Transmissores Microprocessados
Mod. EQ 350
PROFIBUS PA ver. 3.0
FOUNDATION
Automatic switch between protocols
Basic or LAS capability with F.F.
TM
Application
Fieldbus ver. ITK 4.51
Standard signal
Function
Level
Mounting
DIN form B sensor head
Input
Lin. R 0..100 kohm
Output
Profibus PA
FOUNDATION Fieldbus
Supply
Bus-powered
Channels
1 channel
Configuration
Profibus
FOUNDATION Fieldbus
Features
PID controller
Customer linearisation
Alarm/control
Electrical specifications:
Specifications range:
-40 C to +85C
Common specifications:
Supply voltage..................................... 9...32 VDC
Consumption ............................ < 11 mA
Isolation Voltage, test / operation......... 1.5 kVAC / 50 VAC
Signal / noise ratio................................ Min. 60 dB
Response time (programmable).... 160s
Updating time.... < 400ms
Execution time, PID controller.... < 200ms
Execution time, analogue input.. < 50ms
Signal dynamics, input ......................... 24 bit
Calibration temperature... 2028C
Accuracy, the greater of general and basic values:
General values
Absolute
accuracy
Input type
0.05% of reading
All
Temperature
coefficient
0.002% of reading / C
Basic values
Input type
Pt100 and PT1000
Ni100
Cu10
Lin. R.
Vibration ......................................................................... IEC 68-2-6 Test FC
Lloyds specification no. 1............................................... 4 g / 2...100 Hz
Humidity ......................................................................... < 95% RH (non-cond.)
Dimensions...................................................................... 44 x 20.2 mm
Tightness (enclosure / terminal) ..................................... IP68 / IP00
Weight............................................................................. 55 g
Electrical specifications, input:
RTD and linear resistance input:
RTD
type
Pt25Pt1000
Ni25NI1000
Cu10Cu1000
Lin.Resistance
Potentiometer
Min.
value
-200C
-60C
-50C
0W
0W
Max.
value
+850C
+250C
+200C
10k W
100k W
Norm
IEC60751/JIS C 1604
DIN 43760
= 0.00427
-
Cable resistance per wire.................................................50 W
Sensor current..................................................................nom. 0,2 mA
Effect of sensor cable resistance
(3- / 4-wire).......................................................................< 0.002 W / W
Sensor error detection......................................................Yes
Short circuit detection.......................................................< 15 W
TC / mV input:
Type
B
E
J
K
L
N
R
S
T
U
W3
W5
Ext. CJC
mV
Min.
Temperature
+400C
-100C
-100C
-180C
-100C
-180C
-50C
-50C
-200C
-200C
0C
0C
-40C
-800
Max.
Temperature
+1820C
+1000C
+1200C
+1372C
+900C
+1300C
+1760C
+1760C
+400C
+600C
+2300C
+2300C
+135C
+800
Norm
IEC584
IEC584
IEC584
IEC584
DIN 43710
IEC584
IEC584
IEC584
IEC584
DIN 43710
ASTM E988-90
ASTM E988-90
IEC60751
-
Basic
accuracy
Temperature
coefficient
0.1C
0.002C / C
1.3C
0.05W
0.02C / C
0.002W / C
Cold junction compensation (CJC)..............................< 0,5 C
Sensor error detection...............................yes
Sensor error current:
When detecting.............................................................Nom. 4A
Else................................0 A
Short circuit detection.............................< 3mV
Output:
FOUNDATIONTM Fieldbus connection:
TM
FOUNDATION Fieldbus version.............................. ITK 4.51
TM
0.15
0.002C / C
Volt
10V
TC type:
E, J, K, L, N, T, U
TC type:
B, R, S, W3, W5
0.2 V /C
0.5C
0.010C / C
1C
0.025C / C
EMC immunity influence .............< 0.1% of reading
Extended EMC immunity:
NAMUR NE 21, A criterion, burst..< 1% of reading
www.equipe-termopar.com.br
FOUNDATION F. capability.........................................Basic or LAS
TM
FOUNDATION F. function blocks.................................2 analogue and 1 PID
PROFIBUS PA connection:
PROFIBUS PA protocol standard..................................EN 50170 vol. 2
PROFIBUS PA function blocks......................................2 analogue
PROFIBUS PA address (at delivery)..............................126
Tel.: (11) 4191-1244 - Fax: (11) 4195-1640