PROJECT: COTE DIVORE AND MALI INTERCONNECTION PROJECT
CUSTOMER :
TITLE : LT POWER CABLE SCHEDULE
VOLTAGE DROP
VOLTAGE DROP in %
500
Cu
XLPE
1Cx500
980.00
0.077
0.0859
0.85
0.53
735.00
208
416
5.774
2.783
415V Switchboard
Oil Filration Unit
415
125
Cu
XLPE
3.5Cx50
133.00
0.820
0.0750
0.85
0.53
99.75
73
73
6.721
2.805
C&R Panel
415V Switchboard
C&R Panel
415
32
Cu
XLPE
4Cx50
174.00
0.495
0.0750
0.85
0.53
130.50
33
33
0.486
0.203
110/33kV Trafo-1 OLTC& Cooler-1
415V Switchboard
110/33kV Trafo-1 OLTC& Cooler-1
415
32
Cu
XLPE
4Cx6
54.00
3.940
0.0884
0.85
0.53
40.50
73
73
7.932
3.310
110/33kV Trafo-1 OLTC& Cooler-2
415V Switchboard
110/33kV Trafo-1 OLTC& Cooler-2
415
32
Cu
XLPE
4Cx6
54.00
3.940
0.0884
0.85
0.53
40.50
73
73
7.932
3.310
110/33kV Trafo-2 OLTC& Cooler-3
415V Switchboard
110/33kV Trafo-2 OLTC& Cooler-3
415
32
Cu
XLPE
4Cx6
54.00
3.940
0.0884
0.85
0.53
40.50
73
73
7.932
3.310
110/33kV Trafo-2 OLTC& Cooler-4
415V Switchboard
110/33kV Trafo-2 OLTC& Cooler-4
415
32
Cu
XLPE
4Cx6
54.00
3.940
0.0884
0.85
0.53
40.50
73
73
7.932
3.310
110/11kV Trafo-1 OLTC& Cooler-5
415V Switchboard
110/11kV Trafo-1 OLTC& Cooler-5
415
32
Cu
XLPE
4Cx10
72.00
2.340
0.0837
0.85
0.53
54.00
133
133
8.653
3.611
110/11kV Trafo-1 OLTC& Cooler-6
415V Switchboard
110/11kV Trafo-1 OLTC& Cooler-6
415
32
Cu
XLPE
4Cx10
72.00
2.340
0.0837
0.85
0.53
54.00
133
133
8.653
3.611
10
110/33kV RTCC for Trafo-1
415V Switchboard
110/33kV RTCC for Trafo-1
415
16
Cu
XLPE
2Cx4
49.00
5.900
0.0927
0.85
0.53
36.75
33
33
2.674
1.116
11
110/33kV RTCC for Trafo-2
415V Switchboard
110/33kV RTCC for Trafo-2
415
16
Cu
XLPE
2Cx4
49.00
5.900
0.0927
0.85
0.53
36.75
33
33
2.674
1.116
12
110/11kV RTCC for Trafo-3
415V Switchboard
110/11kV RTCC for Trafo-3
415
16
Cu
XLPE
2Cx4
49.00
5.900
0.0927
0.85
0.53
36.75
33
33
2.674
1.116
13
Outdoor LTG Panel
415V Switchboard
Outdoor LTG Panel
415
32
Cu
XLPE
4Cx6
54.00
3.940
0.0884
0.85
0.53
40.50
58
58
6.302
2.630
14
Indoor LTG Panel
415V Switchboard
Indoor LTG Panel
415
32
Cu
XLPE
4Cx6
54.00
3.940
0.0884
0.85
0.53
40.50
23
23
2.499
1.043
15
Fire Fighting
415V Switchboard
Fire Fighting
415
32
Cu
XLPE
4Cx6
54.00
3.940
0.0884
0.85
0.53
40.50
23
23
2.499
1.043
16
Weldting Socket
415V Switchboard
Weldting Socket
415
63
Al
XLPE
3.5Cx25
94.00
1.540
0.0805
0.85
0.53
70.50
73
73
6.215
2.594
17
110kV Metering & Control Room
415V Switchboard
110kV Metering & Control Room
415
32
Cu
XLPE
4Cx10
72.00
2.340
0.0837
0.85
0.53
54.00
128
128
8.328
3.475
18
Motorised Isolator with E/S-1
415V Switchboard
Motorised Isolator with E/S-1
415
16
Cu
XLPE
4Cx4
43.00
5.900
0.0927
0.85
0.53
32.25
108
108
8.750
3.652
19
Motorised Isolator with E/S-2
415V Switchboard
Motorised Isolator with E/S-2
415
16
Cu
XLPE
4Cx4
43.00
5.900
0.0927
0.85
0.53
32.25
95
95
7.697
3.212
20
Motorised Isolator with E/S-3
415V Switchboard
Motorised Isolator with E/S-3
415
16
Cu
XLPE
4Cx4
43.00
5.900
0.0927
0.85
0.53
32.25
108
108
8.750
3.652
21
Motorised Isolator with E/S-4
415V Switchboard
Motorised Isolator with E/S-4
415
16
Cu
XLPE
4Cx4
43.00
5.900
0.0927
0.85
0.53
32.25
95
95
7.697
3.212
22
Motorised Isolator with E/S-5
415V Switchboard
Motorised Isolator with E/S-5
415
16
Cu
XLPE
4Cx4
43.00
5.900
0.0927
0.85
0.53
32.25
88
88
7.130
2.976
23
Motorised Isolator with E/S-6
415V Switchboard
Motorised Isolator with E/S-6
415
16
Cu
XLPE
4Cx4
43.00
5.900
0.0927
0.85
0.53
32.25
88
88
7.130
2.976
24
Motorised Isolator with E/S-7
415V Switchboard
Motorised Isolator with E/S-7
415
16
Cu
XLPE
4Cx4
43.00
5.900
0.0927
0.85
0.53
32.25
103
103
8.345
3.483
25
Motorised Isolator with E/S-8
415V Switchboard
Motorised Isolator with E/S-8
415
16
Cu
XLPE
4Cx4
43.00
5.900
0.0927
0.85
0.53
32.25
68
68
5.509
2.299
26
Motorised Isolator w/o E/S-9
415V Switchboard
Motorised Isolator w/o E/S-9
415
16
Cu
XLPE
4Cx4
43.00
5.900
0.0927
0.85
0.53
32.25
68
68
5.509
2.299
27
Motorised Isolator w/o E/S-10
415V Switchboard
Motorised Isolator w/o E/S-10
415
16
Cu
XLPE
4Cx4
43.00
5.900
0.0927
0.85
0.53
32.25
113
113
9.155
3.821
28
Motorised Isolator w/o E/S-11
415V Switchboard
Motorised Isolator w/o E/S-11
415
16
Cu
XLPE
4Cx4
43.00
5.900
0.0927
0.85
0.53
32.25
96
96
7.778
3.246
29
Manual Operated Isolator-1
415V Switchboard
Manual Operated Isolator-1
415
10
Cu
XLPE
2Cx4
49.00
5.900
0.0927
0.85
0.53
36.75
133
133
6.735
2.811
30
Manual Operated Isolator-2
415V Switchboard
Manual Operated Isolator-2
415
10
Cu
XLPE
2Cx4
49.00
5.900
0.0927
0.85
0.53
36.75
113
113
5.722
2.388
31
Manual Operated Isolator-3
415V Switchboard
Manual Operated Isolator-3
415
10
Cu
XLPE
2Cx4
49.00
5.900
0.0927
0.85
0.53
36.75
133
133
6.735
2.811
32
Manual Operated Isolator-4
415V Switchboard
Manual Operated Isolator-4
415
10
Cu
XLPE
2Cx4
49.00
5.900
0.0927
0.85
0.53
36.75
113
113
5.722
2.388
Qty
GLAND QTY
Cos
415
Oil Filration Unit
TOTAL
LENGTH (L)
REACTANCE (Ohms/km)
PANEL / DRIVE
ROUTE
LENGTH (L)
RESISTANCE
(Ohms/Km)
Incoming Supply From
415V Switchboard
LTPCC
PANEL
POWER CABLE
NO.
DE-RATED CABLE
CURRENT
CURRENT CARRYING
CAPACITY OF THE
CABLE
415V Switchboard
DESCRIPTION
TO
sin
CABLE SIZE SELECTED
S.NO
FROM
NO OF RUNS
INSULATION
DATE:10.02.10
CONDUCTORS
REV:0
FEEDR RATING (A)
RATED VOLTAGE (V)
DOC.NO
Nos
CHP MCC
415V SWITCHBOARD
SHEET 1 of 6
REMARK
S
PROJECT: COTE DIVORE AND MALI INTERCONNECTION PROJECT
CUSTOMER :
TITLE : LT POWER CABLE SCHEDULE
1Cx500
490.00
0.077
0.0859
.(2)
Cu XLPE
2Cx6
60.00
3.940
0.0884
Al XLPE
2Cx6
55.00
5.900
0.0884
.(3)
Cu XLPE
3Cx4
43.00
5.900
0.0927
Al XLPE
3Cx4
34.00
9.480
0.0927
Cu XLPE
4Cx35
144.00
0.671
0.0783
Al XLPE
4Cx6
43.00
5.900
0.0884
Cu XLPE
3.5Cx25
119.00
0.930
0.0805
Al XLPE
3.5Cx25
94.00
1.540
0.0805
Formulaes Used
Voltage Drop
Vd
I ( RCos + XSin) * L/1000
Percentage Voltage Drop for
three phase current
%VD
Vd*1.732*100/V
Percentage Voltage Drop for
Single phase current
%VD
Vd*2*100/V
SHEET 2 of 6
GLAND QTY
Al XLPE
VOLTAGE DROP in %
0.0000
VOLTAGE DROP
5.900
TOTAL
LENGTH (L)
47.00
ROUTE
LENGTH (L)
1Cx4
DE-RATED CABLE
CURRENT
REACTANCE (Ohms/km)
Cu XLPE
sin
RESISTANCE
(Ohms/Km)
.(1)
Cos
CURRENT CARRYING
CAPACITY OF THE
CABLE
PANEL / DRIVE
CABLE SIZE SELECTED
PANEL
POWER CABLE
NO.
NO OF RUNS
TO
INSULATION
FROM
CONDUCTORS
DESCRIPTION
DATE:10.02.10
FEEDR RATING (A)
REV:0
RATED VOLTAGE (V)
S.NO
Qty
DOC.NO
Nos
REMARK
S
PROJECT: COTE DIVORE AND MALI INTERCONNECTION PROJECT
CUSTOMER :
TITLE : LT POWER CABLE SCHEDULE
RESISTANCE
(Ohms/Km)
DE-RATED CABLE
CURRENT
VOLTAGE DROP
VOLTAGE DROP in %
Charger
125V DCDB
125
63
Cu
XLPE
2Cx35
168.00
0.524
126.00
14
14
0.924
0.739
Battery Bank
Charger
Battery Bank
125
50
Cu
XLPE
2Cx35
168.00
0.524
126.00
20
20
1.048
0.838
225kV Line Bay BMK
125V DCDB
225kV Line Bay BMK
125
50
Cu
XLPE
2Cx70
246.00
0.268
184.50
136
136
3.645
2.916
225kV MVAr ReaCtor Bay BMK
125V DCDB
225kV MVAr ReaCtor Bay BMK
125
50
Cu
XLPE
2Cx95
288.00
0.193
216.00
181
181
3.493
2.795
ReaCtor Bay C&R Panel
125V DCDB
ReaCtor Bay C&R Panel
125
32
Cu
XLPE
2Cx10
84.00
1.830
63.00
22
22
2.577
2.061
225kV Line C&R Supply
125V DCDB
225kV Line C&R Supply
125
32
Cu
XLPE
2Cx10
84.00
1.830
63.00
22
22
2.577
2.061
415V ACDB Panel
125V DCDB
415V ACDB Panel
125
16
Cu
XLPE
2Cx6
60.00
3.080
45.00
20
20
1.971
1.577
CommuniCation System SCada
Panel Supply
125V DCDB
CommuniCation System SCada Panel
Supply
125
16
Cu
XLPE
2Cx6
60.00
3.080
45.00
20
20
1.971
1.577
CommuniCation System Fiber
OptiC Panel Supply
125V DCDB
CommuniCation System Fiber OptiC
Panel Supply
125
16
Cu
XLPE
2Cx6
60.00
3.080
45.00
20
20
1.971
1.577
10
EmergenCy Lighting
125V DCDB
EmergenCy Lighting
125
16
Cu
XLPE
2Cx6
60.00
3.080
45.00
23
23
2.267
1.814
TO
PANEL
PANEL / DRIVE
Qty
FROM
POWER CABLE NO.
GLAND QTY
CURRENT CARRYING
CAPACITY OF THE
CABLE
125V DCDB
DESCRIPTION
TOTAL
LENGTH (L)
CABLE SIZE SELECTED
S.NO
ROUTE
LENGTH (L)
INSULATION
NO OF RUNS
DATE:10.02.10
CONDUCTORS
REV:0
FEEDR RATING (A)
RATED VOLTAGE (V)
DOC.NO
Nos
CHP MCC
125V DCDB
Formulaes Used
Voltage Drop
Percentage Voltage Drop
Vd
(I *R *2 L)/1000
%VD
Vd*100/V
SHEET 3 of 6
Cu XLPE
1Cx4
47.00
4.610
Al XLPE
1Cx4
36.00
7.410
Cu XLPE
2Cx70
246.00
0.268
Al XLPE
2Cx6
55.00
4.610
Cu XLPE
3Cx4
43.00
4.610
Al XLPE
3Cx4
34.00
7.410
Cu XLPE
4Cx35
144.00
0.524
Al XLPE
4Cx6
43.00
4.610
F
I
E
L
D
PROJECT: COTE DIVORE AND MALI INTERCONNECTION PROJECT
CUSTOMER :
TITLE : LT POWER CABLE SCHEDULE
VOLTAGE DROP
VOLTAGE DROP in %
630
Cu
PVC
1Cx800
1776.00
0.028
0.0826
0.85
0.53
1332.00
208
416
4.419
2.130
415V Switchboard
Oil Filration Unit
415
125
Cu
PVC
3.5Cx50
100.00
0.829
0.0750
0.85
0.53
75.00
73
73
6.794
2.835
C&R Panel
415V Switchboard
C&R Panel
415
32
Cu
PVC
4Cx6
45.00
3.925
0.0884
0.85
0.53
33.75
33
33
3.572
1.491
110/33kV Trafo-1 OLTC& Cooler-1
415V Switchboard
110/33kV Trafo-1 OLTC& Cooler-1
415
32
Cu
PVC
4Cx6
45.00
3.925
0.0884
0.85
0.53
33.75
73
73
7.903
3.298
110/33kV Trafo-1 OLTC& Cooler-2
415V Switchboard
110/33kV Trafo-1 OLTC& Cooler-2
415
32
Cu
PVC
4Cx6
45.00
3.925
0.0884
0.85
0.53
33.75
73
73
7.903
3.298
110/33kV Trafo-2 OLTC& Cooler-3
415V Switchboard
110/33kV Trafo-2 OLTC& Cooler-3
415
32
Cu
PVC
4Cx6
45.00
3.925
0.0884
0.85
0.53
33.75
73
73
7.903
3.298
110/33kV Trafo-2 OLTC& Cooler-4
415V Switchboard
110/33kV Trafo-2 OLTC& Cooler-4
415
32
Cu
PVC
4Cx6
45.00
3.925
0.0884
0.85
0.53
33.75
73
73
7.903
3.298
110/11kV Trafo-1 OLTC& Cooler-5
415V Switchboard
110/11kV Trafo-1 OLTC& Cooler-5
415
32
Cu
PVC
4Cx10
60.00
2.332
0.0837
0.85
0.53
45.00
133
133
8.624
3.599
110/11kV Trafo-1 OLTC& Cooler-6
415V Switchboard
110/11kV Trafo-1 OLTC& Cooler-6
415
32
Cu
PVC
4Cx10
60.00
2.332
0.0837
0.85
0.53
45.00
133
133
8.624
3.599
10
110/33kV RTCC for Trafo-1
415V Switchboard
110/33kV RTCC for Trafo-1
415
16
Cu
PVC
2Cx4
41.00
5.875
0.0927
0.85
0.53
30.75
33
33
2.662
1.111
11
110/33kV RTCC for Trafo-2
415V Switchboard
110/33kV RTCC for Trafo-2
415
16
Cu
PVC
2Cx4
41.00
5.875
0.0927
0.85
0.53
30.75
33
33
2.662
1.111
12
110/11kV RTCC for Trafo-3
415V Switchboard
110/11kV RTCC for Trafo-3
415
16
Cu
PVC
2Cx4
41.00
5.875
0.0927
0.85
0.53
30.75
33
33
2.662
1.111
13
Outdoor LTG Panel
415V Switchboard
Outdoor LTG Panel
415
32
Cu
PVC
4Cx6
45.00
3.925
0.0884
0.85
0.53
33.75
58
58
6.279
2.620
14
Indoor LTG Panel
415V Switchboard
Indoor LTG Panel
415
32
Cu
PVC
4Cx6
45.00
3.925
0.0884
0.85
0.53
33.75
23
23
2.490
1.039
15
Fire Fighting
415V Switchboard
Fire Fighting
415
32
Cu
PVC
4Cx6
45.00
3.925
0.0884
0.85
0.53
33.75
23
23
2.490
1.039
16
Weldting Socket
415V Switchboard
Weldting Socket
415
63
Al
PVC
3.5Cx25
76.00
1.553
0.0805
0.85
0.53
57.00
73
73
6.265
2.615
17
110kV Metering & Control Room
415V Switchboard
110kV Metering & Control Room
415
32
Cu
PVC
4Cx10
60.00
2.332
0.0837
0.85
0.53
45.00
128
128
8.300
3.464
18
Motorised Isolator with E/S-1
415V Switchboard
Motorised Isolator with E/S-1
415
16
Cu
PVC
4Cx4
36.00
5.875
0.0927
0.85
0.53
27.00
108
108
8.714
3.637
19
Motorised Isolator with E/S-2
415V Switchboard
Motorised Isolator with E/S-2
415
16
Cu
PVC
4Cx4
36.00
5.875
0.0927
0.85
0.53
27.00
95
95
7.665
3.199
20
Motorised Isolator with E/S-3
415V Switchboard
Motorised Isolator with E/S-3
415
16
Cu
PVC
4Cx4
36.00
5.875
0.0927
0.85
0.53
27.00
108
108
8.714
3.637
21
Motorised Isolator with E/S-4
415V Switchboard
Motorised Isolator with E/S-4
415
16
Cu
PVC
4Cx4
36.00
5.875
0.0927
0.85
0.53
27.00
95
95
7.665
3.199
22
Motorised Isolator with E/S-5
415V Switchboard
Motorised Isolator with E/S-5
415
16
Cu
PVC
4Cx4
36.00
5.875
0.0927
0.85
0.53
27.00
88
88
7.100
2.963
23
Motorised Isolator with E/S-6
415V Switchboard
Motorised Isolator with E/S-6
415
16
Cu
PVC
4Cx4
36.00
5.875
0.0927
0.85
0.53
27.00
88
88
7.100
2.963
24
Motorised Isolator with E/S-7
415V Switchboard
Motorised Isolator with E/S-7
415
16
Cu
PVC
4Cx4
36.00
5.875
0.0927
0.85
0.53
27.00
103
103
8.310
3.468
25
Motorised Isolator with E/S-8
415V Switchboard
Motorised Isolator with E/S-8
415
16
Cu
PVC
4Cx4
36.00
5.875
0.0927
0.85
0.53
27.00
68
68
5.486
2.290
26
Motorised Isolator w/o E/S-9
415V Switchboard
Motorised Isolator w/o E/S-9
415
16
Cu
PVC
4Cx4
36.00
5.875
0.0927
0.85
0.53
27.00
68
68
5.486
2.290
27
Motorised Isolator w/o E/S-10
415V Switchboard
Motorised Isolator w/o E/S-10
415
16
Cu
PVC
4Cx4
36.00
5.875
0.0927
0.85
0.53
27.00
113
113
9.117
3.805
28
Motorised Isolator w/o E/S-11
415V Switchboard
Motorised Isolator w/o E/S-11
415
16
Cu
PVC
4Cx4
36.00
5.875
0.0927
0.85
0.53
27.00
96
96
7.745
3.233
29
Manual Operated Isolator-1
415V Switchboard
Manual Operated Isolator-1
415
10
Cu
PVC
2Cx4
41.00
5.875
0.0927
0.85
0.53
30.75
133
133
6.707
2.799
30
Manual Operated Isolator-2
415V Switchboard
Manual Operated Isolator-2
415
10
Cu
PVC
2Cx4
41.00
5.875
0.0927
0.85
0.53
30.75
113
113
5.698
2.378
31
Manual Operated Isolator-3
415V Switchboard
Manual Operated Isolator-3
415
10
Cu
PVC
2Cx4
41.00
5.875
0.0927
0.85
0.53
30.75
133
133
6.707
2.799
32
Manual Operated Isolator-4
415V Switchboard
Manual Operated Isolator-4
415
10
Cu
PVC
2Cx4
41.00
5.875
0.0927
0.85
0.53
30.75
113
113
5.698
2.378
Qty
GLAND QTY
Cos
415
Oil Filration Unit
TOTAL
LENGTH (L)
REACTANCE (Ohms/km)
PANEL / DRIVE
ROUTE
LENGTH (L)
RESISTANCE
(Ohms/Km)
Incoming Supply From
415V Switchboard
LTPCC
PANEL
DE-RATED CABLE
CURRENT
CURRENT CARRYING
CAPACITY OF THE
CABLE
415V Switchboard
DESCRIPTION
TO
sin
CABLE SIZE SELECTED
S.NO
FROM
POWER
CABLE
NO.
NO OF RUNS
INSULATION
DATE:10.02.10
CONDUCTORS
REV:0
FEEDR RATING (A)
RATED VOLTAGE (V)
DOC.NO
Nos
CHP MCC
415V SWITCHBOARD
SHEET 4 of 6
REMARK
S
PROJECT: COTE DIVORE AND MALI INTERCONNECTION PROJECT
CUSTOMER :
TITLE : LT POWER CABLE SCHEDULE
1Cx50
175.00
0.829
0.1080
Cu PVC
2Cx95
240.00
0.246
0.0724
Al PVC
2Cx6
40.00
5.965
0.0884
.(1)
Cu PVC
3Cx4
36.00
5.875
0.0927
Al PVC
3Cx4
28.00
9.589
0.0927
Formulaes Used
Voltage Drop
sin
Vd
I ( RCos + XSin) * L/1000
Percentage Voltage Drop for
three phase current
%VD
Vd*1.732*100/V
.(2)
Cu PVC
4Cx50
145.00
0.493
0.0750
Al PVC
4Cx6
35.00
5.965
0.0884
Percentage Voltage Drop for
Single phase current
%VD
Vd*2*100/V
.(3)
Cu PVC
3.5Cx25
99.00
0.926
0.0805
Al PVC
3.5Cx25
76.00
1.553
0.0805
R0(1+(T2-T1))
AC Resistance
.(4)
Description for Eq-4
R 0 is D.C Resistance at 20 C
isTemp Coefficient
for Copper at 20 C as per ABB
Switchgear Manual Table 1-15
page 32
for Aluminium at 20 C is as per
0.00392
ABB Switchgear Manual Table 1-15 =
page 32
0.0042
T2 in C
90
T1 in C
20
Note: Single Core Copper and Aluminium conductor datas are taken from ducab catalogue
SHEET 5 of 6
GLAND QTY
Al PVC
VOLTAGE DROP in %
0.1080
VOLTAGE DROP
0.493
TOTAL
LENGTH (L)
235.00
ROUTE
LENGTH (L)
1Cx50
DE-RATED CABLE
CURRENT
REACTANCE (Ohms/km)
Cu PVC
Cos
RESISTANCE
(Ohms/Km)
PANEL / DRIVE
CURRENT CARRYING
CAPACITY OF THE
CABLE
PANEL
CABLE SIZE SELECTED
DESCRIPTION
NO OF RUNS
TO
INSULATION
FROM
POWER
CABLE
NO.
CONDUCTORS
S.NO
DATE:10.02.10
FEEDR RATING (A)
REV:0
RATED VOLTAGE (V)
Qty
DOC.NO
Nos
REMARK
S
PROJECT: COTE DIVORE AND MALI INTERCONNECTION PROJECT
CUSTOMER :
TITLE : LT POWER CABLE SCHEDULE
RESISTANCE
(Ohms/Km)
DE-RATED CABLE
CURRENT
VOLTAGE DROP
VOLTAGE DROP in %
Charger
125V DCDB
125
63
Cu
XLPE
2Cx35
140.00
0.524
105.00
14
14
0.924
0.739
Battery Bank
Charger
Battery Bank
125
50
Cu
XLPE
2Cx35
140.00
0.524
105.00
20
20
1.048
0.838
225kV Line Bay BMK
125V DCDB
225kV Line Bay BMK
125
50
Cu
XLPE
2Cx70
205.00
0.268
153.75
136
136
3.645
2.916
225kV MVAr ReaCtor Bay BMK
125V DCDB
225kV MVAr ReaCtor Bay BMK
125
50
Cu
XLPE
2Cx95
240.00
0.193
180.00
181
181
3.493
2.795
ReaCtor Bay C&R Panel
125V DCDB
ReaCtor Bay C&R Panel
125
32
Cu
XLPE
2Cx10
70.00
1.830
52.50
22
22
2.577
2.061
225kV Line C&R Supply
125V DCDB
225kV Line C&R Supply
125
32
Cu
XLPE
2Cx10
70.00
1.830
52.50
22
22
2.577
2.061
415V ACDB Panel
125V DCDB
415V ACDB Panel
125
16
Cu
XLPE
2Cx6
50.00
3.080
37.50
20
20
1.971
1.577
CommuniCation System SCada
Panel Supply
125V DCDB
CommuniCation System SCada Panel
Supply
125
16
Cu
XLPE
2Cx6
50.00
3.080
37.50
20
20
1.971
1.577
CommuniCation System Fiber
OptiC Panel Supply
125V DCDB
CommuniCation System Fiber OptiC
Panel Supply
125
16
Cu
XLPE
2Cx6
50.00
3.080
37.50
20
20
1.971
1.577
10
EmergenCy Lighting
125V DCDB
EmergenCy Lighting
125
16
Cu
XLPE
2Cx6
50.00
3.080
37.50
23
23
2.267
1.814
Cu PVC
1Cx120
390.00
0.153
Al PVC
1Cx4
0.00
0.000
Cu PVC
2Cx70
205.00
0.268
Al PVC
2Cx6
40.00
4.610
Cu PVC
3Cx4
36.00
4.610
Al PVC
3Cx4
28.00
7.410
Cu PVC
4Cx35
120.00
0.524
Al PVC
4Cx6
35.00
4.610
TO
PANEL
PANEL / DRIVE
Qty
FROM
POWER CABLE NO.
GLAND QTY
CURRENT CARRYING
CAPACITY OF THE
CABLE
125V DCDB
DESCRIPTION
TOTAL
LENGTH (L)
CABLE SIZE SELECTED
S.NO
ROUTE
LENGTH (L)
INSULATION
NO OF RUNS
DATE:10.02.10
CONDUCTORS
REV:0
FEEDR RATING (A)
RATED VOLTAGE (V)
DOC.NO
Nos
CHP MCC
125V DCDB
Formulaes Used
Voltage Drop
Percentage Voltage Drop
Vd
(I *R *2 L)/1000
%VD
Vd*100/V
Note: Single Core Copper and Aluminium conductor datas are taken from ducab catalogue
SHEET 6 of 6