CODES AND STANDARDS The following are some of the important codes and standards which describe the
earthing requirements and methods: Indian Electricity Rules National Electrical Code (India) IS:3043 (Code of Practice for Earthing) API RP 14F (Design and Installation of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities) IEEE Std. 142 (Recommended Practice for Grounding of Industrial and Commercial Power Systems)
Earthing
Size conductors for anticipated faults Select the right connector Pay attention to ground rod length, number, placement, and spacing Select/Prepare the soil with low conductivity Limiting step and touch potential to safe values for employee safety.
Checks and Measurements: 1)Check earth electrode and earth mat terminations for loose connection, contact, pitting and flash marks. 2)Inspect all terminations for salt formation and clean. 3)Ensure moisture level is maintained in earth pit. 4)Inspect the earth pit brick / concrete lining a n d p i t c o v e r f o r g o o d condition. 5)Ensure all pits have unique identification. 6)Measure earth resistance value of earth electrode / earth mat. 7)Maintain a register and record values and observations. 8)Apply thin layer of petroleum jelly at earth / electrode terminations. 9)If any reading is more than 4 ohms, inform supervisor and arrange f o r reconditioning the pits as per procedure. 10)List out and arrange for cement works and identification as required. 11)Ensure all the pit covers are in position.
12) Cancel the permit.