LITHIUM POWER
ONYX
Large Capacity Lithium Ion Batteries
For Standby Power Applications
ONYX Features:
Lithium Ion Chemistry
Lightweight, high performance cells
Integrated Battery Management System (BMS)
Controls critical functions to ensure safety and reliability
o Monitors voltage and current
o Protects the battery in the event of over-charge and over-discharge
o Performs State of Charge calculation
o Performs State of Health calculations
o Performs cell balancing within the module
o Internal memory to track operating conditions
Integrated Status Indicator
Red/Green LED visually indicates battery status
Horizontal or Vertical Operation
Design Life on Float
10 Years at 25C/77F per Telcordia GR-3150-CORE Section 5.1.4
Available Data Logger with Remote Access Capabilities
LITHIUM POWER
ONYX Capacity, Dimensions and Weight
Model
Nominal
Number
Voltage
M70X24V068P
+24
M70X48V010P
+48
M70X48V024P
+48
M70X48V034P
+48
M70X48V010N
-48
M70X48V024N
-48
M70X48V034N
-48
Nominal Dimensions
Weight
Capacity Inches Millimeters
(Ah) 8hr
Certifications
rate at
25C
L
W H
L
W
H
lbs
kg
68
10.7 3.4 14.4 273 86 366
29.5
13.4
in progress
10
10.1 3.4 5.9 256 86 150
8.8
4.0
in progress
24
10.1 3.4 10.7 256 86 272
19.4
8.8
in progress
34
10.1 3.4 14.4 256 86 366
27.3
12.4
in progress
10
10.1 3.4 5.9 256 86 150
8.8
4.0
in progress
24
10.1 3.4 10.7 256 86 272
19.4
8.8 NEBS 1 & 3, UN 38.3
34
10.1 3.4 14.4 256 86 366
27.3
12.4
in progress
Multi-colored LED
MDC Connectors
L
W
SDC
Connector
High Voltage
Connector
H
DATA LOGGER
ONYX Specifications
+24V Line
-48V Line
+48V Line
29.0 +/- 0.3V
53.8 +/- 0.5V
53.8 +/- 0.5V
Applied Charge Voltage
Operating Temperature
-20C to +60C / -4F to 140F
Minimum Charging Temperature
0C / 32F
Discharge Cut-Off
22.6V
42V
42V
Maximum Discharge Current
15A
10A
15A
Installation Orientation
Bottom, side or end
Storage Temperature
-20C to +45C
Alarm and Monitoring Dry contact, Data logger with alarming, Internet (TCP/IP)
Battery Status Indicator
Note:
Design and/or specifications are subject to change without notice. Do not use for detailed design of
equipment or facilities.
If questions arise, contact your local Exide Technologies Industrial Energy sales representative
for clarification.
Exide Technologies Industrial Energy
USA - Tel: 877.462.4636
Canada - Tel: 604.525.4114
www.exide.com
SECTION 28.10 2010-01
Multi-Colored LED