Sequence Component Modelling in Transformer and Transmission Line
Sequence Component Modelling in Transformer and Transmission Line
Problem 2
S. A. Soman
Problem 1
Problem 2
Outline
Problem 1
Problem 2
S. A. Soman
Problem 1
Problem 2
Problem 1
Figure shows the single line diagram of a 13.8kV system connected to a 480V bus through a 13.8kV/480V transformer. Two motor loads of 400hp and 600hp are connected to the bus through three parallel three core copper cables. If a 3 phase bolted fault occurs at F1 , compute the fault currents. Repeat the calculations for fault at F2 .
S. A. Soman
Problem 1
Problem 2
Problem 2
Figure shows the single line diagram of a 3 bus system. The sequence data for transmission lines and generators are given in table. If a bolted single line to ground fault occurs at F, calculate the fault current. If the fault impedance is j0.1 pu; what will be the fault current?
S. A. Soman
Problem 1
Problem 2
Problem 2 (Contd.)
Description Generator-A Generator-B Transmission Line 1 Transmission Line 2 Transmission Line 3 Transmission Line 4
Sequence Data in pu Zero Positive Negative j0.03 j0.25 j0.15 j0.02 j0.20 j0.12 j0.24 j0.08 j0.08 j0.65 j0.13 j0.13 j0.18 j0.06 j0.06 j0.18 j0.06 j0.06
S. A. Soman
Problem 1
Problem 2
Thank You
S. A. Soman