Luminaire classification
Emergency lighting luminaires shall be classified and marked in accordance with their construction,
as follows:
A unique designation denoting the type, mode of operation, the facilities included and the rated
duration of operation of the luminaire shall be affixed to the luminaire in a conspicuous position.
The designation shall consist of a rectangle divided into three or four segments each containing one
or more symbols. Relevant to the construction of the designation, each symbol in a segment shall
indicate a letter or a figure or a point of no indication.
The shape of the emergency lighting luminaire designation shall be as follows:
* * **** ***
The segments and symbols shall be completed by letters and figures that indicate the construction
of a luminaire.
a) The first segment shall contain one symbol that indicates TYPE, i.e.
X: self-contained, or
Z: central supply.
b) The second