12MW, 3MW Protection

1. The document describes various protection schemes and their set points for a 12MW alternator, including generator differential protection, frequency protection, power protection, over/under current protection, earth fault protection, V/Hz protection, dead machine protection, field failure protection and voltage protection. 2. It provides status, function, settings and time delays for each protection scheme, such as enabling the under frequency protection if frequency drops below 47.5Hz with a 2 second time delay. 3. The set points for the protection schemes are specified, for example the generator differential has a percentage bias of 100mA and the power protection has a reverse power setting of 15kW with a 2 second time delay.

Uploaded by

Ram Krishna
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
81 views6 pages

12MW, 3MW Protection

1. The document describes various protection schemes and their set points for a 12MW alternator, including generator differential protection, frequency protection, power protection, over/under current protection, earth fault protection, V/Hz protection, dead machine protection, field failure protection and voltage protection. 2. It provides status, function, settings and time delays for each protection scheme, such as enabling the under frequency protection if frequency drops below 47.5Hz with a 2 second time delay. 3. The set points for the protection schemes are specified, for example the generator differential has a percentage bias of 100mA and the power protection has a reverse power setting of 15kW with a 2 second time delay.

Uploaded by

Ram Krishna
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 6

12MW ALTERNATOR PROTECTION SCHMES AND THEIR SET POINTS

1. Generator Differential -Group 1: Gen Diff Function Gen Difff Is 1 Gen Diff K1 Gen Diff Is2 Gen Diff K2 : : : : : Percentage Bias 100.00 mA 0.000% 1.200 A 150.0%

9.Frequency Protection Under Frequency :F < 1 Status F < 1 Setting F < 1 Time Delay F < 2 Status F < 2 Setting F < 2 Time Delay F < 3 Status F < 4 Status F < Function Link Over Frequency :F > 1 Status F > 1 Setting F > 1 Time Delay F > 2 Status F > 2 Setting F > 2 Time Delay : : : : : : Enabled 52.50 Hz 2.000 s Enabled 53.50 Hz 1.000 s : : : : : : : : : Enabled 47.70 Hz 2.00s Enabled 47.50 Hz 250.00 ms Disabled Disabled 000

2.Power Group 1 Operatig Mode Power 1 Function - P>1 Setting Power 1 Time delay Power 1 Do Timer P 1 Poledead Inch Power 2 Function P < 2 Setting Power 2 Time Delay Power 2 Do Timer P 2 Poledead Inch : : : : : : : : : : : Generating Reverse 4.00w 2.000s 0.000s Enablaed Low Forward 4.00w 2.000s 0.000s Enablaed

3.Over Current I > 1 Functon I > 2 Functin : : Disabled Disabled

10.CB Fail & I < Under current :I < Current Set I N < Current Set I Sef < Current I < CT Source : : : : : : Measured DT 100.00mA 300.00ms 0.000ms Disabled : : : : 700.0 mA 100.0 mA 20.00 mA IA -1,IB -1,IC -1

4.Earth Fault IN > Input IN > 1 Function IN > 1 Current IN > 1 Time Delay IN > 1 Reset IN > 2 Functon

11.NPs Thermal I 2 > 1 Alarm I 2 > 1 Current I 2 > 1 Time Delay I 2 > 2 Trip I 2 > 2 Current Set I 2 > 2 K Setting I 2 > 2 K Reset I 2 > 2 t max I 2 > 2 t min : : : : : : : : : Enabled 80.00 mA 3.000 s Enabled 100.0 mA 15.0 s 15.0 s 1.00k s 250.00 ms

5.SEF/REF Protection Sef/Ref Options I Ref > Is : : Hi > Ref 100.0ms

6.V/Hz Protection 12.System Backup V/Hz Alarm Status V/Hz Alarm Set V/Hz Alarm Delay V/Hz Trip Function V/Hz Trip Set V/Hz Trip Delay : : : : : : Enabled 2.420 V/Hz 1.000s DT 2.500 V/Hz 2.000s Backup Function Vector Rotation V Dep OC Char V Dep OC I > set V Dep OC Delay V Dep OC t Reset V Dep OC V < 1 Set V Dep OC K Reset : : : : : : : : Voltage Controlled None DT 1.110 A 2.000 s 500.0 ms 80.00 v 0.500

7.Dead Machine Dead M/c Status Dead M/c I > Dead M/c V < Dead M/c t pu Dead M/c Do : : : : : Enabled 2.000 A 66.00 v 0.000s 0.000s

13.Field Failure Protection F.Fail Alarm Status F.Fail Alarm Angle F.Fail Alarm Delay F.Fail 1 Status F.Fail 1 Xa1 F.Fail 1 Xab1 F.Fail Time Delay F.Fail Do Timer F.Fail 2 Status F.Fail 2 Xa2 F.Fail 2 Xb2 F.Fail 2 Time Delay F.Fail 2 Do Timer : : : : : : : : : : : : : Enabled 15.00 deg 4.00 s Enabled 9.00 ohms 115.0 ohms 5.000 s 8.000 s Enabled 9.00 ohms 115.0 ohms 5.000 s 8.000 s

8.Voltage Protection Under Voltage :V < Measurement mode V < Operating Mode V < 1 Function V < 1 Voltage set V < 1 Time Delay V < 1 Pole dead Inch V < 2 Status V < 2 Voltage Set V < 2 Time Delay V < 2 Pole dead Inch Over Voltage :V > Measurement mode V > Operate Mode V > 1 Function V > 1 Voltage Set V > 1 Time Delay V > 2 Status V > 2 Voltage Set V > 2 Time Delay : : : : : : : : Phase - Phase Any Phase DT 126.0 v 2.000 s Enabled 132.0 v 500.0 ms : : : : : : : : : : Phase - Phase Any Phase DT 97.00 v 2.000s Enabled Enabled 88.0 v 500.00 ms Enabled

SET POINTS

age Controlled

3 MW ALTERNATOR PROTECTION SCHMES AND THEIR SET POINTS

1. Generator Differential -Group 1: Gen Diff Function Gen Difff Is 1 Gen Diff K1 Gen Diff Is2 Gen Diff K2 : : : : : Percentage Bias 100.00 mA 0.000% 1.200 A 150.0%

6.Frequency Protection Under Frequency :F < 1 Status F < 1 Setting F < 1 Time Delay F < 2 Status F < 2 Setting F < 2 Time Delay F < 3 Status F < 4 Status F < Function Link Over Frequency :F > 1 Status F > 1 Setting F > 1 Time Delay F > 2 Status F > 2 Setting F > 2 Time Delay : : : : : : Enabled 52.50 Hz 2.000 s Enabled 51.50 Hz 2.000 s : : : : : : : : : Enabled 47.50 Hz 2.00s Enabled 47.50 Hz 1.000 s Disabled Disabled 000

2.Power Group 1 Operatig Mode Power 1 Function - P>1 Setting Power 1 Time delay Power 1 Do Timer P 1 Poledead Inch Power 2 Function : : : : : : : Generating Reverse 15.00w 2.000s 0.000s Enablaed Disabled

3.Earth Fault IN > Input IN > 1 Function IN > 1 Current IN > 1 Time Delay IN > 1 Reset IN > 2 Functon : : : : : : Measured DT 50.00mA 1.000s 0.000ms Disabled

07.CB Fail & I < Under current :I < Current Set I N < Current Set I Sef < Current I < CT Source : : : : 100.0 mA 100.0 mA 20.00 mA IA -1,IB -1,IC -1

4.V/Hz Protection V/Hz Alarm Status V/Hz Alarm Set V/Hz Alarm Delay V/Hz Trip Function V/Hz Trip Set V/Hz Trip Delay : : : : : : Enabled 2.310 V/Hz 1.000s DT 2.420 V/Hz 1.000s

08.NPs Thermal I 2 > 1 Alarm I 2 > 1 Current I 2 > 1 Time Delay I 2 > 2 Trip I 2 > 2 Current Set I 2 > 2 K Setting I 2 > 2 K Reset I 2 > 2 t max I 2 > 2 t min : : : : : : : : : Enabled 80.00 mA 3.000 s Enabled 100.0 mA 15.0 s 15.0 s 1.00k s 250.00 ms

5.Voltage Protection Under Voltage :V < Measurement mode V < Operating Mode : : Phase - Phase Any Phase

V < 1 Function V < 1 Voltage set V < 1 Time Delay V < 1 Pole dead Inch V < 2 Status V < 2 Voltage Set V < 2 Time Delay V < 2 Pole dead Inch Over Voltage :V > Measurement mode V > Operate Mode V > 1 Function V > 2 Status V > 2 Voltage Set V > 2 Time Delay

: : : : : : : :

DT 90.00 v 2.000s Enabled Enabled 80.0 v 2.000 s Enabled

09.System Backup Backup Function Vector Rotation V Dep OC Char V Dep OC I > set V Dep OC Delay V Dep OC t Reset V Dep OC V < 1 Set V Dep OC K Reset : : : : : : : : Voltage Controlled None DT 1.000 A 2.000 s 500.0 ms 80.00 v 1.000

: : : : : :

Phase - Phase Any Phase Disabled Enabled 126.0 v 1.000 s

10.Field Failure Protection F.Fail Alarm Status F.Fail Alarm Angle F.Fail Alarm Delay F.Fail 1 Status F.Fail 1 - Xa1 F.Fail 1 Xab1 F.Fail Time Delay F.Fail Do Timer F.Fail 2 Status : : : : : : : : : Enabled 15.00 deg 5.00 s Enabled 7.00 ohms 143.0 ohms 5.000 s 8.000 s Disabled