0% found this document useful (0 votes)
315 views1 page

Electrical Load for Chlorination

This document contains an electrical load list for a chlorination plant, listing 14 drive systems along with their duty, power ratings, voltages, speeds, and control details. The drives provide power for systems like dosing pumps, blowers, strainers, pumps, chillers, and cooling towers. Most are continuous duty and rated between 0.37KW to 18KW, operating at 415V or 230V, with speeds ranging from 750 to 2900 RPM. Control is done through local control panels without motor circuit breakers or variable speed drives.

Uploaded by

Supriya Jadhav
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
315 views1 page

Electrical Load for Chlorination

This document contains an electrical load list for a chlorination plant, listing 14 drive systems along with their duty, power ratings, voltages, speeds, and control details. The drives provide power for systems like dosing pumps, blowers, strainers, pumps, chillers, and cooling towers. Most are continuous duty and rated between 0.37KW to 18KW, operating at 415V or 230V, with speeds ranging from 750 to 2900 RPM. Control is done through local control panels without motor circuit breakers or variable speed drives.

Uploaded by

Supriya Jadhav
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 1

Electrical Load List

ELECTRICAL
Duty
Rating(for each
drive)
Shaft Power Voltage Speed
KW KW V nom RPM Primary Secondary Status POS Ind. Ammeter
1 Tranformer - Rectifier
Indoor (Chlorination
Plant)
3 1 Continous 380 350 415V, 3, 50Hz. NA None DOL / ACB No
Control
Panel
None ON / TRIP NA No MCC
2 Dosing Pump - CW
Outdoor (Chlorination
Plant)
2 1 Shock 3.7 2.4 415V, 3, 50Hz. 2900 None DOL No
Control
Panel
None ON / TRIP NA No MCC
3 Dosing Pump - PT Plant
Outdoor (Chlorination
Plant)
1 1 Continous 0.74 0.38 415V, 3, 50Hz. 2900 None DOL No
Control
Panel
None ON / TRIP NA No MCC
4 Dosing Pump - Potable water- Plant
Outdoor (Chlorination
Plant)
1 1 Continous 0.37 0.015 415V, 3, 50Hz. 2900 None DOL No
Control
Panel
None ON / TRIP NA No MCC
5 Dosing Pump - Potable water- Colony
Outdoor (Chlorination
Plant)
1 1 Continous 0.37 0.015 230V, 1, 50Hz. 1440 None DOL No
Control
Panel
None ON / TRIP NA No MCC
6 Blower
Outdoor (Chlorination
Plant)
1 1 Continous 5.5 4.2 415V, 3, 50Hz. 2900 None DOL No
Control
Panel
None ON / TRIP NA No MCC
7 Self cleaning strainers
Outdoor (Chlorination
Plant)
1 1 Continous 3.7 ------- 415V, 3, 50Hz. 1500 None DOL No
Control
Panel
None ON / TRIP NA No MCC
8 Feed Water Pump Outdoor (S) 1 1 Continous 11 9.11 415V, 3, 50Hz. 2900 None DOL No
Control
Panel
None ON / TRIP NA No MCC
9 Chiller Water Pump
Indoor - For chilled
water circulation
4 1 Continous 3.7 2.6 415V, 3, 50Hz. 2900 None DOL No
Control
Panel
None NA NA No MCC
10 Brine Pump
Outdoor (Chlorination
Plant)
1 1 Continous 5.5 2.78 415V, 3, 50Hz. 2900 None DOL No
Control
Panel
None ON / TRIP NA No MCC
11 Acid recirc. Pump
Outdoor (Chlorination
Plant)
1 1 Continous 2.2 1.34 415V, 3, 50Hz. 2900 None DOL No
Control
Panel
None NA NA No MCC
12 Chiller Compressor
Indoor (Chlorination
Plant)
4 1 Continous 18 16 415V, 3, 50Hz. NA None DOL No
Control
Panel
None ON / TRIP NA No MCC
13 Circulating water pump
Outdoor (Chlorination
Plant)
1 1 Continous 11 9.65 415V, 3, 50Hz. 1500 None DOL No
Control
Panel
None ON / TRIP NA No MCC
14 Sump-Pump
Outdoor (Chlorination
Plant)
1 1
Intermittent
(3 to 4 hrs)
0.37 0.2 415V, 3, 50Hz. 1500 None DOL No
Control
Panel
None ON / TRIP NA No MCC
15 Local control Panel
Indoor (Chlorination
Plant)
1 1 Continous 5 ------ 240V, 1, 50Hz. NA None MCB No NA None NA NA No UPS power supply
16 Cooling Tower Fan
Outdoor (Chlorination
Plant)
1 0 Continous 5.5 ------ 415V, 3, 50Hz. 750 None DOL No
Control
Panel
None NA NA No MCC
No. of feeders 25 15
No. of feeders
S.P.Pal SJ JK
PREPARED CHECKED APPVD
Tel Fax 0 21.10.2013 Rev.
+91 22 40910000 +91 22 40910010 Rev. No. Date 4
Contact
Work ELECTRO-CHLORINATION SYSTEM
Grand Total 40
RAJASTHAN RAJYA VIDYUT UTPADAN NIGAMLTD. Client
Project
Contractor LARSEN & TOUBRO LIMITED
System
SystemSupplier
CAPITAL CONTROLS INDIA
PVT. LTD.
Remarks
REMARKS
TITLE
Electrical Load List
Doc. No.
Total
Consultant L&T S&L LIMITED 15 A/J, Laxmi Estate, Andheri,
Mumbai - 400 053
Preliminary Submission
www.capitalcontro
lsindia.com
Auto
Selection
Mode of
Control
MECHANICAL
Client's
Ref. Dwg.
2 660 MWCHHABRA SUPERCRITICAL TPS,
4 x 60 Kg/h Electro chlorination System
S. No.
Power Source Working Standby
Location Description
Quantity
Control Location Indication on field panel
OPERATION / MCC INTERLOCKING
Sheet 1 of 1 7/17/2014