Introduction to current chopping:
• Current chopping refers to the Phenomenon Where the current is
Interrupted before It reaches the zero crossing point
• This can occur in circuit breakers Particularly those using air as the
Interrupting medium
• Understanding Current chopping is essential for optimizing circuit
breakers Performance and ensuring System reliability
Current chopping:
• It is the phenomenon of the current interruption before the natural
current Zero is reached.
• Current chopping mainly occurs in air blast Circuit breakers because the
retain the same extinguishing Power irrespective of the magnitude of
the current to be interrupted.
• When breaking low current ( ex: transformer magnetising current) with
such breakers, the Powerful ionising effect of air Blast causes the
current to be abruptly to zero well before the natural current Zero is
reached .
• This phenomenon is known as current chopping and results in the
Production of high voltage transient across the contact of the circuit
breakers.
Current chopping circuit diagram:
• In such a situation energy stored in the magnetic field appears in the form of
High voltage across the stray Capacitance , which will cause restriking of the
arc.
• The energy stored in the magnetic field ½ Li² is the instantaneous value of the
current Which is interrupted This will appear in the form of electrostatic
energy is equal to ½ CV².As the two energies are equal they can be related as
Follow
½ Li²= ½ CV²
V= i √L/c
• The Prospective voltage V is very high as compared to dielectric strength
Gained by the Gap so that the breaker restrikes.
• As the de ionising force still in action Therefore chop occurs But the arc
current this time is smaller than the previous case.
• This induces lower prospective Voltage re ignite the arc . In fact several chops
may occurs until a low enough current is interrupted Which produces
insufficient Induced voltages to re strike across the breaker gap .
• Consequently the Final interruption of the current take place . Excessive
Voltage surges due to current chopping are prevented by Shunting the
contacts of the breaker with a resistor (resistance switching) Such that
reignition is unlikely to occur.
• Applications of current chopping:
• Switching shunt reactors.
• Switching unloaded Transformers
• Advantages and Disadvantages:
• Fast operation: circuit breakers can operate quickly and repeatedly
• Oscillating voltage : Current chopping can causes the Voltage across the circuit
breakers to oscillate which may leads to restriking
• How to reduce current chopping?
• Use SF6 gas
• Use metals with High Vapor pressure and low conductivity.
• The metals can help Limit current chopping
Conclusion:
• Current chopping is a critical phenomenon that circuit breaker Engineers
need to address
• Understanding its causes and effects is vital For ensuring the longevity
and reliability for electrical system .
• By implementing Appropriate Mitigation strategies the negative impact
of current chopping Can be significantly reduced .