IM 2007R Data Sheet

The instruction manual for the KEW2007R Digital Clamp Meter provides essential safety warnings, specifications, and operational guidelines for safe usage. It emphasizes the importance of adhering to safety instructions to prevent injury and equipment damage, and outlines measurement categories and accuracy for various functions. Additionally, it includes details on battery replacement, low battery indication, and features like data hold and sleep function.

Uploaded by

mohammad.afaneh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
39 views2 pages

IM 2007R Data Sheet

The instruction manual for the KEW2007R Digital Clamp Meter provides essential safety warnings, specifications, and operational guidelines for safe usage. It emphasizes the importance of adhering to safety instructions to prevent injury and equipment damage, and outlines measurement categories and accuracy for various functions. Additionally, it includes details on battery replacement, low battery indication, and features like data hold and sleep function.

Uploaded by

mohammad.afaneh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

INSTRUCTION MANUAL 1.

Safety Warnings NOTE


This instrument has been designed, manufactured and ● The LCD shows some digits at the ACV and the DCV
tested according to IEC 61010: Safety requirements for ranges even while the test leads are open. In addition,
the LCD shows some digits instead of 0 when short-
DIGITAL CLAMP METER Electronic measuring apparatus, and delivered in the best
circuiting the test leads. However, these phenomena
condition after passed the inspection. This instruction
manual contains warnings and safety rules which must be don’t affect measurement results.

KEW2007R observed by the user to ensure safe operation of the


instrument and retain it in safe condition. Therefore, read
through these operating instructions before using the
2. Specification
instrument. DANGER
Temperature: 23 ± 5°C, Humidity: 45 - 75%
● Never make measurements under the circumstances
WARNING exceed the designed measurement category and the ACA (Auto-range)
● Read through and understand the instructions contained rated voltage of the instrument and the test leads.
● Do not attempt to make measurement in the presence of Range Display Range Accuracy (sine wave)*1
in this manual before using the instrument.
● Keep the manual at hand to enable quick reference flammable gasses. Otherwise, the use of the instrument 600A 0.0, 0.4-629.9A ±1.5 %rdg±4dgt (45-65Hz)
Current Sensor may cause sparking, which can lead to an explosion.
whenever necessary. 1000A 570-1049A ±2.0 %rdg±4dgt (40-400Hz)
● The instrument is to be used only in its intended ● Never attempt to use the instrument if its surface or your
applications. hand is wet. *1 : when the measured conductor is in the center of clamp jaw
● Understand and follow all the safety instructions ● Do not exceed the maximum allowable input of any Guaranteed accuracy : 0.8A -1000A,less than 1500A Peak
contained in the manual. measuring range.
Barrier Input protective current : AC1200A
● It is essential that the above instructions are adhered to. ● Never open the Battery cover during a measurement.
Trigger Failure to follow the above instructions may impair the ● To avoid electrical shock by touching the equipment ACV
protection provided by the instrument and test leads, and under test or its surroundings, be sure to wear insulated
protective gear. Range Display Range Accuracy (sine wave)
may cause injury, instrument damage and/or damage to
● Never measure current while the test leads are inserted ±1.2 %rdg±3dgt (45-65Hz)
equipment under test. 600V 0.0, 0.6-629.9V
into the input terminals. ±1.5 %rdg±4dgt (40-400Hz)
The symbol indicated on the instrument means that the ● Test leads to be used for voltage measurements shall be
Function user must refer to the related parts in the manual for safe rated as appropriate for Measurement Category III or IV Guaranteed accuracy : 1.0V - 600.0V,less than 900V Peak
Switch operation of the instrument. It is essential to read the according to IEC 61010-031 and shall have a voltage Input protective voltage : AC/DC720V 10 sec
instructions wherever the symbol appears in the manual. rating of 600V or higher.
DANGER is reserved for conditions and actions that ● Barriers on the instrument body and the test leads DCV
Hold Key are likely to cause serious or fatal injury. provide protection to keep your fingers and hands from Range Display Range Accuracy
WARNING is reserved for conditions and actions that touching an object under test. Keep your fingers and
hands behind the barriers during measurement. 600V 0.0-±629.9V ±1.2%rdg±3dgt
can cause serious or fatal injury.
LCD CAUTION is reserved for conditions and actions that WARNING Guaranteed accuracy : 0.0V - ± 600.0V
can cause injury or instrument damage. ● Never attempt to make measurement if any abnormal Input protective voltage : AC/DC720V 10 sec
conditions, such as broken case and exposed metal ACV/DCV input impedance : approx. 10MΩ
● Marks listed below are used on this instrument.
parts are found on the instrument or test leads.
User must refer to the manual. ● Verify proper operation on a known source before use or Resistance / Continuity (Auto-range)
COM V/Ω Instrument with double or reinforced insulation take action as a result of the indication of the instrument. Range Display Range Accuracy
Terminal Terminal ● Firmly attach the caps to the test leads when 600Ω 0.0-629.9 Ω ±1.3%rdg±5dgt
Indicates that this instrument can clamp on
performing measurements in CAT III or higher test
bare conductors when measuring a voltage 6kΩ 0.570-6.299 kΩ ±2.0%rdg±3dgt
environments. When KEW2007R and the test leads
corresponding to the applicable measurement are combined and used together, whichever is lower Cont. 0.0-629.9 Ω Bz threshold value <90Ω
category, which is marked next to this symbol. category & voltage to earth either of them belong to
Guaranteed accuracy : 0.0Ω - 6.000kΩ
AC DC Ground (Earth) is applied.
Open-loop voltage : 3V or less
● Do not rotate the Function Switch if the instrument and
This instrument is subject to WEEE Directive Input protective voltage : AC/DC600V 10 sec
the equipment under test are connected.
Wrist Strap (2002/96/EC). Please contact our dealer near
● Do not install substitute parts or make any modification to
you at disposal. ●Measuring method : ⊿Σ modulation
the instrument. For repair or re-calibration, return the
●Over-range indication : OL
instrument to your local KYORITSU distributor
Measurement Category ●Measurement cycle : 2.5 times per second
O Circuits which are not directly connected to the mains CAUTION ●Crest factor : less than 3 (45-65Hz)
power supply. ● Use of this instrument is limited to domestic, commercial Add ±0.5%rdg±5dgt to above specified accuracies.
Barrier of Test Leads and light industry applications. Strong electromagnetic (Applicable functions : ACA, ACV)
CAT II Primary electrical circuits of equipment connected interference or strong magnetic fields, generated by ●Applicable Standards :
Cap to an AC electrical outlet by a power cord. large currents, may cause malfunction of the instrument. IEC 61010-1/ 61010-2-032/ 61010-2-033 (instrument)
CAT III Primary electrical circuits of the equipment ● Connect the test leads to the terminals firmly. Pollution degree 2, Indoor use, Altitude up to 2000m
connected directly to the distribution panel, and feeders ● This instrument isn’t water proofed. Keep away from CAT III 600V / CAT IV 300V
water. IEC 61010-031(Test leads Model 7066A)
from the distribution panel to outlets.
● Do not pull or twist the test leads to prevent the risk of w/ caps CAT IV 600V / CAT III 1000V
CAT IV The circuit from the service drop to the service damage. w/o caps CAT II 1000V
entrance, and to the power meter and primary over current ● Power off the instrument after use. Remove batteries if IEC61326 (EMC), EN50581 (RoHS)
protection device(distribution panel). the instrument is to be stored and will not be in use for a ●Withstand voltage : AC5160Vrms 5sec
long period. between current sensor and enclosure or
This instrument is designed for CAT IV 300V / CAT III ● Do not expose the instrument to the direct sunlight, high circuit and enclosure
600V. Test leads M-7066A with the supplied cap are temperature and humidity or dewfall. ●IP rating : IP40 (IEC60529)
designed for CAT IV 600V / CAT III 1000V and without ● Use a cloth dipped in water or neutral detergent for ●Insulation resistance :
the caps are for CAT II 1000V. cleaning the instrument. Do not use abrasives or solvents. >100MΩ /1000V between enclosure and electrical circuit
●Operating Temperature and humidity range : 6. Other Functions MEMO
0 to 40°C 85%RH or less (no condensation) ACV DCV
●Storage Temperature and humidity range : ●Data Hold
-20 to 60°C 85%RH or less (no condensation) Press the Hold key. The LCD shows “ ” mark and the
●Power source : DC3V R03 / LR03 (AAA) ×2 reading will be held.
●Current consumption : < 4mA Press the Data Hold Key again
●Battery life (ACA, continuous, no load, with R03) : to release the display.
approx. 170 hours
●Dimension, Weight : 204(L)×81(W)×36(D)mm,
approx. 220g (including batteries) ●Low battery indication
●Accessories : The LCD shows “ ” mark when the batteries fall
Test leads Model 7066A 1set below the normal operating voltage.
Battery R03(AAA) 2pcs
Instruction manual 1pce Replace the batteries
Carrying case Model 9079 1pce with new ones when
this mark appears.

●Sleep Function
Automatically powers off the instrument in about 10 min
3. ACA Measurement after the last switch or key operation. Buzzer beeps five
Black(-) Red(+) times one minute before entering into the Sleep mode,
DANGER and also one time just before entering into the mode. To
●Disconnect the test leads from the instrument when exit from the Sleep mode, rotate the Function switch or
performing a test. NOTE press Hold key.
●Do not exceed the rated voltage (600V) and the If the connection is reversed, the LCD indicates the
“ - “ mark (DCV measurement). To disable the Sleep function, DISTRIBUTOR
category ratings of the instrument.
press the HOLD key and
●Keep your fingers and hands behind the barrier power on the instrument.
during measurement. [Link](Continuity)Measurement Confirm that the LCD shows
“ ” about 1 sec.
(1) Set the Function switch to ACA position.
(2) Press the trigger to open the Current Sensor and clamp
WARNING
the one conductor (Dia. 33mm max.) under test. Power off the circuit under test before making 7. Battery Replacement
measurements with this instrument.
Correct Incorrect (1) Set the Function switch to resistance or continuity WARNING
position. ● Replace the batteries when a Low Battery Voltage
(2) Firmly connect the test leads to V/Ω and COM terminals. warning " " mark is indicated on the LCD. Otherwise,
precise measurement cannot be made.
If batteries are completely exhausted, the LCD goes
Resistance Continuity blank without showing " " mark.
● Do not try to replace the batteries if the surface of the
instrument is wet.
● Disconnect the test leads from the object under test and
power off the instrument before opening the Battery
Compartment Cover for battery replacement.

CAUTION
NOTE ● Do not mix old and new batteries. Brand and type of the
batteries to be used should be harmonized.
Measurement accuracy is guaranteed when the measured ● Install batteries in correct polarity as indicated in Kyoritsu reserves the rights to change specifications
object is placed at the center of the Current Sensor. or designs described in this manual without notice
the Battery Compartment.
and without obligations.
(1) Set the Function Switch to "OFF" position.
4. ACV/DCV Measurement (2) Unscrew and remove the Battery Compartment Cover
on the instrument.
(3) Replace the batteries observing correct polarity.
DANGER Use new two AAA 1.5V batteries.
●Before starting a measurement, ensure that the (4) Install the Battery Compartment Cover and tighten the
Function switch is set to the appropriate position. screw.
●Do not exceed the rated voltage (600V) and the Screw
category ratings of the instrument.
●Keep your fingers and hands behind the barrier

during measurement.
Beeps less than 90Ω.
(1) Set the Function switch to ACV or DCV position.
(2) Firmly connect the test leads to V/Ω and COM terminals. NOTE
LCD indicates ”OL” when the test leads are open.

11-15 92-2261