KHARAFI NATIONAL - EGYPT
CHECK LIST FOR INSTALLATION OF CONDUITS AND ACCESSORIES
Project
West Damietta Simple Cycle Gas Turbine Units
Owner
East Delta Electricity Production Company
Owner Representative
Power Generation Engineering and Services Company (PGESCo)
Contractor
Kharafi National
Sub-Contractor
Unit:
Project No.:
Location:
Area:
Report No.:
IR Ref. No.:
Ref. Drg. No.:
Date:
008004500
Signature
Sl. No.
Activity
Observation
<SUB CONTRACTOR>
KHARAFI NATIONAL
Check the conduits routed and co-ordinated with
other services as per the approved drawings.
Check conduits are properly supported at
regular intervals as following :
- EMT conduits - supported each 3 mt for all
trades size.
- IMC/RGS conduits :
*Supported each 3 mt for conduits size 21 mm
*Supported each 3.7 mt for conduits size 27 mm
* Supported each 4.3 mt for conduits size 41mm
Check that lighting and receptacles conduits
exposed to weather shall be rigid galvanized
Steel with weather proof fitting.
Check the pull box is provided at regular
intervals as per requirement if conduit runs are
more in length.
Check the outlet boxes and junction boxes
provided as per requirement.
Check the conduits have been firmly connected
to the raceways and boxes, using proper fittings.
Check conduits ends filed smoothly and free
from sharp edges.
Check threads are fully engaged.
Check flexible conduits installed wherever
necessary as per specifications.
10
Check that at No case ; the conduits have more than
4-90 degree bends from start to finish
11
Check the fitting of E.M.T conduits shall be rain tight
Compression type.
Remarks:-
ACCEPTED
< SUB CONTRACTOR >
REJECTED
KHARAFI NATIONAL
< OWNER/ OWNER REPRESENTATIVE >
Signature
Name
Position
Date
008004500/ TWI 552 Att.3 Rev. 0 1 Oct. 2011
Page 1 of 2