0% found this document useful (0 votes)
118 views

MCC #3 Elevation: District of Sicamous Mara Lake WTP Upgrade

This document provides a single line diagram and layout for motor control center (MCC) #3. The diagram shows that MCC #3 supplies power to various pumps and fans for the wastewater treatment process. It receives 600A of copper bus power and distributes it through circuit breakers and motor circuit protectors to two distribution panelboards, two transformers, and various variable frequency drives and direct-on-line motors for equipment including exhaust fans, feed pumps, air compressors, and waste discharge pumps.

Uploaded by

Surya Kazu Maru
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
118 views

MCC #3 Elevation: District of Sicamous Mara Lake WTP Upgrade

This document provides a single line diagram and layout for motor control center (MCC) #3. The diagram shows that MCC #3 supplies power to various pumps and fans for the wastewater treatment process. It receives 600A of copper bus power and distributes it through circuit breakers and motor circuit protectors to two distribution panelboards, two transformers, and various variable frequency drives and direct-on-line motors for equipment including exhaust fans, feed pumps, air compressors, and waste discharge pumps.

Uploaded by

Surya Kazu Maru
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

300 mm

MCC #3

3050
635

635

635

510

635

200

600A CU BUS

3P, 60A CB

3P, 20A CB

3P, 60A CB

3P, 7A MCP

3P, 30A CB

3P, 15A MCP

3P, 15A MCP

3P, 15A MCP

3P, 15A MCP

DISTRIBUTION
PANELBOARD
'A'

3P, 15A MCP

3P, 15A MCP

DISTRIBUTION
PANELBOARD
'B'

2ND STAGE
UF FEED
PUMP #1
(5HP)

EAF-1
EXHAUST
FAN FOR
AHU
(3HP)

WASTE
DISCHARGE
PUMP #1
(5 HP)

AIR COMP.
#1 (7.5HP)

XFMR
45KVA,
600V/120-208V

XFMR
45KVA,
600V/120-208V

60A
FEEDER

ASD

ASD

3P, SIZE 1

ASD

3P, SIZE 1

ASD

20A
HYPO
GEN
FEEDER

100

42-CIRCUIT
LIGHTING
PANEL 'A'

LOAD
FILTER

42-CIRCUIT
LIGHTING
PANEL 'B'

LOAD
FILTER

CL. 10

CL. 10

25A
HYPO
GEN HW
FEEDER

ASD
45kVA
DISTRIBUTION

LOAD
FILTER

60A
FEEDER

LOAD
FILTER

45kVA
DISTRIBUTION

AIR COMP.
#2 (7.5HP)
2ND STAGE
UF FEED
PUMP #2
(5HP)

SPACE

WASTE
DISCHARGE
PUMP #2
(5 HP)

LOAD
FILTER

3c#12TECK90

MCC #3 ELEVATION
1:20

50

3P, 30A DS

(FROM MCC #1)

HYPOCHLORITE
GENERATION
RECTIFIER

HYPOCHLORITE
GENERATION
HOT WATER

3P, 30A DS

3P, 30A DS

3P, 30A DS

3P, 30A DS

3P, 30A DS

3P, 30A DS

3
hp

5
hp

5
hp

7.5
hp

7.5
hp

5
hp

5
hp

EAF-1
EXHAUST
FAN FOR
AHU

2nd STAGE
UF FEED
PUMP #1

2nd STAGE
UF FEED
PUMP #2

AIR
COMPRESSOR
#1

AIR
COMPRESSOR
#2

WASTE
DISCHARGE
PUMP #1

WASTE
DISCHARGE
PUMP #2

10 mm

SINGLE-LINE DIAGRAM

(SHEET 3/4)

PRELIMINARY
Revision

Amendment

Approved Revision Date

Project

R0

PRELIMINARY DESIGN - INTERNAL REVIEW

DISTRICT OF SICAMOUS
MARA LAKE WTP UPGRADE

01/23/14

North Vancouver Office


604-990-4800

1:1
@ ANSI D

10

20

Original Sheet Size ANSI D [22"x34"]

30

40

50

60

70

80

90

100

mm

Plot Date 17 Jun 2014 @ 4:36 PM Path G:\D&K CAD Drawings\DKSERVER P Share\Drawings\SICAMOUS\D-94102.00\Current Working Folder\Electrical\WTP\D-94102 E3-E9.dwg E5

210-889 Harbourside Drive


North Vancouver BC
V7P 3S1, Canada

Drawn

Designed

Approved

Revision Date

GV/RB

GV

01/23/14

Sheet

ELECTRICAL
MCC #3 SINGLE LINE DIAGRAM AND LAYOUT

Project No.

Scale

Drawing No.

Sheet. No.

Revision

D-94102.00

NTS

NV D-94102.00

E5

R0