Capitalization of losses as per supplied Transformers
A Factor as per UHBVN = Rs. 192.873
B Factor as per UHBVN = Rs. 25.479
Calculation:
SUPPLIED
TRANSFORMER LOSSES
(As per approved GTP)
BEE 4 STAR RATED TRANSFORMER LOSSES
FULL LOAD 50% LOAD 100 % LOAD
DTR
NO LOAD
NO LOAD FULL LOAD
25 KVA
36 W
685 W
190 W
635 W
63 KVA
55 W
1235 W
340 V
1140 W
41.67 W
73.34 W
593.33 W
1066.67 W
Max losses at 100% load = No Load losses + Full load losses
2
Max losses at 50% load = No load losses + (0.5) X full load losses
Difference in losses
No Load (A-E )
Full Load (B-F )
25 KVA
-5.67 W
91.67 W
63 KVA
-18.34 W
168.33 W
Net Difference in loss value as follows:
25 KVA
63 KVA
=
=
(-5.67)X192.873 + (91.67)X25.479
(-18.34)X192.873 + (168.33)X25.479
=
=
Rs. 1242.07
Rs. 751.59
*No load & full load losses calculation for BEE 4 Star rated transformer as follows
25 KVA Transformer :
Max losses at 100% load = No Load losses + Full load losses
= 635 = x + y
2
Max losses at 50% load = No load losses + (0.5) X full load losses
= 190 = x + 0.25 (y)
635 = x + y
190 = x + 0.25 (y) which gives x = 41.67 & y = 593.33
63 KVA Transformer :
1140 = x + y
340 = x + 0.25 (y)
which gives x = 73.33 & y = 1066.67