Power Transformers
Power Transformers
1 Definition:
Transformers :transfer electrical energy at system voltage to electrical
energy at the required voltage or higher voltage.
∑e.m.f = ∑V.D
From the secondary circuit e2 = v2
e1 N1 V1
K = = =
e 2 circuitN: 2
Equivalent V2
Io = 10 : 15 % of rated current .
1 = − E 1 + I1r1 + JI1X1
V 1
Determination of parameters :
Connect the primary to a source of alternating current at nomial voltage the
secondary is open circuit – read the magnitude of ( Io , V1 , Po ) at no load .
The impeadence of the circuit at no load .
V1
= Z 1 +Z 0
Io
Z1 < < Zo
V1
Z0 ≅
Io
Z1 < < Zo
Z1 can be neglected
po
ro =
( Io ) 2
Zo = r 2 o + X o
2
2
= Zo − ro
2
Xo
-Another method:
Po = V1 Io is go
V1
Zo ≅
I0
Po Po
cos φo ≅ φo = cos-1
V1 Io V1 Io
Ro = Zo cos φo
For parallel circuit rm & JXm :
Neglect Zm relation to Z1
x o = Zo sin φo
I o a = I o cos φo
Io r = Io sin φo
Po
φo =cos -1
V
1
V V1
rm 2 = 1
Xm =
Ioa Ior
-Short circuit test:
Connect the primary to a reduced voltage ( from 15 – 20 % of V1 ) until the
primary current becomes near to the value of the full load current of the
primary .
Short circuit the secondary winding .
Measure ; ( V1 ) sh.c ( I1 ) sh.c ( P1 ) sh.c
x eq 1
+ x+′ 2r2′
Req= =x r1
P1 (sh.c ) = ( V1 )sh.c ( I1 )sh.c ( cos φ ) sh.c
-1 P1
φsh.c =cos
P1
sh .c
V1I1
xeq = Zeq sin φ
Req = Zeq cos φ
r1 ≅ r′2
Xeq
X1 ≅ X′2
2
r2′ x′2
r2 = 2
x2 = 2
K k
•D.C Test :
Connect the primary coil with a direct current supply . measure
the applied voltage and the current .
E
= r1 ohms
I
The effect of X1 , X0 will not appear when using direct current
Ldi
X → dt
I is the const. relative to time[ also the effect of ro will not appear
because it represent the eddy and hysteresis losses which are not existing
in the case of direct current they appear only when there is varialable flux
in the core .
Similarly we can determine the resistance of the secondary ( r2 ) by
connecting the battery to the terminals of the secondary coil .
Voltage regulation :
(V2 )L
ε V.R = × 100 = %
(V2 )n.L - V2 L
=
(V2 )L = per unit
ε
V.R
ε = ( V )n.l − (V )l
2 2
(V2 )l
ε = (K V )n.l − (KV )l
2 2
(KV2 )l
′ ′ ′
ε = ( V )n.l − (V )l = V − V
2 2 1 2
(V2′ )l V2′
where V′ 2 is calculated by eq ( 1 )
V 1 = ( V′ cosφ
2 2 ) (
− I′2Req + V′2 sinφ 2 - I′2 Xeq
2
)
Where ;
I2
I′2 =
K
r′ 2 = k2 r2 , x′ 2 = k2 x2
E′ 2 = kE2
N1 E1 V1 I 2
k= = ≅ ≅
N 2 E1 V2 I1
Transformer efficiency (η ) :
Poutput Pin - losses
η= =
Pinput Pin
∴ Pcu ∝ I2 pcu = I ( r1 + r2 ) = I1 req = I 2 req
2
1
′ ′ 2
This means that if the cu losses are known at a certain load ( current ) ,
then the copper losses can be determined at another load .
( Pcu )a = ( I )a
2
( Pcu )b ( I )b
2
I1 : nominal value ( full load value ) usually the copper losses are
determined from a short circuit test at a current equal to the full load or
nominal value , accordingly the equation can be written as :
Pcu = ( I ) 2
( Pcu) f .l ( I) f .l 2
2
( pcu ) required = ( pcu ) f .l I
If.l
I
let =X
If.l
Pcu required = X 2 ( Pcu ) f.l
η=
Pout
=
( K.V.A) out cosφ
Pout + const.loss + cu loss ( K.V.A) out cosφ + Po + P
cu
E.X :
100 K.V.A lighting transformer has a full load loss of 3 K.V.A , the
losses being equally devided between iron and copper . During a day the
transformer operates , on full load for 3 hours , one half for 4 hours , the
output being negligible for the reminder of the day calculate the all day
efficiency .
Solution :
It should be noted that lighting transformers are taken to have a load p.f
of unity iron losses for 24 hours = 1.5 x 24 = 36 K.W.h ( const. losses )
FL.cu losses = 1.5 K.W
Cu loss for 3 hours on F.L = 1.5 x 3 = 4.5 k.w.h
Cu loss for half F.L = 1.5 /4 k.w.h
Cu loss for 4 hours at half the load = ( 1.5 / 4 ) x 4 = 1.5 k.w.h
Total losses = 36 + 4.5 + 1.5 = 42 k.w.h
Total output = ( 100 x3 ) + ( 50 x 4 ) = 500 k.w.h
η all day = 500 x 100 / 542 = 92.26 %
Group numbers :
The group number indicates the phase differience between primary and
secondary ( H.T and L.T ) line voltages in electrical degrees . It is
sometimes determined as a clock reading each hour is equivalent to
30° phase difference .
Y-Y connectios :
(∆ Y)
Parallel operation :
Normal rated power in KVA as follows . ( 25- 50- 100 – 160 – 250 – 400 –
500- 630 – 800 – 1000 – 1250 – 1600 – 2000 – 2500 – K.V.A -………. )
2.2 Formation of distribution مكونات محولت التوزيع
transformers :
•2.2.1 Iron core: : * القلب الحديدى
Made of cold rolled silicon steel sheets 0.3mm يصنع القلب الحديدى من رقائق الصلب السيليكونى المسحوب
to minimize losses مم لتقليل الفقد فى الفيض المغناطيسى0.3 على البارد بسمك
transformers are filled with special oil تملم المحولت بزيمت محولت ذو درجة عزل عالية
( Diala ( 5 ) or equal ) of high insulating IEC )ديالة ب أو ما يماثلها ( طبقا لمواصفات
grade according to IEC specifications
2.2.7 – Main accessories of distribution : الملحقات الساسية لمحولت التوزيع
transformers :
Oil expansion reservoir . خزان تمدد الزيت
Thermometer pocket جراب الترمومتر
Oil drain cock صمام تصريف الزيت أو أخذ عينات منه
Oil level indicator مبين مستوى الزيت
Lifting chackles حلقات لرفع المحول
Four two – directional adjustable wheels أربع عجلت
Earth screw مسمار توصيل الرضى
Name plate لوحة البيان
Determine wheather the ransformer will يجب تحديد ما إذا كانت المحولت المطلوبه تعمل
work in parallel or individual In case of منفرده أوعلسى التوازى مع بعضها أو مع محولت
parallel work with old transformers, the أخرى موجودة وفى هذه الحاله يجب بيان المعاوقه
voltages and impeadance of them must be . الكليه للمحولت الموجودة
mentioned .
3.2 Selection: كيفية تحديد مواصفات المحولت
3.2.1 Rated values :
The rated power is found first by determining the peak effective power
demand designed or measured , usually a margin is added to provide
for the regular increase in power demand .
( ) تتحد القدرة السمية عن طريق التصميم أو القياس لقصى قدرة فعاله مطلوبة مع إضافة نسبة
. من القدرة لحتمالت الزيادة المستقبلية العادية فى الطاقة الكهربائية المطلوبة
When calculate the rated power (PN) we must take in consideration the
anticipated power factor (COS )
. ويجب عند حساب هذة القدرة السمية مراعاة قيمة معامل القدرة المتوقع
3.2.3 The impendence voltage(UK) :
the rated impeadance voltage (UKN) is the value of the impedance voltage
on the principal tap when related to the rated voltage (UN) it is called UKN
and given in percent
UkN = UkN
X 100%
UN
Where ;
UKN = rated impeadence voltage % .
UKN = rated impeadence voltage in V.
U.N = reated voltage in V.
3.2.5 Selection of rated impeadence voltage :
In distribution system a rated impeadence voltage UKN= 4 % is preferred in order to keep
the voltage drop small .
For larger industrial systems with greater power demand transformers with a rated
impeadence voltage of 6 % are used in order to limit the short – circuit stresses on the
switch gear of the plant .
3.2.6 Transformers loss PK:
For transformers losses include no-load losses Po and load losses ( Pk ) the no load losses
resulting from the continious magnetic flux reversal in the iron are practically constant
voltage impeadence of load .
The load losses ( copper losses ) constant of resistive losses in the windings and losses due
to stray fields , the load losses vary with the square of the load . the total losses of a
transformer are :-
PV = PO + a 2 Pk
Pv = total losses in watt ..
Po = no-load in watt.
part load pa in K.V.A
a = load factor ( )
rated power P in K.V.A
PK = load losses in W
3.2.7 η - Efficiency :
the efficiency η of a distribution transformer can be calculated
with reasonable accuracy from the following ; N
where ;
η = efficiency in % .
PN = rated power in K.V.A .
Po = no-load losses in K.W ,
Pk = load losses in K.W .
Cos φ = power factor .
a = load factor .
Po + a 2 Pk
η = 100 % - × 100 %
a PN Watt cos φ + Po
* Example :-
calculate efficiency (η ) of a transformer at full load given the
following information :
PN = 500 K.V.A., Po = 1.1 K.W , Pk = 5.5 K.W ,
Cos = 0.8 , a = 1.0
Po + a 2 PK
η = 100 % - × 100 %
a PN cos φ + Po
1.1 K.W + (1)2 × 5.5 K.w
η = 100 % - × 100 %
1 × 500 K.V × 0.8 + 1.1 K.W
η = 98.36 %
3.2.8 Maximum efficiency:
the load factor ( a ) for the maximum efficiency of a transformer is defined as
follows ;
Po
a=
Pk
For the transformer in the above example this becomes ;
1.1 (k.w)
a= = 0.447
5.5(k.w)
Therefore maximum efficiency occurs with a load of ;
Pa = PN.a
Pa = 500 K.V.A × 0.447 = 224 K.V.A
And for this load the efficiency is ;
1.1 K.W + ( 0.447 ) × 5.5 K.w
2
η = 100 % - × 100 %
0.447 × 500 KVA × 0.8 + 1.1 K.W
η = 98.36 %
η = 98.78 % .
3.2.9 Insulation class :
the insulation rating of a transformer is designed by numerals indicating the
insulation voltage class in K.V & a letter N indicating that the transformer is
designed for use no a system where a neutral is not solidly earthed .
the insulation class corresponds to the values given in table no (1)*
Table no (1)*
3.2.10 Maximum continuous operating voltage ( U.b) :
transformers must be selected with an insulation class such that the voltage on which
they are continuously used does not exceed the allocated operating voltage ( Ub ) .
Rated voltages (UN):
the clock hour number indicate the multiple of 30° with which the vector of the low
voltage side is lagging when moving anti-clock wise in comparison to the high
voltage side of the corresponding terminal this angle between the voltage vectors can
have values between 0° & 360° .
the terminals 2U,2V& 2W on the low voltage side are related to the terminals
1U,1V,1W on the high voltage side , the mark up U , V, W corresponding to DIN
standard .
Obtaining the clock hour number:
the clock hour number can be obtained by first drawing the vector diagrams of the
connections of the windings up one on top of the other and both on top of a clock face
in such a way that the marking 1V of the high voltage side coincides with number 12
corresponding to 0 .
the position 2V of the connection diagram of the low voltage side on the clock face
gives the clock hour number of the vector group .
Example: (fig 2).
* C – Y/S:
High voltage side : C connection .
Low voltage side : y connection
the length & width of a transformer station with service access should be
dimensioned such that for transformers with rated power of up to 630 KVA
the inspection passage wais are at least 70 cm wide , for transformers of
800-1600K.V.A. the passage- ways should be at least 75 cm wide
the floor of the transformer station can be made from either a reinforced
concrete slab with an opening in the centre or from girders of reinforced
concrete slab construction is used . the cement grouting should have an
inclination of 1-2° in the direction of the collecting pit as shown in fig.(4) *
fig no ( 4 )
example for the indoor
installation of a transformer
4.6 Rails for transportation rollers :
the international specifications states the recommendations for steel
I section girders for supporting transformers the transportation
rollers rest on these girders which also incorporate a guide strip 2
cm high fig. (5) *
Fig no (5)
Typical arrangement of girder
And guide strip for
transportation rollers
4.7 For oil immersed transformers:
Collecting tank and pits cooling and insulating fluid :
For transformers with a rated power of 630 – K.V.A a collecting tank below the
transformer can be used providing it has capacity sufficient to hold the total fluid of
the transformer floor can also be used as collecting tank when the door step &
ventilation openings are correspondingly high
Collecting pit :
For transformers with rated power of 800 – 1600 K.VA, the collecting pit provided
must have a capacity of approxi 2 m³ ( oil content of transformers ) .
With a number of transformers each with rated capacity of between 800 – 1600
K.VA. a common collecting pit can be used providing this has a capacity at least 2
m³ . this pit can be situated out side the transformers , it is permitted to construct a
number of small inter connected pits providing the total capacity of these pits exceed
2 m³ . a sum pit should be provided in the bottom of each pit to facilitate the pumping
out of small amounts of water or oil .
Gravel, granite chipping layer :
Collecting pits & the oil carrying ducts for a common collecting pit must be screened
above by a layer of gravel or granite chipping at least 20 cm , thick laid on a
galvanized iron grating to minimize the spread of fire fig no (5) *
Outdoor collecting pit :
A collecting pit must also be provided if transformers are installed
outdoor in order to prevent seepage of cooling &insulating fluid into
the ground . the out door collecting pit must have a capacity of at
least 1.2 times the fluid content of the transformer to allow for part
filling of rain water or melted or melted snow , the pit must be
pumped out regularly , other wise it would became filled with
rainwater .
4.8 Ventilation of transformer rooms :
3. oil level for safe operation –3التأكد من أن مستوى الزيت فى المحول بالقدر الكافى
للتشغيمل بحيمث ل يقمل عمن أدنمى مسمتوى ممبين على
خزان التمدد واذا احتاج المر فيمكن تزويد الزيت عن
طريمق الفتحة العليما بخزان التمدد وبنفمس نوع الزيت
الصلى أو المعادل له
- 4فى حالمة عدم اسمتعمال المحول لمدة طويلمة وكذلك 4. in case that the transformer is not used
بعد مرور عام على التشغيل يجب اعادة اختبار قوة for long time the dielectric strength of
oil is to be checked & after a year of عزل الزيت ويجب أل تقل عن 20ك.ف2.5/مم.
operation it must be not less than 20
K.V/2.5 mm
5. to ensure safety of operation apparatus like ، التأكمد ممن سملمة أجهزة الوقايمة مثمل البوخهلز- 5
bucholz relay , thermometer , silica gel and الترمومتر والسيلكاجل ومسمار الرضى
earthing screw
6. to be sure that the silica – gel is blue التأكمد ممن لون الملمح السميلكاجل الزرق حتمى يمكنه-6
( i,e) able to remove humidity , if it became امتصمماص الرطوبمة فإذا تحول الممى اللون الحمر
red it must be dried 140° till it is blue again الوردى فإنمه يجمب إعادة تجفيمف الملمح بتعريضه
or must be changed . حتى يستعيد لونهºم140 لدرجة حرارة ل تزيد عن
الزرق أو بتغيير الملح
7. terminals of warning and switching off in the يجب توصيل نقطتى النذار ونقطتى الفصل فى- 7
Buchholz relay must be connected to the روزتة جهاز البوخهلز بأجهزة النذار والفصل بمفاتيح
warning circuit and to the protection circuits العميل حيث تعمل صفارة النذار اذا تراكمت الغازات
of the customer Here is a guide connection حول العوامة العليا بجهاز البوخهلز وحيث يفصل جهاز
diagram (fig.No.13) In case of small faults الوقاية مفتاح تغذية المحول بالكهرباء فى حالة حدوث
the gasses gathered around the upper fault قصر فى الدائرة واندفاع الغازات من المحول الى العوامة
which closed , the warning circuit and the . السفلية فى جهاز البوخهلز
warning voice is heared , in case of big وتعمل دائرتا النذار والفصل على تيار تشغيل
faults a big amount of gasses move the 220 الى24 أجهزة الوقاية عند العميل على جهد من
lower float which shuts the tripping circuit .فولت تيار مستمر أو متردد
and the current is switched off the trafo – ( يوضح توصيل جهاز البوخهلز13) شكل رقم
warning and switching circuits work on the بأجهزة النذار والفصل
customer protection current on voltages
between 24 & 220 Volts A.C or D.C .
8. To be sure that the tape changer is in the التأكد من تثبيت منظم الجهد فى الوضع المراد تشغيل- 8
required position . . المحول عليه
9. In case of indoor installation of Trafo, the فى حالمة تركيمب المحول داخمل المبانمى فيراعمى أن- 9
dimensions of the Trafo room must be تكون أبعاد الغرفمة مناسمبة لحجمم المحول كمما يحسن
suitable to the Trafo , size and aeration , air عمل فتحات تهوية فى اتجاهين متضادين ويحسن أن
ducts must be made in opposite تغطى فتحات التهوية بشبكة معدنية
directions .Covering the air ducts with a
metallic net is recommended
شكل رقم ) (7يوضح توصيل جهاز البوخهلز بأجهزة النذار والفصل
5.2Transformer tests: الختبارات
routine tests are carried out according تجرى علقى المحولت الختبارات الروتينيقة طبققا لمواصفات
to IEC standards : IECوتشمل :
5.2.1 upon request following حسب طلب العميل يمكن إجراء الختبارات التالية
tests can be made :
loading and heat test اختبار التحميل ودرجة الحرارة
resistance of insulation to impulse اختبار تحمل العزل للصدمات الكهربائية
test قياس مستوى الضوضاء
noise lvel
6.1 Arrangement of distribution transformers
The distribution transformers can be arranged centrally in one station or
in a number of sub – stations distributed over the whole load area .
As a rule they should be placed at the centers of load thus the length of
cables cross section of conductors and losses are kept within economic
limits .
The centrally arranged system used for distribution systems where only
small extension of the area is likely and load intensity is high .
the load equalization occurs mainly on the low tension side on the bus
bars see fig (8)* in calculating the rated power of distribution
transformer .
Fig no (8)
Centrally Arranged distribution
Transformers in a sub-station
6.2 Some requirements for operation :-
The peak load of the whole distribution system taking into account a
reserve in the event of one transformer being out of order the
transformers should if possible be equal in size to facilitate operation
in parallel and interchangeability.
The decent tralized arrangement of distribution transformers is of ten
favored for wide supply area and for widely distributed centers of
load neighborly substation can then be connected by ri ng main on
the low voltage side in this way load equalization between the sub
station Can be achieved and the supply can be maintained when
one of the transformers on the high voltage side of substation is out
of order.
if necessary several transformers may be required as reserve , as
shown in fig ( 9 ) and fig ( 10 ) and fig (11 ) .
Fig no (9)
Decentralized arrangement of distribution
Transformers in several sub-stations
Fig no (10)
Ring-main system with ring
Circuit looped between sub-
stations
Fig no (11)
diagram of ring-main
system.
a) Ring –main system
with two ring circuits
b) Ring-main system with
terminal station
6.3 Peculiarities of high voltage ring system:
this simple way to loop ring circuits into substations is via load break isolators
the ring circuit can be opened at convenient points to confine a fault to a part
of the circuit only ( e.g in substation b3 ) fig (12)*
By means of short circuit indicators in each sub-station affected can be
determined thus the faulty section of the circuit can be readily found and
isolated.
After isolating the faulty cable run at (d) ( worst fault condition ) & closing the
isolating point in substation b3 , normal service can be resumed under the
worst fault condition , with the fault in cable run ( d ) between the ring supply
and the first substation the remaining cable has to supply current to the whole
ring circuit and must therefore be rated for single supply if there is a load
center with high load demand opposite the transfer station ( e.g a university ,
hospital in a rural area ) , it will found advantageous to provides a ring main
system with a terminal substation at the load center . this would ensure good
load equalization and high security of supply to, all sub station yet the number
of ring circuits will be less fig. (11)
6.4 Parallel operation:
transformers will operate in parallel when they are connected to the same network
system, both on the high voltage as well as on the low voltage side .
slight different conditions apply between operation in parallel bus bars and operation
in parallel on systems networks .
6.5 general requirements for parallel operation :
for satisfactory operation in parallel , especially on bus bars the following general
requirements apply ;
For transformers having the same vector group and clock hour number, terminals
having identical designations are paralleled .
The ratio of transformation must be identical .
All taping must have identical values on each transformer .
The rated impeadence voltage must be practically the same within 10 % , the
transformer with the smaller rated power should have the higher rated
impeadence voltage , if possible the ratio of the rated power of transformers
working in parallel should not be more than3:1 .
for checking the phase relationship the 2N-terminal of the transformer to be
connected to the transformer to be connected is connected to the 1N bus bar of the
system the phase relation is then check by using a voltmeter if the connection is
correct the voltmeter will indicate zero , if the connection is correct the voltmeter
will indicate values values of up to twice the phase voltage fig (13) * .
Fig no ( 13 )
6.6 Protection by fuses ( short circuit protection ) :
Distribution transformers are normally protected against short circuits by high
voltage H.R.C- fuses ( table No 5 ) can be used for the selection of fuses for
distribution transformers ; the maximum current inrush when switching on the
transformer has been taken into consideration .
Table no (5)
Guiding values for the rating Of high-voltage HRC-fuses
6.7 Over load protection:
the over load protection of transformers is provided on the low voltage side
. the low voltage H.R.C- fuses or the thermally delayed over current trips
of the circuit breakers are selected according to the rated current IN of the
transformer . this selection normally provides adequate selectivity between
high – voltage and low voltage side .
6.8 Short circuit strength:
Distribution transformers need to be designed to with stand the effects of
external short circuits with out damage .
Steady state R.M.S short circuit current I.K :
The short circuit current Ik of a transformer is the steady state R.M.S.
value of current at the terminals following on all phases short circuit on the
terminals of the outgoing side and when the D.C component has decayed
with constant rated voltage applied to the input terminals .
Calculation of steady state R.M.S short circuit current :
For transformer operating at rated voltage & rated frequency and tappings
adjusted to the principal tap , the continuous short circuit current Ik can be
calculated from the rated current IN & the rated impeadence voltage UKN .
the type of fluid used is stated on the rating plate .the maintenance of this
type of transformer includes :
Checking the level of fluid at the sight glass .
Checking effectiveness of gaskets and quality of paint finish .
Testing the insulating fluid of moisture content and checking or
reactivating the silica – gel in the breather .
To check the moisture content of the insulating fluid a sample must be taken
to ensure that the measurement corresponds to the actual conditions of the
fluid within the transformer , special care the highest degree of clean lines
is required when taking samples .
1. A specimen bottle with large opening and glass stopper ( not cork ) is
required
2. The bottle must be cleaned with clean alcohol and well dried .
3. The drain cook must be carefully cleaned and dried before taking a test
sample .
4. The specimen bottle should be approximately half filled with the fluid
and rinsed with this fluid before a test sample is taken ..
7.4 break down voltage :
Eleven samples should be taken and a break down voltage test made with
electrodes having a 2 – 5 mm gap for each sample the break down
voltage test is repeated six times with a 2 minute interval between each .
the break down voltage is the mean value of the results of tests 2 to 6 .
the transformers of insulation rating up to 30 k.v. the mean value
acceptable is for new oil or a skarel 60 k.v. minimum and for used oil 30
k. v. minimum .
if the measured values fall below the above mentioned minimum values
the insulating fluid must be changed or re conditional by use of special
filter presses or for small trans formers the complete transformer can be
dried under vacuum the manufacturers of transformers and the electricity
boards have the necessary plant and devices for the conditioning and
drying of the insulating fluid .
for refilling is necessary the fluid used must be identical to the original it
is recommended to test the new fluid for break down voltage before
refilling