position "OFF" ........................................................................................................................................ 8

7 Technical Data ............................................................................................................................................................................. 9

8 Special designs ............................................................................................................................................................................ 9


8.1 Protective relay with change-over contact CO .................................................................................................... 9
8.2 Protective relay with two reed switches ................................................................................................................. 9

9 Appendix ........................................................................................................................................................................................ 9

NOTE

The data described in these Operating Instructions may vary in detail from the design delivered.
We reserve the right to make alterations without notice.

059/06/01/0
3
1 General

1 General

1.1 Safety instructions 1.2 Designated application


All personnel involved in installation, commissioning,
operation, maintenance or repair of the equipment must:
- be suitably qualified and WARNING
- strictly observe these Operating Instructions.
Improper operation or misuse can lead to The serial number of the protective relay must match the
- a reduction in the efficiency of the equipment, serial number of the on-load tap-changer for which the
- damage to the equipment and property of the user protective relay is used.
and Installation, electrical connection and function check of
- serious or fatal injury. the protective relay must be carried out exclusively by
suitably qualified personnel and under strict observation
Safety instructions in this manual are presented in three of these Operating Instructions.
different forms to emphasize important information.
It is the responsibility of the user to ensure that the relay
is exclusively used for the designated application.
The non-observance of these Operating Instructions and
WARNING work carried out inappropriately during the installation,
electrical connection and function test of the protective
This information indicates particular dangers to life and relay can put the on-load tap-changer and transformer at
health. Disregarding such a warning can lead to serious or risk and lead to damage to the equipment and serious
fatal injury. injury.

1.3 Function
CAUTION The protective relay is used to protect the on-load tap-
changer and the transformer when a malfunction occurs in
This information indicates particular dangers to the equip- the diverter switch or selector switch oil compartment. It is
ment or other property of the user. Serious or fatal injury triggered when the specified oil flow between the on-load
cannot be excluded. tap-changer head and oil conservator is exceeded due to a
malfunction. Connect the protective relay so that the trans-
former is immediately disconnected when the protective
relay is tripped. Install the protective relay in the pipe
between on-load tap-changer head and oil conservator.
NOTE
Since the protective relay is part of an oil on-load tap-
This note gives important information on a certain subject. changer and its properties are subject to IEC 60214 publica-
tions in the applicable version or a future subsequent
standard, it is part of the scope of our delivery.

WARNING

Connect the protective relay in such a way to ensure that


the transformer is immediately disconnected when the
protective relay is tripped.

4 059/06/01/0
2 Design
3 Mode of operation

2 Design
MR

2.1 Housing (fig. 1: front view


fig. 2: rear view)
The housing consists of corrosion-proof light-metal and is
provided with flanges for the connection of pipes leading to
the tap-changer head and to the oil conservator.
An inspection window is located on the front side of the
housing to check the flap valve position.
The terminals of the reed switch are housed in a terminal
box, sealed from the oil chamber of the relay by oil-tight
seals. The terminal box is ventilated by a covered opening.
In addition, two test buttons in the terminal box serve for
checking the tripping function of the protective relay as well 1 KHW 848-4.1

as for resetting the flap valve.


The terminals are protected by a clear plastic screen.
1

2.2 Relay (fig. 3: protective housing open)


The actuating element of the relay consists of a flap valve
with a permanent magnet.
This magnet serves for actuating the reed switch and for 2 F.N 192 443
1.2 - NO
3
fixing the flap valve in position "IN SERVICE".
An intermediate position of the flap valve is not possible:

3 Mode of operation
1 - Cable gland M25
The protective relay responds only if oil flows occur from the 2 - Ventilation for terminal box
3 - Identification label
tap-changer head to the oil conservator. The flowing oil 2 KHW 851-4

actuates the flap valve which tips over into position "OFF".
The reed switch is thereby actuated, the circuit breakers are
tripped and the transformer is deenergized. 2

MR

NO TE
NOTE

Switching operations at rated switching capacity or at


permissible overload will not result in a response of
the protective relay.

1
3

1 - Flap valve
2 - Permanent magnet
3 3 - Reed switch KHW 852-4

059/06/01/0
5
4 Installation instructions

4 Installation instructions Test button


IN SERVICE
Test button OFF

4.1 Assembly BETRIEB AUS


RESET TRIP
SERVICE DÉCLENCHÉ
SERVIZIO INTERROTTO
DESCONEXION

Install the protective relay in the pipe leading from the tap-
SERVICIO

changer head to the oil conservator – located as near as


possible to the tap-changer head.
Prior to mounting check the function of the protective relay.
Open the cover of the terminal box at the 3 bolts M6/w. s. 10
(fig. 4) and actuate:
Test button "OFF":
flap valve is inclined (line marker appears in the middle of
the inspection window, fig. 5).
Test button "IN SERVICE":
flap valve is vertical (fig. 6). 4 Cover open KHW 853-4

Note

Do not press both test bottons at the same time.

The associated contact positions for checking of the electrical


continuity are evident from the drawing 899084 in the
appendix.
Always check the position of the flap valve.
Install the protective relay in a horizontal position and with
the test buttons upwards. The reference arrow on the termi-
nal box cover must point towards the oil conservator.
Use a pipe of at least 25 mm nominal width between
protective relay and tap-changer head/oil conservator.
Take care to install the protective relay well supported and 5 Position "OFF" KHW 849-4

protected against vibrations in this pipe connection.


The pipe to the oil conservator must be placed with an
inclination of at least 2 % to ensure free escape of
MR
switching gas.
Provide a stop valve between protective relay and oil conser-
vator (fig. 7).

Note

Install the protective relay in a place where the influcence


of magnetic fields (bushings, busbars etc.) is felt as little as
possible.

6 Position »"N SERVICE" KHW 850-4

6 059/06/01/0
4 Installation instructions

Inclination at least a continuous 2 %

a b c d e

a – On-load tap-changer
oil compartment
b – On-load tap-changer head
c – Protective relay RS 2001
d – Stop valve
e – Oil conservator

7 899759

4.2 Electrical connection


The reed switch of the protective relay can either be provided Replace the clear plastic screen and lock the cover of the
as NO or as NC contact. Other contact combinations are terminal box (3 bolts M6/w. s. 10, max. torque 5 Nm).
available as special design (see section 8).

CAUTION CAUTION
Connect the protective relay into the tripping circuit of the Do not dry the protective relay together with the active
circuit breakers of the transformer to be protected so that part of the transformer.
the transformer is immediately disconnected by the circuit
breakers when the protective relay of the transformer is
tripped. The protective relay responds to oil flow, not to gas accu-
mulated in the protective relay. It is not necessary to bleed
the protective relay when filling oil into the transformer
tank. Gas accumulation in the protective relay is normal.
For entering the leads use the thread-hole at the most
suitable side of the terminal box. Fit the cable gland and
close the other hole by the blind screw. The cable gland is
adequate for leads with an outside dia. of 10 ...19 mm.
Remove the cover of the terminal box (3 bolts M6).
Connect the leads (terminal bolt M6, max. torque 2 Nm).
Connect the protective conductor to the ground screw M6 in
the terminal box (max. torque 5 Nm).

059/06/01/0
7
5 Commissioning
6 Response of the protective relay

5 Commissioning

Repeat the test of the protective relay according to section 6.1 Flap valve in position "IN SERVICE"
4.1 when commissioning the transformer.
If the flap valve is in position "IN SERVICE", there may be a
In addition, check to make sure that the circuit breakers dis- fault in the tripping circuit. Check the tripping circuit. If this
connect on all sides the transformer to be protected when does not clarify the cause, remove and check the diverter
the "OFF" test button is pressed. switch insert or tap selector insert (visual check), see sec-
tion 6.2.
During the test make sure that
• the transformer stays disconnected,
• the grounding for work has not been removed on the 6.2 Flap valve in position "OFF"
transformer and If the flap valve is in position "OFF", it is essential to remove
• the automatic fire extinguishing device is deactivated. and examine the diverter switch insert/tap selector insert and
examine according to the relevant maintenance instructions.
Be sure that the transformer can be switched on again only
after the pushbutton "RESET" of the protective relay has Check the tripping force of the flap valve.
been pressed.
Contact MR and inquire about the tripping force, indicate
the serial no. of the on-load tap-changer.
Furthermore, the following questions must be clarified:
6 Response of the protective relay • What was the load of the transformer at the instant of
tripping?
• Was a tap-change operation performed right before or
WARNING during the tripping?
• Did any other protective devices of the transformer
Make sure to check on-load tap-changer and transformer
respond at the instant of tripping?
after the protective relay has been tripped.
Remove the diverter switch insert or the tap selector insert • Were switching operations in the network performed at
and check as described in the relevant maintenance manual. the instant of tripping?
Do not put into service before having made sure that there • Were overvoltages registered at the instant of tripping?
is no damage to on-load tap-changer and transformer. In addition to the measures described under 6.1 and 6.2,
Safety concerns prohibit to reconnect the transformer Maschinenfabrik Reinhausen or the authorized MR
without prior check as this can result in considerable representative and the transformer manufacturer should
damage to the on-load tap-changer and transformer. be informed whenever the protective relay has responded.

When the circuit breakers have been tripped by the protec-


tive relay, proceed as follows:
• Determine the instant of tripping.
• Determine the operating position of the on-load tap-
changer.
• As a precaution, block the motor-drive by tripping the
motor protective switch to prevent the on-load tap-
changer being actuated by remote control.
• Examine the on-load tap-changer cover. If oil leaks out,
shut the oil conservator stop valve immediately.
• Check the flap valve of the protective relay if it is in
position "OFF" or in position "IN SERVICE".

8 059/06/01/0
7 Technical Data / 8 Special Designs
9 Appendix

7 Technical Data

Housing: Tripping switch:


Outdoor design Reed switch, available on request as NO (version 1) or NC
switch (version 2). Designations of versions, see dimension
Protection: drawing 899084 in the appendix. Other switch combina-
IP 54 tions, see section 8.
Relay actuation:
Make/break current, switching capacity:
Flap valve with aperture
2 A, AC 24 V to 250 V, 400 VA
Assignation of response values to the relevant on-load tap- 2 A, DC 24 V to 250 V, 250 W
changer type
Power-frequency voltage test:
On-load tap-changer - current delivery program At least 2.5 kV, 50 Hz, 1 min. duration between all live con-
nections and grounded parts.
Frequency Response value Vibration immunity:
[Hz] [m/s] OLTC-type
up to max. 3 g

0.65 VV Weight:
ca. 3.5 kg
V, V V (with OF 100), MS,
50/60 1.20
M (without M I 1203, M I 1503)

R, RM, G, 8 Special Designs


3.00 (on request, at extra cost)
M I 1203, M I 1503

G-16 2/3 Hz, 8.1 Protective relay with change-over contact CO


16 2/3 4.80 (see appedix, dimension drawing), version 3
M-16 2/3 Hz,
The protective relay can be supplied with a reed switch,
including change-over contact CO.
On-load tap-changer - not current delivery program Make/break current, switching capacity
max. 1 A, AC 24 ... 250 V, 200 VA
max. 1 A, DC 24 ... 250 V, 130 W
Frequency Response value
[Hz] [m/s] OLTC-type

8.2 Protective relay with two reed switches


0.65 A (see annex, dimension drawing), versions 4 ... 6
50/60 1.20 H The protective relay can be supplied on request with two
independent reed switches (max. admissible switching cur-
M 1200, M I 1500, rents as with version 1 and 2, see section 7). These can be
3.00 designed as NO or as NC contacts. Designations of versions,
M I 1800, T
see dimension drawing 899084 in the appendix.

Oil flow speed on response (oil temperature 20°C):


0.65 ± 0.15 m/s
1,20 ± 0,20 m/s 9 Appendix
3.00 ± 0.30 m/s
4.80 ± 0.30 m/s Protective relay RS 2001,
dimension drawing ................................................................... 899084

059/06/01/0
9
8990842E
Protective relay RS 2001
(Standard)

Cable gland
Inspection M25 x 1.5
window

Identification label

Gasket Gasket

Test push buttons


IN SERVICE OFF
(reset) (test tripping)

Dummy plug M25 x 1.5

The arrow must always point towards the oil pipe leading to the Plan view of test push buttons
oil conservator of the transformer. (cover removed)

Key of versions

Reed Contact positions


Version Relay designation1) switch Arrangement of terminals Design
In service Off

0.65 - NO
1 1.2 - NO A
Standard design
3.0 - NO
4.8 - NO
0.65 - NC
2 1.2 - NC B
3.0 - NC
4.8 - NC
0.65 - CO
3 1.2 - CO C
3.0 - CO
Special design against surcharge

4.8 - CO
0.65 - 2NO
4 1.2 - 2NO 2A
3.0 - 2NO
4.8 - 2NO
0.65 - 2NC
5 1.2 - 2NC 2B
3.0 - 2NC
4.8 - 2NC
0.65 - NO + NC
6 1.2 - NO + NC 1 A and 1 B
3.0 - NO + NC
4.8 - NO + NC

1)
NO - normally open, NC - normally closed, CO - change-over contact

The protective relay is to be connected in such a way that if it is energized, the power transformer is switched off immediately by the corresponding circuit breakers.

10 059/06/01/0
© Maschinenfabrik Reinhausen GmbH Phone +49 941 40 90-0
[Link] Falkensteinstrasse 8 Fax +49 941 40 90-111
93059 Regensburg, Germany E-mail sales@[Link]

Please note: The data in our publications may differ from the data of devices delivered.
We reserve the right to make changes without notice.
BA 059/06 en • 0204/3000 • 059/06/01/0 • F0015204 • Printed in Germany

You might also like