The document specifies the requirements for medium voltage switchgear including: - Ratings of 5-15kV, 95kV BIL, 600-1200A, 31.5kA arc ratings, and fully front accessible metal clad construction. - Draw out breakers, current transformers, and potential transformers. - Factory testing per UL, ANSI, and CSA standards including design tests, high potential tests, control and secondary wiring checks, and mechanical operation checks to ensure no defects.

Uploaded by

abhijit_wce
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
37 views1 page

Vesta Specification 1

The document specifies the requirements for medium voltage switchgear including: - Ratings of 5-15kV, 95kV BIL, 600-1200A, 31.5kA arc ratings, and fully front accessible metal clad construction. - Draw out breakers, current transformers, and potential transformers. - Factory testing per UL, ANSI, and CSA standards including design tests, high potential tests, control and secondary wiring checks, and mechanical operation checks to ensure no defects.

Uploaded by

abhijit_wce
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Medium Voltage Switchgear Specification

MEDIUM VOLTAGE METAL CLAD SWITCHGEAR


PART 1 - GENERAL
1.1 DESCRIPTION
This section specifies the furnishing, installation, connection and testing of the medium
voltage switchgear.

1.2 SWITCHGEAR FEATURES AND RATINGS


The design standard for the equipment specified herein is VESTA switchgear as
manufactured by Industrial Electric Mfg, Fremont, California. Other equipment meeting all
requirements specified may be acceptable.
1.2.1 The switchgear shall have the following features and ratings
Physical Size: each section: 24 wide x 60 Deep x 96 high
Fully Front Accessible, Metal clad switchgear
Ratings: 5 kV 15 kV, 95 kV BIL, 600A 1200A, 31.5 kA
Arc Ratings: 15 kV, 25 kA, type 2A
Draw out Breaker, CPT and PT
IR windows and Viewing windows in front and back
Breaker: UL listed Magnetically Actuated ABB VM1 or equivalent
The equipment supplied shall be the tested and UL and cUL / CSA listed product of a
manufacturer of electrical power equipment with a minimum of five years experience in the
production of the type of equipment herein specified.

1.3 FACTORY TESTS


A. Medium voltage switchgear shall be thoroughly tested at the factory to assure that there
are no electrical or mechanical defects. Tests shall be conducted as per UL, ANSI and
CSA Standards.
B. Thoroughly test the switchgear at the factory with the circuit breakers in the connected
position in their cubicles. The factory tests shall be in accordance with IEEE C37.09 and
shall include the following tests: