TECHNICAL PARTICULARS FOR TRANSFORMER
Sr. No. DESCRIPTION 550KW
1 Type
2 Specification Reference IS 2026
3 Rating (KVA) 660
HV 11000
4 No load Voltage Ratio
LV 375 X 2
HV 35
5 Amperes
LV 510.0
6 No of phase 6
7 Vector group Dd0, Dyn11
8 Frequency 50 Hz
9 Method of cooling Oil natural air natural [ ONAN ]
10 Tapping on HV side: for voltage variation on HV side ±7.5% in 2.5 % step voltage in 7 steps (Auto)
HV Cable Box
11 Terminations
LV Cable Box
No Load Loss in KW As per IS 2026 Standard
12 Losses
Full Load Loss in KW As per IS 2026 Standard
13 Impedance : at rated current, at normal tap 6.0 % ( As per IS 2026 tolerance )
Electrostatic sheild Required
14 Insulation Level
A. Power frequency test [ HV/LV ] 28 KVrms / 3 KVrms
B. Impulse test voltage [ HV / LV ] 75 kvp / ----- kvp
15 Material of winding [HV / LV ] Best EC Grade copper double wound
16 Temperature Ambient - 50 °C, Oil - 50 °C, Wind. - 55°C
LIST OF ROUTINE TEST
Sr. No. Name of routine test
1 Winding resistance
2 Voltage ratio & Vector group
3 Impedance voltage
4 Full load loss & current
5 No load loss & current
6 Insulation resistance
7 Induced over voltage withstand
8 Separate sourace voltage withstand test
9 Oil BDV test