Switchgear and Protection
Unit II
Circuit Breakers & Fuses
[Link] Devi,
AP/EEE,
Thiagarajar College of Engineering.
Circuit Breakers
• Circuit breaker is a mechanical switching device capable of making,
carrying and breaking currents under normal circuit conditions.
• Making, carrying for a specified time, and automatically breaking
currents under specified abnormal circuit conditions such as those
of short-circuits (faults).
• The function of a circuit breaker is to isolate the faulty part of the
power system.
Diagram of CB
Fixed and Moving contacts of the CB
LV MCB DEMO
[Link]
Fault clearing time of a CB
Relaying time:
• The relaying time for electromechanical relays can vary from about one cycle to five
cycles.
• Static relays are faster than electromechanical relays.
• Numerical relays give very fast operation and their relaying time is within one cycle.
CB operating time:
• The contact opening time of the circuit breaker may be between
about one and three cycles. The arcing time is now generally
between one and two half-cycles, depending upon the instant in
the current half-cycles at which the contacts part.
• Therefore, fast relays and modern circuit breakers make it possible
to achieve fault clearance in as little as about three cycles of 50 Hz
current, but the time varies considerably from system to system.
Arc Voltage
• The voltage drop across the arc is called arc voltage.
Arc Interruption
Two methods of Arc Interruption
High Resistance Interruption
Current Zero Interruption
High Resistance Interruption
Arc resistance is increased
to reduce the current to a value insufficient to maintain the
arc
Arc resistance can be increased by
Cooling
Lengthening
Constraining
Splitting
Employed in low power AC & DC CB’s
Current Zero Interruption
Applicable to AC CB’s
In AC Supply Current wave passes thro’
zero point
100 times in a second for 50Hz
This feature of ac is utilized for Arc
interruption
Current is not interrupted at any point other than zero
current instant
Otherwisea high transient voltage will occur across the
contact gap
Current is not allowed to rise again after zero current
crossing
Recovery Rate Theory
Energy Balance Theory
Recovery Rate Theory
Arc is a column of ionized gases
To extinguish the arc, the electrons & ions are to be removed
from the gap
Immediately after the current reaches a natural zero
Ions & electrons can be removed
Either by recombining them into neutral molecules or
by sweeping them away by inserting insulating medium into the
gap
Arc is interrupted if ions are removed from the
gap at a rate faster than the rate of ionization
The rate at which the gap recovers its dielectric
strength is compared with the rate at which the
re-striking voltage across the gap rises.
If the dielectric strength increases more rapidly
than the re-striking voltage
The Arc is extinguished
If the re-striking voltage rises more rapidly than the
dielectric strength
The ionization persist & breakdown of the gap
occurs
Resulting in an arc for another cycle
Energy Balance Theory
• Space between the contacts contains
some ionized gas, immediately after
current zero, it has a finite post zero
resistance.
• At current zero moment, power is zero
because re-striking voltage is zero.
When arc is finally extinguished
Power again become zero
Gap is fully de-ionized
Resistance is infinitely high
In between these Arc starting to extinguish
First
the power increases, reaches a maximum value
Then decreases and finally reaches zero value
Due to rise of re-striking voltage & Associated current
Energy is generated in the space between the contacts
The energy appears in the form of heat
CB’s is designed to remove the heat as early as possible
by cooling the gap
Cooling is achieved by
Blast of air at a pressure
Flow of Oil at higher velocity & pressure
If the rate of removal of heat is faster than the
rate of heat generation
Arc is extinguished
If the rate of heat generation is more than the
rate of heat dissipation
The space breaks down again resulting in an arc
for another half cycle
RESTRIKING VOLTAGE AND RECOVERY VOLTAGE
• The voltage across the contacts of the circuit breaker is arc voltage when the
arc persists.
• This voltage becomes the system voltage when the arc is extinguished.
• The arc is extinguished at the instant of current zero.
• After the arc has been extinguished, the voltage across the breaker terminals
does not normalise instantaneously but it oscillates and there is a transient
condition.
• The transient voltage which appears across the breaker contacts at the
instant of arc being extinguished is known as restriking voltage.
• The power frequency rms voltage, which appears across the breaker contacts
after the arc is finally extinguished and transient oscillations die out is called
recovery voltage.
During this short period which is of interest, the change in the power frequency term is very little
and, hence negligible, because cos wt ~=1
Resistance Switching
• To reduce the restriking voltage, RRRV and severity of the
transient oscillations, a resistance is connected across the
contacts of the circuit breaker.
• This is known as resistance switching.
• The resistance is in parallel with the arc.
• A part of the arc current flows through this resistance resulting
in a decrease in the arc current and increase in the deionisation
of the arc path and resistance of the arc.
• This process continues and the current through the shunt
resistance increases and arc current decreases. Due to the
decrease in the arc current, restriking voltage and RRRV are
reduced.
Current Chopping
• When low inductive current is being interrupted and the
arc quenching force of the circuit breaker is more than
necessary to interrupt a low magnitude of current, the
current will be interrupted before its natural zero
instant.
• In such a situation, the energy stored in the magnetic
field appears in the form of high voltage across the
stray capacitance, which will cause restriking of the arc.
• The energy stored in the magnetic
field is ½ L i , if i is the instantaneous value of the
2
current which is interrupted.
• This will appear in the form of electrostatic energy equal
to ½ Cv . As these two energies are equal, they can be
2
related as follows.
• If the value of v is more than the withstanding capacity
of
the gap between the contacts, the arc appears again.
Since the quenching force is more, the current is again
chopped.
• This phenomenon continues till the value of v becomes
less than the withstanding capacity of the gap.
• The theoretical value
of v is called the prospective value of the voltage.
Classification of CB
Voltage Classification
Low Voltage CB Less than 1 kV
Medium Voltage CB 1kV to 52kV
High Voltage CB 66kV to 220kV
Extra High Voltage CB 300kV to 765 kV
Ultra High Voltage CB Above 765kV
,
TYPES OF CBs
Conditions for CB Operation
Overload
Short Circuit
Earth Fault
Local Maintenance work
Any other Abnormal operation
Circuit Breakers Requirements
Opens & closes in shortest possible time
Conducts rated current
Withstands thermally & mechanically any short circuit
Maintains its voltage to earth across open contacts
Does not create over voltages during circuit opening
Easy to maintain
Not very expensive
Particulars of a Circuit Breaker
Medium for arc extinction
Rated line voltage
Rated breaking current
Total breaking time
Type of construction
Outdoor, indoor. etc
Type of operating mechanism
Other additional features such as switching resistors
Rupturing Capacity
Rupturing Capacity represents the Max. power a
CB can Safely interrupt
Factors Determine Rupturing Capacity
Length & Speed of Breaking
Position of Arcing Contacts
Dimensions of Parts
Mechanical Strength of Breaker
Selection of Circuit Breakers
Type Arc Quenching Voltage Rating
Medium &Breaking Capacity
MCB/ Air at 400-600V ;
MCCB Atmospheric For Small Current
Pressure Rating -10 to 30KA
Air- Air at 400-11KV;
Break Atmospheric 5-750MVA
CB Pressure
Minimum Transformer Oil 3.3KV to 220KV;
Oil CB 150-25000MVA
Selection of Circuit Breakers
Classification of Circuit Breakers
Oil CB
Air Blast CB
Sulphur Hexafluroride(SF6)
CB
Vacuum CB
Oil Circuit Breakers
Oil is used as quenching media to
quench the arc produced during
opening
Has insulating property
Good cooling property
Energy absorber
Disadvantages
Highlyinflammable
Production of carbon particles
Plain-break oil CB’s
Fixed & moving contact immersed in oil
Metal tank is strong, weather tight &
earthed
When contacts separate there is a severe
arc
Which decomposes the oil into gases
Gas obtained is mainly hydrogen
Volume of gases produced is about
thousand times that of the oil decomposed
Plain Break Oil Circuit Breaker
Oil is pushed away from arc & the gaseous
medium surrounds the arc
Arc quenching factors are as follows:
Elongation of the arc
Formation of gaseous medium in between the
fixed & moving contacts
This has a high heat conductivity & high dielectric
strength
Turbulent motion of the oil resulting from the
gases passing through it
A large gaseous pressure is developed
Because a large amount of energy is dissipated
within the tank
The tank of the CB is made strong to withstand
such a large pressure
When gas is formed around the arc
Oil is displaced around the contacts
To accommodate the displaced oil
An air cushion between the oil surface & the
tank is essential
Air cushion also absorb the mechanical shock
produced due to upward oil movement
It is necessary to provide vent fitted in the tank
cover for the gas outlet
A sufficient level of oil above the contacts is
required to provide substantial oil pressure at
the arc
Certain gap between the contacts must be
created before the arc interruption occurs
To achieve this, the speed of the break should
be as high as possible
The two breaks is series provide rapid arc
elongation without the need for a fast contact
Double break provides ample gap distance
Before arc interruption
Limitations of Plain break Oil CB
Unequal voltage
distribution across the
breaks
C is capacitance
between Fixed &
Moving contacts
C’ is the capacitance
between moving
contact & Earth
V1 is the voltage across the first contact
V2 is the voltage across the second
contact
Suppose fault current is i
Voltages V1 & V2 will be expresses as
follows:
V = i/C
1
V = i/(C+C’)
2
V1/V2 = (C+C’)/C
To equalize the voltage distribution across
the breaks, non-linear resistors are
connected across each break
Applications of Plain Break CB’s
Employed for breaking low current at
comparatively lower voltages
Used in Low voltage DC circuit
Used in Low voltage AC distribution circuits
Can be used up to 11KV with an interrupting
capacity up to 250MVA
Size become unduly large for higher voltage
Require large amount of Tr. Oil
Not suitable for auto re-closing
Speed is slow
Self-generated Pressure Oil CB
Arc energy is utilized to generate a
high pressure in a chamber
Knownas explosion pot or pressure
chamber or arc controlling device
Contacts are enclosed within the pot
Pot is made of insulating material &
placed in the tank
Have high interrupting Capacity
Arcing time is reduced
Since the pressure is developed by
the arc itself It depends upon the
magnitude of the current
Pressure will be low at low current
Pressure will be high at high current
This creates a problem in designing a
suitable explosion pot
At low current, pressure generated
should be sufficient to extinguish the
arc
At high current, the pressure should
not be too high so as to burst the pot
Various types of explosion pots have
been developed to suit various
requirements
Plain explosion pot
Simplest form of an
explosion pot
When the moving
contact separates a
severe arc is formed
Oil is decomposed &
gas is produced
Generate a high
pressure within the
pot
High Pressure developed causes turbulent
flow of streams of the gas into the arc
Resulting in arc extinction
If arc extinction does not occurs within the
pot
It occurs immediately after the MC leaves the
pot due to the high velocity axial blast of the
gas
Which is released through the throat
Arc extinction in the plain explosion pot is
performed axially
Known as axially extinction pot
Not suitable for breaking heavy
current
Pot may explodes due to very high
pressure developed
During extinguishing large current
At low currents
Arcing time is more
This type of explosion pot is
suitable for the interruption of
Current of Medium voltage
Cross-jet Explosion Pot
Suitable for High Current interruptions
Arc splitters are used to obtain an
increased arc length for a given
amount of contact travel
When the moving contact is
separated from the fixed contact, an
arc is formed
The arc is pushed into the arc
splitters & finally it is extinguished
In this type of a pot, the oil blast
is across the arc
Hence known as a cross-jet
explosion pot
Cross-jet Explosion pot
Self Compensated Explosion Pot
It is a combination of a Cross-jet
explosion pot & a plain explosion pot
Its upper portion is a cross-explosion
pot
Lower portion is a plain explosion pot
On heavy current the rate of gas
generation is very high
Pressure developed is very high
Arc extinction takes place when the
first or second lateral orifice of the
arc splitter is covered by the MC
The pot operates as a cross-jet
explosion pot
When the current is low, the pressure
is also low in the beginning
So the arc is not extinguished when
the tip of the MC is in the upper
portion of the pot
By the time the MC reaches the
orifice at the bottom of the pot,
sufficient pressure is developed
Arc is extinguished, when the tip of
the MC comes out of the throat
Arc is extinguished by the plain
explosion pot action
Double Break Oil Circuit Breaker
Used to obtain high speed arc
interruption at low currents
Employs an intermediate contact
between
The fixed & moving contacts
When the Moving contact separates,
the intermediate contact also follows it
Arc first appears between Fixed &
intermediate contact
Soon after, the intermediate contact
stops & a second arc appears
Between the intermediate contact
and the moving contact
The second arc is extinguished
quickly by employing gas pressure &
Oil momentum
Developed by the first arc
Classification
Axialblast pot
Cross blast pot
Commercial Oil CB
Minimum Oil Circuit Breakers
Bulk Oil Circuit Breakers
Minimum Oil Circuit Breakers
Used in large numbers for Medium
voltage Distribution system
Low Capacity Applications
Low Fault MVA
Up to 11KV Application
Disadvantages of using oil as
quenching media
MOCB does not employ a steel tank
Its container is made of porcelain or other
insulating material
Consists of two sections
Upper chamber
Lower chamber
Upper chamber contains
An arc control device
Fixed and moving contacts
Lower chamber acts as
An insulating support & Contains the
operating mechanism
Two chambers are filled with oil
But physically separated from each
other
Arc control chamber is placed in a resin
bounded glass fiber cylinder
Also filled with oil
Fiber glass cylinder is then placed in a
porcelain cylinder
Annual space between fiber glass
cylinder & Porcelain insulator is filled
with oil
Minimum Oil Circuit Breaker
Advantages
1. Current transformers can be
accommodated on the bushings.
2. Can be used for 3.3kV to 420kV.
Bulk Oil Circuit Breaker
Used in large numbers for High voltage
Distribution system
High Capacity Applications
High Fault MVA
Up to 110KV Applications
Oil Performs two function
Acts as an arc extinguishing medium
Serves as insulation between live
terminals & earth
Limitations of Bulk Oil CB
Requires a huge amount of oil at HV
Flammability
High maintenance cost
Bulk Oil Circuit Breaker
Air Blast CB
Compressed air at a
pressure of
20-30Kg/cm2 is
employed
As an arc quenching
medium
Air blast CB are
suitable for operating
voltages of 132Kv &
Above
Air Blast Circuit Breakers
Air is compressed in reservoir up to 14
atmospheric pressure.
The compressed air is released &
directed towards the arc at high velocity
The arc is then extinguished
Suitable for Medium Voltage Application
ACB’s are also used for switching motors
of higher rating
Air blast Circuit Breaker
Advantages of ACB
Cheapness & Free availability of the
interrupting medium
Chemical stability & inertness of air
High speed operation
Elimination of fire hazard
Short & consistent arcing time
Less burning of contact
Less maintenance
Suitability of frequent operation
Facility for high speed re-closure
Limitations of ACB
An air compressor plant has to be installed and
maintained
A high level of noise, when air is discharged
Problem of current chopping
Problem of re-striking voltage
Types of Air Blast CB
Cross Blast CB
Axial Blast CB
Cross Blast Circuit Breakers
A HP blast of air is directed
perpendicularly
To the arc for its interruption
Arc is forced into a suitable chute
Sufficient lengthening of the arc is
obtained
Resulting
in the introduction of
appreciable resistance in the arc
itself
Contd.
Resistance switching is not
common in this type of CB
Cross blast CB are suitable for
interrupting
High Current up to 100KA @
comparatively Lower voltage
Axial Blast Circuit Breakers
A HP blast of air is directed longitudinally
In line with the arc
Axial blast are suitable for EHV & Super
HV applications
Interrupting chamber is fully enclosed in
porcelain tubes
Resistance switching is employed
To reduce transient over voltages
Air-Break Circuit Breakers
Oil Circuit Breakers are not suitable
for Heavy current interruption at LV
Due to carbonization of oil
Air-break CB are quite suitable for
high current interruption at LV
Air at Atmospheric pressure is used
as an arc extinguishing medium
Principle of increasing Arc R is
employed for Arc interruption
Employs two pairs of contacts
Main contact & Arcing contacts
Main contacts carry current
When the breaker is in closed
position
Main contacts have low contact
resistance
When contacts are opened
The main contacts separate first &
the arcing contact still remain
closed
Current is shifted from the main
contacts to the arcing contact
Arcing contacts separate late on &
the arc is drawn between them
Arc R is increased by lengthening,
splitting & Cooling the arc
Air Break Circuit Breaker
Arc length is rapidly increased
employing
Arc runners & Arc chutes
Arc moves upward by both
electromagnetic & Thermal effects
Moves along the arc runner & then
it is forced into a chute
Split by arc splitters
A blowout coil is employed to
provide magnetic filed to speed up
arc movement
To direct the arc into arc splitters
Arc interruption is assisted by
current zero
High R is obtained near current
zero
Air Break Circuit Breaker
ACB’s are required to CARRY short
circuit current for a specified time
Which is usually one second
Is invariably more than what the
downstream devices require to interrupt
faults
In case the downstream devices fail to
interrupt the fault current, the, breaker
acts as a back-up protective device
Air Break Circuit Breaker
SF6 CIRCUIT BREAKERS
Novel properties of SF6
• Sulphur Hexafluoride or SF6 circuit breaker is a type of circuit breaker that
uses pressurized SF6 gas (@14kg/cm^2 )to extinguish the arc.
• It has good dielectric strength.
• It is an electronegative gas.
• Inert, non-toxic, non-flammable and heavy gas.
• It is a dielectric gas having superior insulating property.
• Excellent arc quenching properties far better than air or oil.
• Emission free SF6 can protect the environment- is the most potent
greenhouse gas known. It is 22,800 times more effective at trapping infrared
radiation than an equivalent amount of CO 2 .
• It is used for arc quenching in high voltage circuit breakers up to 800 kV in
power stations, electrical grids.
Electronegativity of SF6
• SF6 gas has very high electronegativity. It has a strong
tendency to absorb free electrons. When an arc is struck
between the contacts, it absorbs the free electrons from it. It
converts into negative ions which are heavier than electrons.
Due to its heavyweight, its mobility is reduced. Therefore, the
mobility of the charges in SF6 gas has low mobility which
enhances the dielectric strength of the medium since the
movement of charges is responsible for current flow.
But decomposes to SF4, SF2, S2,F2,S & F @1000°C &
above
It has superior dielectric strength which is directly proportional to the
pressure. Its arc quenching capabilities is almost 100 times better than
air. The frequency of the voltage does not affect its dielectric strength.
• Corona inception voltage
Corona inception voltage for SF6 in a non-uniform electric field is also considerably
higher than that for air.
• Dielectric constant
Because of being non-polar (i.e., dipole moment is zero), the dielectric constant of SF6 is independent
of the frequency of the applied voltage. Further, the dielectric constant changes by only 7% over a
pressure range of 0 to 22 atmospheres.
• Arc-interrupting capacity
Construction of SF6 Circuit Breaker
• The SF6 circuit breakers consist of two main parts:
I) Interrupter Unit
• The interrupter unit consists of two types of current-carrying
contacts i.e. the fixed and movable contact. The fixed contacts as
its name suggest do not move while the movable contact moves
back and forth using an arm actuated by a mechanism.
• There is a vent for the inlet and outlet of the pressurized SF6 gas
to cool off the arc as well as extinguish it.
II)Gas System
• The SF6 is a very expensive gas and the emission of its product
gases is hazardous for the environment. Therefore, a closed gas
system is used, where the used SF6 is recombined for reuse. Its
pressure is also maintained as its dielectric strength greatly
depends upon it.
Types of SF6 Circuit Breaker
• Non-Puffer Type SF6 Circuit Breaker (This circuit
breaker works on the same principle as air blast
CB.)
Single Pressure Puffer Type SF6 Circuit Breaker
• Double Pressure Puffer Type SF6 Circuit Breaker
Double Pressure SF6 CB
Early design of SF6 CB
Operating Principle is similar to that of air-blast
CB
SF6 Gas from HP compartment is released to
the LP compartment
To extinguish the arc
Need for Auxiliaries such as
Compressors, filters & Control devices
Nowadays becomes obsolete
Double Pressure SF6 CB
Puffer type SF6 CB
Also called as single pressure or impulse type
SF6 CB
Gas is pressurized by a moving cylinder system
& is released through a nozzle
To quench the arc
Moving cylinder & moving contacts are coupled
together
When the contacts separate & Moving cylinder
moves
The trapped gas is compressed
SF6 Circuit Breakers
The trapped gas is released thro’ a
nozzle & flows axially to quench the arc
There are two types of tank design
Live
Tank design
Dead Tank design
In live tank design, interrupters are
supported on porcelain insulators
Preferred for outdoor sub-stations
In dead tank design, interrupters are
placed in SF6 filled tank,
Which is at earth potential
ADVANTAGES
DISADVANTAGES
• Problem of imperfect sealing –leakage of gas
• Suffocation
• Arced SF6 is poisonous and should not be inhaled
• Influx of moisture
• Special facilities for transportation of gas-costly
• At 15 atm pressure, Gas liquifies at a temp of 10
deg C. Hence thermostatically controlled heaters
are needed at low temp.
Vacuum Circuit Breaker
Interruption chamber is vacuumed
Vacuum as quenching media
No gas which is ionized to form the arc
An arc is formed from the vaporized
contact material
Small mechanical energy required for
tripping
Features include high speed interrupting
time
Vacuum Circuit Breakers
Long working life due to minimized contact
wear & shock
Very small damage to contacts (life up to 30
years).
Maintenance of circuit breaker is reduced
Service interval lies between 10,000 & 20,000
operations
Used for Feeders & Mains protection
Rugged Housing & Small in size
Superior Than SF Breaker
6
Advantages
Suitability for repeated operations,
least maintenance,
silent operation,
long life,
high speed of dielectric recovery,
less weight of moving parts
Vacuum Circuit Breakers
Vacuum Circuit Breakers
Earth Leakage Circuit Breaker
• An Earth Leakage Circuit Breaker (ELCB) is a device
used to
directly detect currents leaking to earth from an
installation and cut the power.
• There are two types of ELCBs:
1. Voltage Earth Leakage Circuit Breaker (voltage-
ELCB)
2. Current Earth Leakage Circuit Breaker (Current-ELCB).
Refer the material (pdf) sent
Q1
Q2
Q3
Q4
Q5
Testing of CB
• Routine test
• Type test
Testing of Circuit Breakers
Types of Tests
Routine Test
Performed on every pieces of CB’s in the
premises of Manufacturers
To confirm the proper functioning of CB
Type Tests
Performed in a High Voltage laboratory
Performed on sample pieces of CB of each
type
To confirm their characteristics & rated
capacities according to the design
All routine & type tests are performed according
To Indian Standard (IS) Codes or
To International Electromechanical Commission
(IEC) codes or
British Standard (BS) Codes
Important Type tests are
Breaking Capacity
Making Capacity
Short-time current rating
For CB’s of smaller capacity
Tests are carried out by direct testing techniques
For CB’s of larger capacity
Tests are carried out by Synthetic testing
method
Other Tests on CB’s
Mechanical tests
Thermal tests
Dielectric tests
Power frequency & Impulse tests
Capacitive charging current breaking
tests
Small inductive breaking currents
Short-Circuit Testing Stations
Two Types of Short circuit testing
stations
Field type Testing Station
Power reqd. for testing is derived
from large Power Station.
Laboratory type Testing Station
Power reqd. for testing is taken from
specially designed generators
Which are installed in the laboratory for
testing
Field type Testing Station
Advantages
Large amount of power is easily available for
testing
Economical method of testing CB’s for HVCB
Limitations
Lacks flexibility
For R&D work, tests cannot be repeated again &
again without disturbing the PS
Power available for testing varies, depending
upon the loading conditions of the system
It is very difficult to control the transient recovery
voltage, RRRV, etc
Laboratory Testing Stations
For R&D work, tests can be carried out again & again to
confirm the designed characteristics & Capacity
Advantages
For R&D work, tests can be carried out again & again to
confirm the designed characteristics & Capacity
Current, Voltage, Re-striking voltage, RRRV, etc can be
controlled conveniently
Test for CB’s of large capacity can be carried out using
synthetic testing
Limitations
High cost of installation
Availability of limited power for testing of CB
Laboratory Testing Stations consists of
Short Circuit Generator
Short Circuit transformer
Master Circuit Breaker
Making Switch
Capacitors
Reactors and Resistors
Short Circuit Generator
Used to provide power for testing
Design of such generator is different from a
conventional generator
Have very low Reactance to give max. short
circuit output
To withstand high electromagnetic forces their
windings are specially braced & made rugged
Provided with Flywheels to supply kinetic
energy during short circuits.
Also helps in speed regulation
Generator driven by three phase induction
motor
Contd.
SC current has a demagnetizing effect on the
field of generator
Which results in reducing the field current
Consequently, the generator's emf is reduced
Impulse excitation or Super excitation is
employed
To counter act the demagnetization effect of
armature reaction
At the time of short circuit
The field current is increased to about 8 to 10
times its nominal value
Short Circuit Transformer
Has a low reactance
Designed to withstand repeated SC
To get different voltages for tests
Its windings are arranged in sections
By series & parallel combinations of these
windings, the desired test voltage is obtained
To get lower voltage than the generated
voltage, a three phase transformer is used
To get higher voltages than the generated
voltages, normally banks of single phase
transformers are employed
Master Circuit Breaker
Used as a Backup CB
If the CB under test fails to operate
The master CB opens
Master CB is set to operate at a pre determined
time after the initiation of the SC
After every test, it isolates the CB under test
from the supply source
Its capacity is more than the capacity of the CB
under Test
Making Switch
Used to apply SC current at the desired
moment during the test
Closed after closing the master CB & the test
CB
It must be bounce free to avoid its burning or
contact welding
To achieve this, a high pressure is used in the
chamber
Its speed is also kept high
Capacitors
Used to control RRRV
Used in synthetic testing
Also used for voltage measurement
purpose
Reactors & Resistors
Used to control SC test current
Also control power factor
Resistor controls the rate of decay of the DC
component of the current
Control the transient recovery voltage
Testing Procedure
During SC test, several switching operations
are performed in a sequence in a very short
time
Sequence of switching operations for breaking
capacity test is as follows:
After running the driving motor of the SC
Generator to a certain speed it is switched off
Impulse excitation is switched On
Master CB is closed
Contd.
Making switch is closed
CB under test is opened
Exciter Circuit of the SC generator is switched off
It is not possible to perform this sequence of
operations manually
An automatic control is used for the purpose
Since the time of operation for the above
sequence is of the order of 0.2 second
Direct Testing
The CB is tested under the conditions
Which is actually exist on Power System
It is subjected to re-striking voltage
Which is expected in practical situations
The Reactor X is to control SC current
C,R1 &R2 are to adjust transient re-
striking voltage
Test for Breaking Capacity
First of all, the Master CB & the CB under test
are closed
Then the SC current is passed by closing the
making switch
SC current is interrupted by opening the CB
under test at the desired moment
The following measurements are taken
Symmetrical breaking current
Asymmetrical breaking current
Recovery volatge
Freq. of oscillation & RRRV
Contd.
The CB must be capable of breaking all
currents up to its rated capacity
It is not possible to test at all values of
current
Tests are performed at 10%, 30%, 60% &
100% of its rated breaking capacity
Test for Making Capacity
The Master CB & Making Switch are closed first
Then the SC is initiated by closing the CB Under
test
Rated making current i.e., the peak value of the
first major loop of SC current wave is measured
Duty Cycle Test
B – 3 – B – 3 – B tests are performed at
10%, 30% and 60% of the rated symmetrical
braking capacity
B – 3 MB – 3 – MB tests performed at
Not less than 100% of rated symmetrical
breaking capacity
Not less than 100% of the rated making capacity
Can also be performed as two separate tests
M – 3 – M make test
B – 3 – B – 3 – B break test
Contd.
B – 3 – B – 3 – B Tests are performed at
Not less than 100% of the rated Asymmetrical breaking capacity
B denotes breaking operation
M denotes making operation
MB denotes the making operation followed by the breaking
operation without any intentional time delay
Cost of Breaker
The cost of CB depends on
Working Voltage in KV
Operating Capacity in Amps
Rupturing Capacity in MVA
Speed of Operation in milliseconds
CB Capacity in MVA
Capacity of the CB always expressed in terms
of Fault MVA
Cost of CB Depends upon the fault level
Fault Level Depends on
Generation end
Transmission end
Distribution end
Auto-Reclosuring in Circuit Breakers
In electric power distribution, an autoreclosure is a circuit breaker equipped with a
mechanism that can automatically close the breaker after it has been opened due to a fault.
Autoreclosure schemes are used particularly in coordinated protection schemes for
overhead line power distribution circuits. These circuits are prone to transient faults such as
nearby lightning strikes, wind-borne debris, animals climbing the insulators etc. This fact is
employed as a basis for auto reclosures schemes. In such schemes, after the relays at both ends
of the line have picked up, the circuit breakers are tripped as far as possible at the same time
and reclosed after time has been allowed for deionization. The fault disappears if it is transient,
and line is fully restored to service after the reclosure. A double or triple attempt of isolation and
reclosure can be made if the fault is not cleared after the first reclosure. If the fault persists, the
breaker may permanently open till it is reset manually.