Electrical Transients
Introduction: Transient Over-voltage
Short duration (microseconds to milliseconds) and can
be of large magnitude
Cause billions of dollars of losses each year
worldwide due to damaged equipment and lost
production
Also known as surges or spikes
2
Defined as the response of an electrical network to a
sudden change in network conditions, either intended or
accidental, (e.g. a switching operation or a fault) or
network stimuli (e.g. a lightning strike)
Transients are sub cycle events, lasting less than one cycle
of the AC waveform
Transients are difficult to detect because of their short
duration
Importance of transient study
Microcontroller
Medical electronic instruments
Impulsive Transients
Due to lightning strikes
Oscillatory Transients
3
Due to network switching operations
Impulsive Transient
An impulsive transient is a sudden, non-power frequency
change from the nominal condition of voltage, current, or
both, that is unidirectional in polarity
Characterized by their rise and decay times
An impulsive transient voltage is described as having a
1.2/50 waveshape
Impulsive transients can excite power system resonance
circuits and produce oscillatory transients
4
Impulse transient
5
Characteristics
6
Causes of Impulse Transient
1. Lightning can strike directly to the phase conductors of
overhead power lines producing very high magnitude
transient over voltages
Peak current can be up to 200 kA with voltages over 1 MV
2. Lightning can also strike the overhead earth wire
1. back-flashover
3. Indirect strike
Currents produced in this manner are usually less than 2 kA
with voltages less than 100 kV
4. Overhead conductors at a higher voltage level physically
fall on to lower voltage mains
1. High voltage injection
7
Oscillatory transient
An oscillatory transient is a sudden, non-power
frequency change in the steady state condition of the
voltage and/or current waveforms that swings
(oscillates) both positively and negatively with respect
to the normal voltage waveform
The frequency of this oscillation can be quite high
8
Oscillatory transients are described by their
magnitude, predominate frequency and decay time
(duration).
Subdivided into
Low Frequency Transients
Medium Frequency Transients
High Frequency Transients
9
Low Frequency Transients
Primary frequency component less than 5 kHz
Duration from 0.3 ms to 50 ms, [IEEE Standard 1159-
1995 ].
This category of phenomena is frequently encountered
on sub-transmission and distribution systems and is
caused by several types of switching event.
Capacitor bank energization
300 to 900 Hz and a peak magnitude between 1.3 and
1.5 times the crest voltage of the 50 Hz waveform.
Ferroresonance
Transformer energization
10
Medium Frequency Transient
An oscillatory transient with a predominant frequency
component between 5 and 500 kHz and a duration
measured in tens of microseconds
Transients generated by back-to-back capacitor
energisation and cable switching.
11
High Frequency Transients
Oscillatory transients with a predominant frequency
component greater than 500 kHz and a typical
duration in microseconds
These transients often occur when an impulsive
transient excites the natural frequency of the local
power system network.
12
Causes of Oscillatory Over voltages: Network
switching
Switching of utility capacitor banks
Switching of circuit breakers to clear network faults
Switching of distribution feeders to rearrange the network
for maintenance or construction
13
Oscillatory transient Clearing of fault
14
Capacitor Switching Magnification
15
Figure 6: Voltage magnification
16
Figure 7: Arrester energy duty caused by magnified transient
17
Limiting switching transients
High-energy surge arresters
Harmonic filters
Line Reactor
18
Lightning
Figure 8: Lightning strike locations where
lightning impulses will be conducted into
19
load facilities
Figure 8: Coupling of impulses through the
20
interwinding capacitance of transformers
Figure 9: Lightning impulse bypassing the service
21
transformer through ground connections
Ferro resonance
(a)
(b)
Figure 10(a). Series ferroresonant circuit,
(b) Graphical solution of a series ferroresonant circuit
22
Ferroresonant Operating Conditions
Operation point 1:
It is a non-ferroresonant stable operation point.
This is an inductive situation ( XL−linear > XC E = VL –
VC).
Operation point 2:
It is a ferroresonant stable operation point.
This is a capacitive situation ( XL−sat < XCE = VC – VL)
Operation point 3: It is an unstable operating point
23
Figure 11: Evolution of the solution increasing source
voltage E
24
Figure 12: Evolution of the solution increasing capacitance value C
25
Effects of ferroresonance
Ferroresonant states
Fundamental mode
Subharmonic mode
Quasi-periodic mode
Chaotic mode
Effects
Overvoltages and overcurrents
Sustained levels of distortion
Loud noise (magnetostriction)
Misoperation of protective devices
Overheating
Electrical equipment damage
Insulation breakdown
26 Flicker
Transient system model: Capacitor
is lead resistance.
L is lead inductance (of the order of μH).
represents dielectric loss (responsible for capacitor
heating at higher frequencies).
C is the capacitance of the capacitor.
27
Transient system model: Reactor
R is winding resistance
C is the combined effect of inter-turn capacitance and
capacitance to earth (of the order of nF).
L is the inductance of the reactor.
28
Transient system model: Transformer
is the effective capacitance of the primary winding to earth
is the effective inter-winding capacitance
is the effective capacitance of the secondary winding to
earth.(Capacitances are of the order of nF)
and are the primary and secondary winding leakage
inductances respectively
is the magnetizing inductance of the transformer
29
Transient system model: Power System
30
Other switching transients
Line energization transients
Higher-frequency content than capacitor energizing
transients
Die out in about 0.5 cycle
Energization transients on distribution feeder
Line energizing transients
Transformer energizing inrush
Load inrush
Single-line-to-ground fault
Voltage rise upto 1.4pu
31
Principles of Overvoltage Protection
Limit the voltage across sensitive insulation
Divert the surge current away from the load
Block the surge current from entering the load
Bond grounds together at the equipment
Reduce, or prevent, surge current from flowing between
grounds
Create a low-pass filter using limiting and blocking
principle
32
Figure 14: Principles of overvoltage protection
33
Devices for over voltage protection
Surge arresters and transient voltage surge suppressors
Crowbar devices
Devices that switch into a very low impedance mode to short circuit
the transient until the current is brought to a low level
Triggered by the breakdown of a gas or insulating layer, such as air
gap protectors, carbon block detectors, gas discharge tubes (GDTs)
Very low impedance allows a high current to pass without dissipating
a considerable amount of energy within the device
Disadvantage
As the device switches or transitions to its breakdown mode the load may
be exposed to damaging overvoltage
Power frequency voltage drops to zero or to a very low value for at least
on one-half cycle. This will cause some loads to drop offline
unnecessarily
34
Power current from the voltage source follows the surge discharge
Clamping devices
Zener Diodes/MOVs
Nonlinear resistors (varistors) that conduct very low
amounts of current until an overvoltage occurs.
Then they start to conduct heavily, and their impedance
drops rapidly with increasing voltage.
Advantage over gap-type devices the voltage is not
reduced below the conduction level when they begin to
conduct the surge current.
MOV arresters have two important ratings.
35
Selection Criteria Clamping Devices
1. The normal operating conditions of the apparatus or
system, and whether ac or dc voltage is applied
Maximum continuous operating voltage
Maximum withstand voltage of protected device > [Link] clamping voltage > Max.
continuous operating voltage
2. Determine the repetitive peak current
3. Calculate the energy absorption
4. Package size and style
Energy rating and surge current amplitudes
Lead inductance and device capacitance
36
Figure 14: Suppression directly
across mains
Figure 15: Varistors used to
suppress internally generated
spikes in a TV application
37
Low pass filters
Low-pass filters use the pi-circuit principle achieve even
better protection for high-frequency transients
In surge protection usage, voltage clamping devices are
added in parallel to the capacitors
Figure 16: Hybrid transient protector
38
Utility Surge Arresters
39
Switching Transient Problems with Loads
Nuisance tripping of ASDs
Figure 18: Effect of capacitor switching on adjustable-speed-
40
drive ac
current and dc voltage
41
Transients from load switching (Electric Fast
Transients)
• High frequency filters
• Isolation Transformers
Figure 20: Fast transients caused by de-energizing an inductive load
42
Transformer Energization
Inrush Currents upto 1s
Voltages upto 1.5 pu
Figure 21: Energizing a capacitor and transformer
Figure 22: Dynamic over-voltages during
43 transformer energizing.