EDG5500
Electronic Digital Governor
ISO 9001
CERTIFIED
With Quikset Display
G
A
C
OVERNORS
MERICA
ORP.
120 Ohms
( End of CAN bus)
INSTALLATION
Vertical orientation
allows fluids to drain in
moist environments.
4X
[7]
0.27
A B C DA EB FC GD HE JF KG LHMJ NK PL M N P
Ground to
Case
Mount in a cabinet,
engine enclosure, or
sealed metal box.
DROOP
[127]
5.00
Avoid extreme heat.
Accessory
Input
[mm]
Dimensions: in
TERMINAL
DEFINITION
NOTES
Ground Signal
For Variable Speed/Trim Input & Switches
Not Used
Variable Speed Input
Potentiometer
Droop Select
Active When Connected to Terminal G
Idle Select
Active When Connected to Terminal G
Aux Input
Load Sharing / Synchronizing,
5V Nominal (0-10V), Reverse Ramp
N&P
( Optional: CAN L & H )
CAN L is Terminal N
N P
A B C D E F
Ground to Case
Fuse 15A Max
Actuator
For more basic wiring details
see the chart below:
RECOMMENDATIONS
Magnetic
Speed
Pickup
NOTE
+
Battery
(12V or 24V)
DEFINITION
A&B
Actuator (+/-)
NOTES
C&D
Gap between speed sensor and gear teeth
should not be smaller than 0.02 in. (.51mm)
Speed sensor voltage should be at least 1V
AC RMS during crank
#16 AWG (1.3mm sq) or larger wire
E&F
Battery Power (-/+)
2.
One end of each shield should be grounded to a single point on the EDG case.
DISPLAY & CONTROLS
Alpha-Numerical Area
Displays the value of a
selected parameter or
live running parameter
Displays the units for the
parameter (e.g. RPM)
A 15 amp fuse must be installed in the
positive battery lead to protect against
reverse voltage
VSPD
Range: 500 - 9999 RPM
Default: 2220 RPM
Range: 50 - 255
Default: 120
Range: 0 - 9999 RPM
Default: 400 RPM
Trim
(Default)
OFF
to allow
Rated Speed for Application. Percentage
speed trim
(e.g., 1500 RPM)
(e.g., 5% = 90RPM)
Variable
Speed
ON
Minimum speed when
potentiometer is at lowest
resistance (e.g.,1000 RPM)
SPEED RAMP
V.SPEED
LOCKED
Rate at which speed changes
from idle to speed and back
Maximum speed change
allowed from trim input
Indicates if EDG will lock
after 5 minutes of non-use
Range: 0 - 9999
Default: 400
Range: 0 - 9999 RPM
Default: 5 RPM
Range: OFF, ON
Default: OFF
START FUEL
DROOP%
Percent of fuel to apply to
actuator first upon cranking
Droop to apply under
maximum load (based on
current of actuator)
Percent per second to
apply fuel as engine starts
to idle
Range: 0 - 100%
Default: 99%
Range: 0 - 25.0%
Default: 0.0%
Range: 0 - 100%
Default: 2%
SPEED
IDLE
FUEL LIM
Operating speed of engine
Speed of engine when IDLE
input is closed
Maximum actuator
percentage allowed
Range: 0 - 9999 RPM
Default: 1500 RPM
Range: 0 - 9999 RPM
Default: 900 RPM
Range: 0 - 100%
Default: 99%
GAIN
STABILITY
DEADTIME
Proportional (P) set point of
the PID control at operating
SPEED and IDLE
Integral (I) set point of the PID
control
Derivative (D) set point of
the PID control
Range: 0 - 100,
100 = Max Gain
Default: 20
Range: 0 - 100,
100 = fastest response
Default: 36
Range: 0 - 100
Default: 21
One end of each shield, including the speed sensor shield, should be
grounded to a single point on the EDG case.
WARNING
Loss of Magnetic Pickup Sensing
If the EDG5500 detects no input from the magnetic pickup, the
EDG will set the actuator to 0V and set the speed to 0 RPM. After
the EDG has detected loss of magnetic pickup, the display will
flash the RPM along with the Warning Indicator. Parameters will
be unchangeable.
One row of parameters will be displayed
at a time.
Column
Select 1
Column
Select 2
Column
Select 3
PIB 4145 F
and TAP
or
Rapidly Increment a Value:
HOLD
Change the displayed row of parameters:
View and edit a PARAMETER
Hold: Column Select 1
Hold: Column Select 2
Hold: Column Select 3
and HOLD
Adjust Parameters: Increase
HOLD
and
for 2 seconds
Parameter
Adjust
Down
Overspeed will blink when the unit is in overspeed. (Cycle power to restart)
Before Adjusting DROOP%:
D SW
SPEED
SPEED with Auto Offset
(SPEED in Quikset Menu)
MODE
ON
Control will run at SPEED with an
offset determined by the DROOP%
Droop Speed
(DSPD in Special Menu )
OFF
Control will run to DSPD. A manual
offset is required for operation
For IDLE Speed to be active:
Parameter
Decrease
Parameter
Return to Quikset Menu:
Hold ALL 3
for 2 seconds
The Aux Terminal accepts signals from:
Definition
Range
Default
Off, On
Off
AUX
Auxiliary Input Enable
AVE
On=Averages four pulse samples from the
Mag-Pickup for more accurate response
Off= calculates Speed from pulses
accumulated over the last system update
Off, On
Variable Speed or Trim Select
(On=Variable Speed, Off=Trim)
Off, On
- Auto Synchronizers
- Load Sharing Units
- Other Governing Accessories
* GAC Accessories connect directly to
this terminal
ADJUSTING FOR STABILITY
nce the engine is running at operating speed and at no load, the following goverO
nor performance adjustments can be made to increase engine stability.
GAIN - RATED SPEED & IDLE
The EDG5500 is equipped with two separate gains, one for rated speed, the other for idle
speed. Both are set using the GAIN setting on the Quikset menu. By default, the gain for
rated speed is selected. To modify the idle gain, connect the idle input to ground and change
the gain value. When switching back, the rated gain value will remain.
To change parameters, refer to Section 4 DISPLAY & CONTROLS.
QUIKSET MENU
PARAMETER
A.
GAIN
Off
ADJUSTMENT PROCEDURE
1.
2.
3.
4.
Off
SOFT
Soft Coupling - dampening of system
(slow down response)
Off, On
Off
LEAD
Lead Circuit - response increase
Off, On
Off
D SW
Sets the droop mode (On=Auto Offset,
Off = Manual Offset)
Off, On
On
DITH
Adds white noise to actuator or throttle
body prevent sticking in the fuel rack. (%)
0 - 10
or
Locking the Displpay
TAP any
For: SPEED
For: IDLE
For: FUEL LIM
2.15
Increment a Parameter Value:
HOLD
HOLD
EDG5500 Electronic Digital Governor
Parameter
Adjust Up
Droop will replicate a mechanical governors response to a load change. In Droop
Operation, the engine speed will decrease as engine load increases. DROOP%
(Quikset Menu) is based on the change in current in the actuator (DRNG see
Section 5 Special Menu Parameters) from no load to full load.
- The optional external switch must
be tied to terminal G.
- Pressure switch may also be used
as a method of enabling.
SPECIAL MENU PARAMETERS
Quikset Menu
Maximum Speed when
potentiometer is at the
highest resistance
(e.g., 2000 RPM)
A B C D E F G A
H BJ CK DL M
E FNIDLE
G
P SPEED
H LA)J BK CL DM EN FPAccessory
G
H Input
JM ) K L M N
( Terminal
( Terminal
or
Parameter
V. SPEED
-The optional external selector switch must be in DROOP position
SPECIAL PARAMETERS MENU
NOTE
SPEED
SPEED DROOP OPERATION
A B C D FUEL
E RAMP
F G H J K L M N P( Terminals
AK & BG )( C
D Menu
E )F G H J K L M
Quikset
Previous
Next
Parameter Parameter
Loss of Magnetic Speed Pickup
Over Current
Quikset Menu
Parameters
MODE
VSPD
2.
Special Menu
Parameter
RPM which EDG switches
to starting fuel ramp
Displays Throttle, Delta
Speed Graph, and Current
TAP
Variable Speed Function - Operates over a larger RPM range
Number of teeth on
flywheel
Selecting Parameters:
TOGGLE between the 3 views:
Trim Function - Performs finer adjustments (e.g. generator frequency)
RPM to automatically shutoff
the actuator
Battery positive (+) input is Terminal F
Shielded cable should be used for all external connections to the EDG
control.
Input the Fixed Speed of the Engine (RPM)
Display Special
Hold ALL 3
until
Menu Parameters: AUX appears in display
RECOMMENDATIONS
1.
SPEED
TRIM or VARIABLE SPEED OPERATION
AcanJB&beGconnected
C) D E at:F G H J K
A B C D E F G H J K L Ma 5K
N potentiometer
P ( Terminals
CRANK
Numerical Area
#16 AWG (1.3mm sq) or larger wire
Wires must be twisted and/or shielded for
their entire length
Magnetic Speed
Pickup
(D is ground)
Shielded cable should be used for all external connections to the EDG control.
For additional wiring ( Terminals G - P ), see Section 3 OPTIONAL WIRING (TERMINALS
G-P).
TERMINAL
1.
Input the Crank Termination (RPM)
#TEETH
Ground to
Case
BASIC WIRING (TERMINALS A - F)
Input the Number of Teeth on the Flywheel
CRANK
FEATURES
OVERSPEED
CAN
( Optional )
IDLE
#TEETH
ADJUSTABLE QUIKSET PARAMETERS
[127]
5.00
[144]
5.67
PRE-START SETUP & QUIKSET PARAMETERS
The parameters to the
right must be set before
starting the engine:
Variable Speed /
Trim
[151]
5.94
OPTIONAL WIRING (TERMINALS G-P)
DRNG
System current to the actuator that
represents full load. Units in (A)
0.0 - 10.0
3.9
DSPD
Droop offset when D SW is set to Off (RPM)
0 - 9999
1500
OVRC
Over Current - Turns off actuator if specified current value is exceeded. Units in (A)
0 - 12
11.7
B.
STABILITY
1.
2.
C.
DEADTIME
NOTE
1.
Increase this parameter until instability develops.
Then, gradually decrease this parameter until stability returns.
Finally, decrease this parameter one increment further to ensure
stable performance.
If instability persists, adjust the next parameter.
Follow the same adjustment procedure as the GAIN
parameter.
If instability persists, adjust the next parameter.
Follow the same adjustment procedure as the GAIN
parameter.
Normally, adjustments made at no load achieve satisfactory performance. If further
performance improvements are required, refer to Section (9) ADVANCED PARAMETERS MENU and Section (10) SYSTEM TROUBLESHOOTING.
11
ADVANCED PARAMETERS MENU
SPECIFICATIONS
Advanced Menu Parameters will further adjust engine stability.
until
DISPLAYING ADVANCED Hold ALL 3
MENU PARAMETERS:
RATE appears in display.
Decrease
Adjust Parameters: Increase
Parameter
Parameter
Hold ALL 3
for 2 seconds
Parameter
Definition
Range
Default
RATE
The time (mS) between calls to the PID control loop.
4 - 250 mS
FLTR
Number of speed samples in frequency calculation.
Filter is active when soft coupling (SOFT) is set to
ON. Lower numbers filter high frequency noise.
1 - 62
samples
GMUL
If the GAIN parameter is at maximum and more
GAIN is required, increase GMUL. GAIN will be
more responsive. If small changes in the GAIN
parameter are over responsive, decrease GMUL.
1 - 20
SMUL
If the STABILITY parameter is at maximum and more
STABILITY is required, increase SMUL. STABILITY
will be more responsive. If small changes in STABILITY parameter are over responsive, decrease SMUL.
1 - 20
DMUL
If DEADTIME value is at maximum and more DEADTIME is required, increase DMUL. DEADTIME will be
more responsive. If small changes in DEADTIME parameter are over responsive, decrease DMUL.
NOTE
0.25%
400Hz - 10 KHz
(200-500 RPM w/ 120 tooth flywheel) continuous
Idle Adjust
Full Range
Droop Range
1 - 5% regulation
Speed Trim
Programmable 0-100%, (default = 5%)
40
17
12
Multiplier Changes can make drastic changes. Changing a multiplier
(e.g. GMUL) will affect the corresponding Quikset parameter (e.g.
GAIN) in two ways:
1. If the multiplier is decreased by 1, corresponding Quikset value
will double.
2. If the multiplier is increased by 1, corresponding Quikset value
will halve.
The engine will maintain current operation while adjusting parameters.
( i.e. NO CHANGES ) Since the scaling will be made to the Gain, Stability, and Derivitive parameters automatically, go back and readjust these
parameters to the diesired levels.
12-24 VDC Battery Systems (7.0 to 33 VDC)
Polarity
Negative Ground
Speed Sensor Signal
Dimension
See Section 1 Installation
Weight
1.8 lbs. (820 grams)
Mounting
Any position, Vertical Preferred
G
A
C
MERICA
R
720 Silver Street,
Agawam, MA 01001 USA
[email protected]www.governors-america.com
8-10 Amps Continuous
Load Share /
Synchronizer Input
ORP.
0-10 VDC ( 5V nominal, reversed, 100Hz / V )
Reverse Power Protection
Yes
Transient Voltage Protection
60V
RELIABILITY
Vibration
7G, 20-100 Hz
Shock
20G Peak
Testing
100% Functional Testing
ENVIRONMENTAL
Ambient Temperature
-40 to 85C (-40 to 180F)
Relative Humidity
up to 95%
Fungus Proof and Corrosion Resistant
EN55011, EN50081-2, EN50082-2
SYSTEM TROUBLESHOOTING
Instability
System Inoperative
If the engine governing system does not function, the fault may be determined by
performing the voltage tests described in Steps 1 through 3. Positive (+) and negative (-) refer to meter polarity. Should normal values be indicated during troubleshooting steps, then the fault may be with the actuator or the wiring to the actuator.
Tests are performed with battery power on and the engine off, except where noted.
See actuator publication for testing procedure on the actuator.
STEP
WIRES
NORMAL READING
PROBABLE CAUSE OF
ABNORMAL READING
F(+) & E(-)
Battery Supply
Voltage
(12 or 24V DC)
1. DC battery power not connected. Check for blown fuse
2. Low battery voltage
INSTABILITY
Fast Periodic
Slow Periodic
3. Wiring error
C&D
1.0V AC RMS min.
while cranking
Unsatisfactory Performance
The engine
seems to jitter
with a 3Hz or
faster irregularity
of speed. (Not as
moderate)
1.
Make sure LEAD Special parameter is
set to OFF.
2.
Readjust the GAIN and STABILITY for
optimum control.
3.
In extreme cases, decrease the
DEADTIME parameter.
An irregularity
of speed below
3Hz. (Sometimes
severe)
1.
Verify the SOFT (soft coupling) Special
Manu parameter is disabled.
2.
Decrease the update rate of the controller by decreasing the RATE Advanced
parameter. (Each time RATE is changed,
GAIN, STABILITY, and DEADTIME must
be re-adjusted.
1. Gap between speed sensor
and gear teeth too great
3.
3. Resistance between D and C
should be 130 to 1200 ohms.
See specific mag pickup data
for resistance. Defective speed
sensor.
F(+) & A(-)
1.0 - 2.0V DC while
cranking
PROBABLE CAUSE OF
ABNORMAL READING
SYMPTOM
2. Improper or defective wiring to
the speed sensor
SAE J1939 (Option)
PHYSICAL
1.0-120 VRMS
CE Rated
Communications
70mA max. continuous plus actuator current
All Surface Finishes
10
CE and RoHS Requirements
OVERNORS
Supply
Actuator
1 - 20
Agency
INPUT / OUTPUT
Power Consumption
17
COMPLIANCE / STANDARDS
Isochronous Operation
Speed Range / Governor
ADVANCED MENU PARAMETERS
CAUTION
PERFORMANCE
Return to Quikset Menu:
1. SPEED or IDLE parameter set
imcorrectly
2. CRANK or START FUEL set
incorrectly
3. Short/open in actuator wiring
4. Defective speed control
5. Defective actuator, see
Actuator Troubleshooting
Non-Periodic
Erratic Engine
Behavior
SYMPTOM
Engine
Overspeeds
Dead Time Parameter set too high.
1.
Increasing the GAIN should reduce the
instability but not totaly correct it. If this
is the case, there is most likely a problem
with the engine itself.
Check for:
a. engine mis-firings
b. an erratic fuel system
c. load changes on the generator set
voltage regulator.
If unsuccessful in solving instability, contact GAC for assistance.
[email protected]413-233-1888
1. Do Not Crank. Apply
DC power to the
governor system.
1.
2. Manually hold the
engine at the desired
running speed. Measure the DC voltage
between Terminals
A(-) & F(+) on the
speed control unit.
1.
If the actuator is at minimum fuel position and there exists an erroneous
position signal, then check speed sensor.
If the voltage reading is
1.0 to 2.0V DC:
a. SPEED parameter set above
desired speed
b. Defective speed control unit
2.
If voltage reading is > 2.0V DC then
check for:
3.
NORMAL READING
Overspeed
shuts down
engine
before running speed
is reached
1. Check resistance
between Terminals
C&D. Should be 130
to 1200 ohms. See
specific Magnetic
Pick-up data for
resistance.
1.
OVERSPEED set too low
2.
If the speed sensor signal is erroneous, then check the wiring.
Actuator
does not
energize
fully
1. Measure the voltage
at the battery while
cranking.
1.
If the voltage is less than:
a. 7V for a 12V system, or
b. 14V for a 24V system,
Then: 1. Check wiring
2. Check circuit protection/relay
3. Check charging system
4. Check battery
2. Momentarily connect
Terminals B and F.
The actuator should
move to the full fuel
position.
1.
Actuator or battery wiring in error
2.
Actuator or linkage binding
3.
Defective actuator
4.
Fuse open. Check for short in
actuator or harness.
5.
Check START FUEL and CRANK
If the voltage reading is
below 1.0V DC:
a. Defective speed control unit
Overspeed
shuts down
engine after running
speed is
reached
3. Check #TEETH
parameter.
1.
Incorrect tooth count entered.
1. Examine the SPEED
and OVER SPEED
operating parameters for the engine
1.
SPEED parameter set too high.
2.
OVERSPEED set too close to
SPEED.
3.
Check SPEED RAMP parameter.
4.
Actuator or linkage binding.
5.
Speed Control unit defective.
6.
Gain too low.
PROBABLE CAUSE OF
ABNORMAL READING
SYMPTOM
a. actuator binding
b. linkage binding
Check fuel system linkage during engine
operation for:
a. binding
b. high friction
c. poor linkage
4.
PROBABLE CAUSE OF
ABNORMAL READING
NORMAL READING
Engine
remains
below
desired
governed
speed
1. Measure the actuator 1.
output, Terminals A
& B, while running
under governor
control.
2.
If voltage measurement is within 2V
DC of the battery supply voltage level, then fuel control is restricted from
reaching full fuel position, possibly
due to mechanical governor, carburetor spring, or linkage interference.
Check SPEED, IDLE, GAIN, START
FUEL, and CRANK
EDG5500 Electronic Digital Governor
2.15
PIB 4145 F