0% found this document useful (0 votes)
62 views6 pages

Micro800 Plug-in Modules Overview

The document provides an overview of Micro800 Plug-in Modules, which enhance the functionality of base unit controllers by extending I/O capabilities, improving performance, and adding communication options. It details various types of plug-in modules, their specifications, installation instructions, and wiring guidelines. Additionally, it includes environmental specifications and certifications for the modules, ensuring compliance with industry standards.

Uploaded by

Minh Nhut Luu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
62 views6 pages

Micro800 Plug-in Modules Overview

The document provides an overview of Micro800 Plug-in Modules, which enhance the functionality of base unit controllers by extending I/O capabilities, improving performance, and adding communication options. It details various types of plug-in modules, their specifications, installation instructions, and wiring guidelines. Additionally, it includes environmental specifications and certifications for the modules, ensuring compliance with industry standards.

Uploaded by

Minh Nhut Luu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

Chapter 1

Micro800 Plug-in Modules

Plug-in modules enhance the functionality of a base unit controller. With these
modules, you can:
• Extend the functionality of embedded I/O without increasing the
footprint of your controller.
• Improve performance by adding additional processing power or
capabilities.
• Add additional communication functionality.

Micro800 controllers support the following plug-in modules:


Micro800 Plug-in Modules
Module Type Description
2080-IQ4 Digital 4-point, 12/24V DC Sink/Source input
2080-IQ4OB4 Digital 8-point, Combo, 12/24V DC Sink/Source input
12/24V DC Source output
2080-IQ4OV4 Digital 8-point, Combo, 12/24V DC Sink/Source input
12/24V DC Sink output
2080-OB4 Digital 4-point, 12/24V DC Source output
2080-OV4 Digital 4-point, 12/24V DC Sink output
2080-OW4I Digital 4-point, AC/DC Relay output
2080-IF2 Analog 2-channel, Non-isolated unipolar voltage/current
analog input
2080-IF4 Analog 4-channel, Non-isolated unipolar voltage/current
analog input

Rockwell Automation Publication 2080-UM004D-EN-E - March 2018 1


Chapter 2 Install and Wire Your Module

1. Position the plug-in module with the terminal block facing the front of the
controller as shown.
2. Snap the module into the module bay.
3. Using a screwdriver, tighten the 10…12 mm (0.39…0.47 in.) M3 self
tapping screw to torque specifications.
See Specifications on page 61 for torque specifications.

IMPORTANT Analog I/O performance depends on the application. For better noise
immunity, cable length should ideally be less than 3 m because the plug-
ins are non-isolated. For longer cable length requirements, use the 2085
expansion I/O modules instead.

Wiring The following plug-in modules have 12-pin Back


female terminal blocks:
• 2080-IQ4, B 1 2 3 4 5 6
• 2080-IQ4OB4, 2080-IQ4OV4
• 2080-OB4, 2080-OV4, 2080-OW4I A 1 2 3 4 5 6
• 2080-IF2, 2080-IF4 Front
• 2080-TC2, 2080-RTD2 Twelve-pin Female Terminal Block

Pin Designations for 12-Pin Female Terminal Block Modules


Pin 2080-IQ4 2080-IQ4OB4, 2080-OB4, 2080-OW4I 2080-IF2 2080-IF4 2080-TC2 2080-RTD2
2080-IQ4OV4 2080-OV4
I-02 I-02 Not used COM3 COM COM CH0+ CH0+
A1
I-03 I-03 Not used O-3 Not used VI-2 CH0- CH0-
A2

COM COM -24V DC Not used Not used CI-2 CJC+ CH0L (Sense)
A3

COM -24V DC -24V DC Not used COM COM Not used Not used
A4

Not used O-02 O-02 Not used Not used VI-3 Not used Not used
A5

Not used O-03 O-03 Not used Not used CI-3 Not used Not used
A6

I-00 I-00 Not used COM0 VI-0 VI-0 CH1+ CH1+


B1

I-01 I-01 Not used O-0 CI-0 CI-0 CH1- CH1-


B2

COM COM +24V DC COM1 COM COM CJC- CH1L (Sense)


B3

COM +24V DC +24V DC O-1 VI-1 VI-1 Not used Not used
B4

Not used O-00 O-00 COM2 CI-1 CI-1 Not used Not used
B5

Not used O-01 O-01 O-2 COM COM TH Not used


B6

8 Rockwell Automation Publication 2080-UM004D-EN-E - March 2018


Install and Wire Your Module Chapter 2

Example Wiring for 2080-IQ4OB4

+24V DC (Sinking) +24V DC


-24V DC (Sourcing)
CR

CR

B 1 2 3 4 5 6 Sourcing
DC input
output
A 1 2 3 4 5 6

CR

CR
-24V DC (Sinking)
+24V DC (Sourcing) -24V DC

Example Wiring for 2080-IQ4OV4

+24V DC (Sinking) +24V DC


-24V DC (Sourcing)
CR

CR

B 1 2 3 4 5 6 Sinking
DC input
output
A 1 2 3 4 5 6

CR

CR
-24V DC (Sinking)
+24V DC (Sourcing) -24V DC

Example Wiring for 2080-IF4

Voltage transmitter
Shielded cable

Current transmitter
Shielded cable

B 1 2 3 4 5 6

A 1 2 3 4 5 6

Current transmitter
Shielded cable

Voltage transmitter
Shielded cable

Rockwell Automation Publication 2080-UM004D-EN-E - March 2018 9


Appendix A

Specifications

Digital Plug-in Modules General Specifications – 2080-OB4, 2080-OV4, 2080-IQ4OB4, 2080-IQ4OV4, 2080-IQ4
Attribute Value
Mounting torque 0.2 Nm (1.48 lb-in.)
Status indicators For input or output modules – 4 yellow
For combination modules – 8 yellow
Terminal base screw torque 0.22…0.25 Nm (1.95…2.21 lb-in.)
using a 2.5 mm (0.10 in.) flat-blade screwdriver
Enclosure type rating None (open-style)
Isolation voltage For input modules
50V (continuous), Basic Insulation Type, Inputs to Backplane
Type tested for 60 s @ 720 V DC, Inputs to Backplane
For combination or output modules
50V (continuous), Basic Insulation Type, Inputs to Outputs, I/Os to
Backplane
Type tested for 60 s @ 720 V DC, I/Os to Backplane
Wire size 1.3... 0.2 mm2 (16...24 AWG) solid or stranded copper wire rated @
90 °C (194 °F), or greater, insulation max
Wire category 2 – on signal ports
2 – on power ports
North American temp code T4

Input Specifications – 2080-IQ4, 2080-IQ4OV4, 2080-IQ4OB4


Attribute Value
DC on-state voltage, min 9.0V DC
DC on-state voltage, max 30V DC
DC on-state current, min 2.0 mA @ 9V DC
DC on-state current, nom 3.0 mA @ 24V DC
DC on-state current, max 5.0 mA
DC off-state voltage, max 5V DC
DC off-state current, max 1.5 mA
IEC input compatibility Type 3
Input impedance 0…3V, >4 KΩ
3…12V, 3.5 KΩ min
12…30V, >4 KΩ <10 KΩ
Input filter time ON to OFF 8…10 ms AC/DC
AC on-state voltage, min 10.25V AC (rms)
AC on-state voltage, max 30V AC (rms)

Rockwell Automation Publication 2080-UM004D-EN-E - March 2018 61


Appendix A Specifications

Input Specifications – 2080-IQ4, 2080-IQ4OV4, 2080-IQ4OB4


Attribute Value
AC on-state current, min 2.0 mA @ 9V AC (rms)
AC on-state current, max 5.0 mA
AC off-state voltage 3.5V AC (rms)

Output Specifications – 2080-OB4, 2080-OV4, 2080-IQ4OB4, 2080-IQ4OV4


Attribute Value
Power supply voltage 10.8V DC, min
30V DC, max
On-state voltage 10V DC, min
24V DC, nom
30V DC, max
On-state current 5.0 mA @ 10V DC, min
0.5 A max, steady state
2 A surge, 2 s min
Off-state leakage current, max 10 µA

Environmental Specifications – 2080-OB4, 2080-OV4, 2080-IQ4OB4,


2080-IQ4OV4, 2080-IQ4
Attribute Value
Temperature, operating IEC60068-2-1 (Test Ad, Operating Cold),
IEC60068-2-2, (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20...65 °C (-4…149 °F)
Temperature, surrounding air, 65 °C (149 °F)
max.
Temperature, non-operating IEC60068-2-1 (Test Ad, Operating Cold),
IEC60068-2-2, (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-40...85 °C (-40…185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating):
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock):
25 g
Shock, non-operating IEC 60068-2-27 (Test Ea, Unpackaged Shock):
25 g
Emissions CISPR 11:
Group 1, Class A
ESD Immunity IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges
Radiated RF immunity IEC 61000-4-3:
10 V/M with 1 kHz sine-wave 80%AM from 80…2000 MHz
10 V/M with 200 Hz 50% Pulse 100%AM @ 900 MHz
10 V/M with 200 Hz 50% Pulse 100%AM @1890 MHz
10 V/M with 1 kHz sine-wave 80%AM from 2000…2700 MHz

62 Rockwell Automation Publication 2080-UM004D-EN-E - March 2018


Specifications Appendix A

Environmental Specifications – 2080-OB4, 2080-OV4, 2080-IQ4OB4,


2080-IQ4OV4, 2080-IQ4
Attribute Value
EFT/B immunity ±2 kV @ 5 kHz on signal ports
Surge transient immunity ±1 kV line-line(DM) and ±2 kV line-earth(CM) on signal ports
Conducted RF immunity 10V rms with 1 kHz sine-wave 80%AM from 150 kHz…80 MHz

Certifications – 2080-OB4, 2080-OV4, 2080-IQ4OB4, 2080-IQ4OV4, 2080-IQ4


Certification (when Value
product is marked)(1)
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada.
See UL File E322657.

UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations,


certified for U.S. and Canada. See UL File E334470.
CE European Union 2014/30/EU EMC Directive, compliant with:
EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
RCM Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
KC Korean Registration of Broadcasting and Communications
Equipment, compliant with:
Article 58-2 of Radio Waves Act, Clause 3
EAC Russian Customs Union TR CU 020/2011 EMC Technical Regulation
(1) See the Product Certification link at [Link]
for Declarations of Conformity, Certificates, and other certification details.

General Specifications – 2080-OW4I Digital Relay Output Plug-in Module


Attribute Value
Mounting torque 0.2 Nm (1.48 lb-in.)
Status indicators 4 yellow
Terminal base screw torque, 0.19 Nm (1.7 lb-in.)
max using a 2.5 mm [0.10 in.] flat-blade screwdriver
Wire size 0.05…1.31 mm2 (30…16 AWG) solid copper wire
rated @ 90 °C (194 °F ) insulation max
Enclosure type rating None (open-style)
Isolation voltage 240V (continuous), Reinforce Insulation Type, between Output
Channels and Output channels to Backplane
Type tested for 60 s @ 1480 V AC Outputs to Outputs, Outputs to
Backplane
Insulation stripping length 5 mm
Wiring category 2 – on signal ports
2 – on power ports
Wire type Copper