Report Load Flow Existing Case 2012
1. Low Case:
January-2012
Load
Gen
(MW) (MW)
Norm
al
N-1
VTCNK
(MW)
Total
Imp/E
xp
Remark
(MW)
- Normal Case: Kengkok 115kV Bus
Peak time_(19:00
- 22:00h)
520.7 392.5
-26.3
Voltage drop(108.8kV)
- Voltage Collapse at 115kV (PBI)
140.8 when T/L NN1 NLE Trip out
- Voltage Collapse at (SPO) when
T/L 1cct, MHA SPO Trip out
Day time_(8:00 18:00h)
451.0 367.1
0.5
-94.5 - Voltage collapse at 115kV (PBI,
NAHO, PSA & XNE) when T/L NLE
TKU Trip out.
Light time_(23:00
- 7:00h)
314.8 251.7
14.7
- Voltage collapse at 115kV (PBI,
-69.7 NAHO, PSA) when T/L NLE TKU
Trip out.
2. Medium Case:
April-2012
Peak time_(19:00
Load
Gen
(MW) (MW)
621.1 277.3
Norm
al
N-1
VTCNK
(MW)
X
Total
Imp/E
xp
Remark
(MW)
-
- Voltage collapse at 115kV (PBI,
167.3 353.6
- 22:00h)
Day time_(8:00 18:00h)
Light time_(23:00
- 7:00h)
550.9 271.1
415.0 191.5
23.6
-95.5
286.7
229.0
NAHO, PSA & XNE) when T/L NLE
TKU Trip out.
- Voltage collapse at 115kV
(PBI,NAHO,PSA & XNE) when T/L
NLE TKU Trip out.
- Voltage collapse at 115kV (PBI,
NAHO, PSA) when T/L NLE TKU
Trip out.
3. High Case:
October-2012
Load
Gen
(MW) (MW)
Norm
al
N-1
VTCNK
(MW)
Total
Imp/E
Remark
xp
(MW)
- Normal Case: Kengkok 115kV Bus
Voltage drop(109.2kV)
Peak time_(19:00
- 22:00h)
654.7 370.8
- Voltage collapse at 115kV (PBO,
KKO) when T/L 1cct,
TKE PBO
139.9 259.2 Trip out.
- Voltage collapse at 115kV (SPO)
when T/L 1cct, MHA SPO Trip
out.
Day time_(8:00 -
580.0 345.3
- Voltage collapse at 115kV (PBI,
121.1 243.3
18:00h)
Light time_(23:00
- 7:00h)
Remark:
428.9 284.2
O - 115 kV Bus Voltage Drop
X - System not Stable
- System Stable
-40.9
NAHO, PSA & XNE) when T/L NLE
TKU Trip out.
- Voltage Drop at 115kV (PBI) when
151.5 T/L NLE TKU Trip out.