0% found this document useful (0 votes)
178 views2 pages

LT Capacitor Sizing Calculation Guide

This document discusses the calculation of capacitor sizing for power factor correction. It provides the power factor requirements and load details, including a 0.87 power factor motor and >0.99 lighting load. Formulas from IEEE and CBIP are used to calculate the reactive power compensation needed for the transformer (5.5 KVAR) and two 50HP motors (36.64 KVAR), giving a total reactive power addition required of 42.14 KVAR. With a margin, the capacitor is sized at 50 KVAR.

Uploaded by

Manish Pareek
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
178 views2 pages

LT Capacitor Sizing Calculation Guide

This document discusses the calculation of capacitor sizing for power factor correction. It provides the power factor requirements and load details, including a 0.87 power factor motor and >0.99 lighting load. Formulas from IEEE and CBIP are used to calculate the reactive power compensation needed for the transformer (5.5 KVAR) and two 50HP motors (36.64 KVAR), giving a total reactive power addition required of 42.14 KVAR. With a margin, the capacitor is sized at 50 KVAR.

Uploaded by

Manish Pareek
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 2

LT Capacitor Sizing calculation

Power Factor requirement as per TD : 0.99 Lag Power factor Loads connected to the System. 1. Motor : 0.87 2. External & internal lighting load : > 0.99 Manufacture Data sheet for Motor NB 503 As Electronic ballast will be used .

So Along with the transformer , Motor Power factor also corrected to 0.99. Transformer Power factor correction : As per IEEE , The following formula is to be used for PFC . Qc trf = ( ( I0 *S )2 Pfe2 ) + K2 ( ( ( Z*S )2 Pw2 )) .(1) Where , Qc trf Var comepensation in KVAR I0 No load current of the transformer as factor of total current (1.5 % 0.015 as per attached transformer vendor datasheet S - Transformer capacity in KVA i.e. 200 KVA Pfe - Iron losses of the transformer in KW i.e. 0.53 KW .as per CBIP K : Load factor of transformer i.e. ( Total load : 186 as per Transformer sizing document so 186/200 = 0.93 ) Z - % impedance of transformer i..e. 4.5 % ..vendor datasheet Pw winding ohmic losses of transformer in KW i.e. 2.170 KW . as per transformer vendor datasheet ( ohmic losses = losses @ 100 % loading iron losses ) Putting above values in (1) So Qc trf = 5.5 KVAR

Power factor correction of the Motor : As per IEEE 60831-1 , the Var compensation Qcm for the 3 phase motor is given by the following formula Qcm = K*Pn/ --------------------------------------------------------------------------------------------------(2) Where , Qcm is the Var compensation required for PFC in KVAR K Power factor correction factor and calculated by following equation . ( = ( ) ( ) ( ) = 0.42 )

Pn is the Motor Load in KW i.e. 37 .3 KW is the Motor Full load efficiency i.e. 85.5 % or 0.855 Putting all values in ( 2) Qcm = 0.42 * ( 37.3/0.855 ) = 18.32 KVAR So reactive power required for two working 50 HP motors is Qcm (net) = 2*Qcm = 36.64 KVAR So Total Reactive power addition required /Amount of KVAR required = Qcm net + Qc trafo QC= Qcm(net) +Qctrf = 36.64 +5.5 = 42.14 KVAR Taken Margin , Sizing of KVAR = 50 KVAR

You might also like