Potential Transformers
Potential Transformers
Crompton Instruments
1610 Cobb International Parkway, Unit #4
Kennesaw, GA 30152
Tel. 770-425-8903
Fax. 770-423-7194
compensation is greater- resulting in lower output voltages. When one attempts to use
these transformers in reverse the transformer will not be harmed; however, the output
voltage will be lower than is indicated by the nameplate.
8) Can a Single Phase Transformer be used on a Three Phase source?
Yes. Any single phase transformer can be used on a three phase source by connecting the
primary leads to any two wires of a three phase system, regardless of whether the source
is three phase 3-wire or three phase 4- wire. The transformer output will be single phase.
9) Can Transformers develop Three Phase power from a Single Phase source?
No. Phase converters or phase shifting devices such as reactors and capacitors are
required to convert single phase power to three phase.
10) How do you select transformers?
1. Determine primary voltage and frequency.
2. Determine secondary voltage required.
3. Determine the capacity required in volt-amperes.
This is done by multiplying the load current (amperes) by the load voltage (volts)
for single phase. For example: if the load is 40 amperes, such as a motor, and the
secondary voltage is 240 volts, then 240 x 40 equals 9600 VA A 10 KVA (10,000
volt-amperes) transformer is required. ALWAYS SELECT THE
TRANSFORMER LARGER THAN THE ACTUAL LOAD. This is done for
safety purposes and allows for expansion, in case more load is added at a later
date. For 3 phase KVA, multiply rated volts x load amps x 1.73 (square root of 3)
then divide by 1000.
4. Determine whether taps are required. Taps are usually specified on larger
transformers.
5. Use the selection charts in the Acme catalog.
11) What terminations are provided?
Primary and Secondary Terminations are provided on ACME Dry Type Transformers as
follows:
No lugs-lead type connection on:
Maximum
Ambient
Temperature
40 deg. C (104 deg. F)
50 deg. C (122 deg. F)
60 deg. C (140 deg. F)
Maximum
Percentage
of Loading
100%
92%
84%
Instead of ordering custom built transformers to operate in ambients higher than 40 deg.
C, it is more economical to use a standard transformer of a larger KVA rating.
25) Can transformers listed in this catalog be reconnected as autotransformers to
increase their KVA rating?
Several standard single phase transformers listed in this catalog can be connected as
autotransformers. The KVA capacity will be greatly increased when used as an
autotransformer, in comparison to the nameplate KVA as an insulating transformer.
Examples of autotransformer applications are changing 600 volts to 480 volts in either
single phase or three phase; changing 480 volts to 240 volts single or three phase or vice
versa; or the developing of a fourth wire (neutral) from a 480 volt three phase three wire
system for obtaining 277 volts single phase. This voltage is normally used for operating
fluorescent lamps or similar devices requiring 277 volts. For further details showing
KVA and voltage combinations for various autotransformer connections refer to the
Acme catalog.
26) Are ACME transformers shown in this catalog U.L. Listed?
All of the transformers, with few exceptions, are listed by Underwriters' Laboratories and
have met their rigorous requirements. We are also prepared to have transformers, which
are not presently listed, submitted for listing to Underwriters' upon the customer's
request. Please contact the factory for details.
27) Is CSA certification available for transformers shown in this catalog?
Most ACME transformers shown in this catalog are certified by Canadian Standards
Association. They have been designed and tested in accordance with the latest
specifications. Please contact the factory if further details are required.
28) What is BIL and how does it apply to transformers listed in this catalog?
BIL is an abbreviation for Basic Impulse Level. Impulse tests are dielectric tests that
consist of the application of a high frequency steep wave front voltage between windings,
and between windings and ground. The Basic Impulse Level of a transformer is a method
of expressing the voltage surge lightning, switching surges, etc.) that a transformer will
tolerate without breakdown. All transformers manufactured in this catalog, 600 volts and
below, will withstand the NEMA standard BIL rating, which is 10 KV. This assures the
user that he will not experience breakdowns when his system is properly protected with
lightning arrestors or similar surge protection devices.
29) What is polarity, when associated with a transformer?
Polarity is the instantaneous voltage obtained from the primary winding in relation to the
secondary winding. Transformers 600 volts and below are normally connected in additive
polarity - that is, when tested the terminals of the high voltage and low voltage windings
on the left hand side are connected together, refer to diagram below. This leaves one high
voltage and one low voltage terminal unconnected. When the transformer is excited, the
resultant voltage appearing across a voltmeter will be the sum of the high and low voltage
windings. This is useful when connecting single phase transformers in parallel for three
phase operations. Polarity is a term used only with single phase transformers.
30) What is exciting current?
Exciting current, when used in connection with transformers, is the current or amperes
required for excitation. The exciting current on most fighting and power transformers
varies from approximately 10% on small sizes of about 1 KVA and smaller to
approximately .5% to 4% on larger sizes of 750 KVA. The exciting current is made up of
two components, one of which is a real component and is in the form of losses or referred
to as no load watts; the other is in the form of reactive power and is referred to as KVAR.
31) Will a transformer change Three Phase to Single Phase?
A transformer will not act as a phase changing device when attempting to change three
phase to single phase. There is no way that a transformer will take three phase in and
deliver single phase out while at the same time presenting a balanced load to the three
phase supply system. There are, however, circuits available to change three phase to two
phase or vice versa using standard dual wound transformers. Please contact the factory
for two phase applications.
32) Can air cooled transformers be applied to motor loads?
This is an excellent application for air cooled transformers. Even though the inrush or
starting current is five to seven times normal running current the resultant lower voltage
caused by this momentary overloading is actually beneficial in that a cushioning effect on
motor starting is the result. The tables shown in "Steps for Selecting a Transformer"
illustrate some typical requirements for use with motor applications.
33) How is an Acme Drive Isolation Transformer (DIT) different than a General
Purpose Transformer?
DITs, as the name implies, are designed to be used with motor drives (AC and DC) and
to provide isolation from the service line. They are specifically designed to withstand the
"short circuit-like" duty imposed by the filing of the thyristors. Harmonics generated by
drives create added loads on the transformer. Therefore, it is important that a transformer
of equal or greater KVA to that recommended by the drive manufacturer be installed for
a particular motor application.
34) How are transformers sized to operate Three Phase induction type squirrel cage
motors?
The minimum transformer KVA rating required to operate a motor is calculated as
follows: Minimum Transformer KVA
Running Load Amperes x 1.73 x Motor Operating Voltage
_____________________________________________________
1000
NOTE: If motor is to be started more than once per hour add 20% additional KVA.
Care should be exercised in sizing a transformer for an induction type squirrel cage motor
as when it is started, the lock rotor amperage is approximately 5 to 7 times the running
load amperage. This severe starting overload will result in a drop of the transformer
output voltage. When the voltage is low the torque and the horsepower of the motor will
drop proportionately to the square of the voltage. For example: If the voltage were to
drop to 70% of nominal, then motor horsepower and torque would drop to 70% squared
or 49% of the motor nameplate rating.
The underlying problem is low voltage at the motor terminals. If the ampere rating of the
motor and transformer overcurrent device falls within the motor's 50% RPM draw
requirements, a problem is likely to develop. The overcurrent device may not open under
intermediate motor ampere loading conditions. Overheating of the motor and/or
transformer would occur, possibly causing failure of either component.
This condition is more pronounced when one transformer is used to power one motor and
the running amperes of the motor is in the vicinity of the full load ampere rating of the
transforrner. The following precautions should be followed:
1. When one transformer is used to operate one motor, the running amperes of the
motor should not exceed 65% of the transformer's full load ampere rating.
2. If several motors are being operated from one transformer, avoid having all
motors start at the same time. If this is impractical, then size the transformer so
that the total running current does not exceed 65% of the transformer's full load
ampere rating.
35) Why are Small Distribution Transformers not used for Industrial Control
Applications?
Industrial control equipment demands a momentary overload capacity of three to eight
times normal capacity. This is most prevalent in solenoid or magnetic contactor
applications where inrush currents can be three to eight times as high as normal sealed or
holding currents but still maintain normal voltage at this momentary overloaded
condition. Distribution transformers are designed for good regulation up to 100 percent
loading, but their output voltage will drop rapidly on momentary overloads of this type
making them unsuitable for high inrush applications.
Industrial control transformers are designed especially for maintaining a high degree of
regulation even at eight times normal load. This results in a larger and generally more
expensive transformer. For a complete listing of ACME industrial control transformers,
refer to Section V in the ACME catalog.
36) Can 4-Winding Single Phase Transformer be auto-connected?
Yes. There are occasions where 480 volts single phase can be stepped down to 240 volts
single phase by autoconnecting a standard. If connected in this manner, the nameplate
KVA is doubled.
37) What about balanced loading on Three Phases?
Each phase of a three phase transformer must be considered as a single phase transformer
when determining loading. For example: A 45 KVA three phase transformer with a
208Y/120 volt secondary is to service 4 loads at 120 volts single phase each. These loads
are 10 KVA, 5 KVA, 8 KVA, and 4 KVA.
NOTE: That maximum loading on any phase does not exceed 10 KVA. Each phase has a
15 KVA capacity.
45 KVA = 15 KVA per phase
_____
3 phase
If incorrect method is used, phase B will have an 18 KVA load which is 3 KVA above its
normal capacity of 15 KVA and failure will result even though we only have a total load
of 27 KVA on a 45 KVA transformer.
38) What is meant by "Balanced Loading" on Single Phase Transformer
applications?
Since most single phase transformers have a secondary voltage of 120/240, they will be
operated as a three wire system. Care must be taken in properly distributing the load as
the transformer secondary consists of 2 separate 120 volt windings. Each 120 volt
winding is rated at one-half the nameplate KVA rating. For example: A 10 KVA
transformer, 120/240 volt secondary is to service an 8 KVA load at 240 volts and two 1
KVA loads at 120 volts each.
If the incorrect method is used, winding A will be loaded at 6 KVA, and winding B will
be loaded at 4 KVA. These do total 10 KVA but since each winding is only rated at 5
KVA (1/2 of nameplate rating), we have an overloaded transformer and a certain failure.
39) What are typical applications for transformers?
ACME transformers should be specified to:
1.
2.
3.
4.
5.
6.
7.