Capitalisation of Losses

The document calculates the capitalization of losses for 25 KVA and 63 KVA transformers supplied by UHBVN. It provides the no load and full load losses for the supplied transformers and for BEE 4 star rated transformers. It then calculates the difference in losses between the supplied and BEE rated transformers. The net difference in loss value is Rs. 1242.07 for the 25 KVA transformer and Rs. 751.59 for the 63 KVA transformer.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
228 views1 page

Capitalisation of Losses

The document calculates the capitalization of losses for 25 KVA and 63 KVA transformers supplied by UHBVN. It provides the no load and full load losses for the supplied transformers and for BEE 4 star rated transformers. It then calculates the difference in losses between the supplied and BEE rated transformers. The net difference in loss value is Rs. 1242.07 for the 25 KVA transformer and Rs. 751.59 for the 63 KVA transformer.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 1

Capitalization of losses as per supplied Transformers

A Factor as per UHBVN = Rs. 192.873


B Factor as per UHBVN = Rs. 25.479
Calculation:
SUPPLIED
TRANSFORMER LOSSES
(As per approved GTP)

BEE 4 STAR RATED TRANSFORMER LOSSES

FULL LOAD 50% LOAD 100 % LOAD

DTR

NO LOAD

NO LOAD FULL LOAD

25 KVA

36 W

685 W

190 W

635 W

63 KVA

55 W

1235 W

340 V

1140 W

41.67 W
73.34 W

593.33 W

1066.67 W

Max losses at 100% load = No Load losses + Full load losses


2
Max losses at 50% load = No load losses + (0.5) X full load losses
Difference in losses

No Load (A-E )

Full Load (B-F )

25 KVA

-5.67 W

91.67 W

63 KVA

-18.34 W

168.33 W

Net Difference in loss value as follows:


25 KVA
63 KVA

=
=

(-5.67)X192.873 + (91.67)X25.479
(-18.34)X192.873 + (168.33)X25.479

=
=

Rs. 1242.07
Rs. 751.59

*No load & full load losses calculation for BEE 4 Star rated transformer as follows
25 KVA Transformer :
Max losses at 100% load = No Load losses + Full load losses
= 635 = x + y
2
Max losses at 50% load = No load losses + (0.5) X full load losses
= 190 = x + 0.25 (y)
635 = x + y
190 = x + 0.25 (y) which gives x = 41.67 & y = 593.33
63 KVA Transformer :
1140 = x + y
340 = x + 0.25 (y)

which gives x = 73.33 & y = 1066.67