POWER SYSTEM PROTECTION
and SWITCHGEAR
RUD ec
ET RRC 0 aTata McGraw-Hill
Published by Tata McGraw Hill Education Private Limited,
7 West Patel Nagar, New Delhi 110 008.
Power System Protection and Switchgear, 2/e
Copyright © 2011 by Tata McGraw Hill Education Private Limited
No part of this publication may be reproduced or distributed in any form or by any means, electronic,
mechanical, photocopying, recording, or otherwise or stored in a database or retrieval system without
the prior written permission of the publishers. The program listings (if any) may be entered, stored and
executed in a computer system, but they may not be reproduced for publication.
This edition can be exported from India only by the publishers,
‘Tata McGraw Hill Education Private Limited.
ISBN (13): 978-0-07-107774-3,
ISBN (10): 0-07-107774-X
‘Vice President and Managing Director—McGraw-Hill Education, Asia-Pacific Region: Ajay Shukla
Head—Higher Education Publishing and Marketing: Vibha Mahajan
Publishing Manager (SEM & Tech. Ed.): Shalini Jha
Senior Editorial Researcher: Koyel Ghosh
Executive—Editorial Services: Sohini Mukherjee
Senior Production Manager: Satinder S Baveja
Production Executive: Anuj Kumar Shriwastava
Marketing Manager—Higher Education: Vijay S Jaganathan
Senior Product Specialist: John Mathews
General Manager—Production: Rajender P Ghansela
Assistant General Manager—Production: B L Dogra
Information contained in this work has been obtained by Tata McGraw-Hill, from sources
believed to be reliable. However, neither Tata McGraw-Hill nor its authors guarantee the accu-
racy or completeness of any information published herein, and neither Tata McGraw-Hill nor
its authors shall be responsible for any errors, omissions, or damages arising out of use of this
information. This work is published with the understanding that Tata McGraw-Hill and its
authors are supplying information but are not attempting to render engineering or other pro-
fessional services. If such services are required, the assistance of an appropriate professional
should be sought.
‘Typeset at Bharati Composers, D-6/159, Sector-VI, Rohini, Delhi 110 085, and printed at
A. P Offset, M-135, Panchsheel Garden Naveen Shahdara, Dethi 110 032
Cover: A.P, Offset
RYXCRRQWRQCCX
Reel le ee rtProface
Contents
xiti
1. Introduction 1
1
1
1
1
1
1
1
Ma
12
13
14
15
16
17
18
19
10
al
12
13
14
5
16
‘7
Need for Protective Systems /
Nature and Causes of Faults 2
Types of Faults 3
Effects of Faults 4
Fault Statistics 5
Evolution of Protective Relays 6
Zones of Protection 9
Primary and Back-up Protection 10
Essential Qualities of Protection 1/7
Performance of Protective Relays /2
Classification of Protective Relays 14
Components of a Protection System 18
Classification of Protective Schemes 19
Automatic Reclosing 20
Current Transformers (CTs) for Protection 20
Voltage Transformers (VTs) 22
Basic Relay Terminology 23
Exercises 31
Relay Construction and Operating Principles 32
21
2.2
23
24
25
Introduction 32
Electromechanical Relays 33
Static Relays 50
Numerical Relays 6/
Comparison between Electromechanical Relays
and Numerical Relays 63
Exercises 64vi
35
6.
Contents
Current and Voltage Transformers 65
3.1 Introduction 65
2 Current transformers (CTs) 65
3 Voltage Transformers (VTs) 89
Summation transformer 93
ww ww
ak
Phase-sequence Current-segregating Network 94
Exercises 95
Fault Analysis 96
4.1 Introduction 96
4.2 Per-Unit System 98
43 One-Line Diagram 102
44 Impedance and Reactance Diagrams 103
4.5 Symmetrical Fault Analysis 107
4.6 Symmetrical Components 1/46
4.7 Unsymmetrical Fault Analysis 168
48 Grounding (Earthing) 98
Exercises 215
Overcurrent Protection 221
5.1 Introduction 221
5.2 Time-current Characteristics 22]
5.3 Current Setting 225
54 Time Setting 226
5.5 Overcurrent Protective Schemes 228
5.6 Reverse Power or Directional Relay 234
5.7 Protection of Parallel Feeders 237
5.8 Protection of Ring Mains 237
5.9 Earth Fault and Phase Fault Protection 238
5.10 Combined Earth Fault and Phase Fault
Protective Scheme 240
Phase Fault Protective Scheme 240
Directional Earth Fault Relay 240
Static Overcurrent Relays 247
Numerical Overcurrent Relays 245
Exercises 246
Distance Protection 249
6.1 Introduction 249
6.2 Impedance Relay 250
6.3 Reactance Relay 258
64 MHO (Admittance or Angle Admitiance) Relay 261Contents vii
65 Angle Impedance (OHM) Relay 267
6.6 Input Quantities for Various Types of
Distance Relays 269
67 Sampling Comparator 270
6.8 Effect of are Resistance on the Performance of
Distance Relays 27/
6.9 Reach of Distance Relays 274
6.10 Effect of Power Surges (Power Swings) on the
Performance of Distance Relays 277
Effect of Line Length and Source Impedance on
Distance Relays 28/
6.12 Selection of Distance Relays 283
6.13 MHO Relay with Blinders 283
6.14 Quadrilateral Relay 284
6.15 Elliptical Relay 286
6.16 Restricted MHO Relay 287
6.17 Restricted Impedance Relay 289
6.18 Restricted Directional Relay 289
6.19 Restricted Reactance Relay 290
6.20 Some Other Distance Relay Characteristics 290
6.21 Swivelling Characteristics 293
6.22 Choice of Characteristics for Different Zones of
Protection 294
6.1
6.23 Compensation for Correct Distance Measurement 295
6.24 Reduction of Measuring Units 298
6.25 Switched Schemes 299
6.26 Auto-reclosing 301
Appendix 304
Exercises 305
7. Pilot Relaying Schemes 310
7.1 Introduction 310
7.2 Wire Pilot Protection 3/0
7.3 Carrier Current Protection 3/5
Exercises 326
8. Differential Protection 327
8.1 Introduction 327
8.2 Differential Relays 328
8.3 Simple (Basic) Differential Protection 329
8.4 Percentage or Biased Differential Relay 339viii Contents
85
86
Differential Protection of 3-Phase Circuits 346
Balanced (Opposed) Voltage Differential
Protection 346
Exercises 347
g. Rotating Machines Protection 349
91
9.2
Introduction 349
Protection of Generators 349
Exercises 361
10. Transformer and Buszone Protection 364
10.1 Introduction 364
10.2 Transformer Protection 364
10.3 Buszone Protection 375
10.4 Frame Leakage Protection 376
Exercises. 377
11. Numerical Protection 379
1
1
1
1
1
1
1
1
1
nt
1
11.
a
ll.
ll.
1.1
12
13
14
15
16
Iii;
18
19
10
all
12
mh
14
15
Introduction 379
Numerical Relay 38/
Data Acquisition System (DAS) 386
Numerical Relaying Algorithms 390
Mann-Morrison Technique 390
Differential Equation Technique 397
Discrete Fourier Transform Technique 393
Walsh—Hadamard Transform Technique 402
Rationalised Haar Transform Technique 4/6
Block Pulse Functions Technique 427
Wavelet Transform Technique 433
Removal of the de Offset 447
Numerical Overcurrent Protection 442
Numerical Distance Protection 444
Numerical Differential Protection 445
Exercises 450
12. Microprocessor-Based Numerical Protective Relays 452
1
1
1
1
1
21
2.2
24
25
26
Introduction 452
IC Elements and Circuits for Interfaces 453
AID Converter, Analog Multiplexer, S/H Circuit 457
Overcurrent Relays 471
Impedance Relay 475
Directional Relay 48/712.7
128
12.9
12.10
12.11
12.12
12.13
Contents ix
Reactance Relay 484
Generalised Mathematical Expression for
Distance Relays 487
Measurement of Rand X 489
Mho and Offset Mho Relays 492
Quadrilateral Relay 498
Generalised Interface for Distance Relays 501
Microprocessor Implementation of Digital Distance
Relaying Algorithms 502
Exercises 504
13. Artificial Intelligence Based Numerical Protection 506
13.1
13.2
13.3
13.4
13.5
13.6
13.7
13.8
13.9
13.12
13.13
Introduction 506
Artificial Neural Network (ANN) 507
Fuzzy Logic 5/8
Application of Artificial Intelligence to
Power System Protection 520
Application of ANN to Overcurrent Protection 522
Application of ANN to Transmission Line
Protection 522
Neural Network Based Directional Relay 523
ANN Modular Approach for Fault Detection,
Classification and Location 523
Wavelet Fuzzy Combined Approach for Fault
Classification 525
Application of ANN to Power Transformer
Protection 526
Power Transformer Protection Based on Neural
Network and Fuzzy Logic 528
Power Transformer Protection Based Upon Combined
Wavelet Transform and Neural Network 529
Application of ANN to Generator Protection 530
Exercises 537
14. Circuit Breakers 533
14.1
14.2
14.3
14.4
14.5
14.6
14.7
Introduction 533
Fault Clearing Time of a Circuit Breaker 534
Are Voltage 535
Are Interruption 535
Restriking Voltage and Recovery Voltage 537
Resistance Switching 541
Current Chopping 544x Contents
148
149
14.10
14.11
14.12
14.13
14.14
14.15
14.16
14.17
14.18
14.19
Interruption of Capacitive Current 545
Classification of Circuit Breakers 546
Air-Break Circuit Breakers 547
Oil Circuit Breakers 548
Air Blast Circuit Breakers 553
SF, Circuit Breakers 555
Vacuum Circuit Breakers 562
Operating Mechanism 564
Selection of Circuit Breakers 565
High Voltage DC (HVDC) Circuit Breakers 566
Rating of Circuit Breakers 567
Testing of Circuit Breakers 570
Exercises 575
15. Fuses 578
15.1
15.2
15.3
154
15.5
15.6
15.7
Introduction 578
Definitions 578
Fuse Characteristics 582
Types of Fuses 582
Applications of HRC Fuses 588
Selection of Fuses 588
Discrimination 589
Exercises 590
16. Protection Against Overvoltages 592
16.1
16.2
16.3
16.4
16.5
16.6
16.7
16.8
16.9
16.10
16.11
Causes of Overvoltages 592
Lightning Phenomena 593
Wave Shape of Voltage Due to Lightning 595
Overvoltages Due to Lightning 596
Klydonograph and Magnetic Link 598
Protection of Transmission Lines against Direct
Lightning Strokes 599
Protection of Stations and Sub-stations from
Direct Strokes 603
Protection Against Travelling Waves 605
Peterson Coil 6/5
Insulation Coordination 6/7
Basic Impulse Insulation Level (BIIL) 6/8
Exercises 619Contents xi
17. Modern Trends in Power System Protection 621
17.1
17.2
173
174
17.5
17.6
177
178
Introduction 62!
Gas Insulated Substation/Switchgear (GIS) 623
Frequency Relays and Load-shedding 628
Field Programmable Gate Arrays (FPGA) Based Relays 63/
Adaptive Protection 637
Integrated Protection and Control 639
Relay Reliability 640
Advantages of Fast Fault Clearing 641
Exercises 641
Appendix A: 8085 Assembly Language Programming 643
Appendix rthogonal and Orthonormal Functions 650
Appendix €: Gray-code to Binary Conversion 651
Appendix D: Kronecker (or Direct) Product of Matrices 652
Index 653pina annPreface to the Second Edition
The authors are thankful to the readers including teachers, students and engineers
who have given overwhelming response to the first edition of the book. The response
to the first edition of the book has been so encouraging that there have been about 40
reprints of this edition
The proper operation of a power system requires an efficient, reliable and fast-
acting protection scheme, which consists of protective relays and switching devices.
There has been continuous improvement in the design of relaying schemes. In order
to provide a foolproof protection system to the power system, innovative technology
is complementing the conventional protection system. With revolutionary changes in
the power system and tremendous developments in computer hardware technology,
numerical relays based on microprocessors or microcontrollers are fast replacing the
conventional protective relays.
Revision Rationale
Keeping in view the rapid technological advancement in power system protection,
we haye revised the present second edition of the book thoroughly and have added
many new chapters. This edition of the book will be very useful to undergraduate and
postgraduate students of electrical engineering, research scholars, students preparing
for professional examinations and practicing engincers engaged in system-protection
work. In revising this edition, we gratefully acknowledge the constructive sugges-
tions, critical comments and inspiration received from readers and well-wishers for
the improvement of the book.
New Additions
The present second edition of the book contains seven additional chapters, viz.,
Chapter 3 on Current and Voltage Transformers, Chapter 4 on Fault Analysis, Chapter
8 on Differential Protection, Chapter 9 on Rotating Machines Protection, Chapter
11 on Numerical Protection, Chapter 13 on Artificial Intelligence Based Numerical
Protection, and Chapter 17 on Moder Trends in Power System Protection. With the
addition of these new chapters, the present edition of the book has become consider-
ably up-to-date.
Chapter Organisation
Chapter 1 on Introduction now stands completely rewritten with addition of new sec-
tions on Performance of Protective Relays and Components of a Protection System
and many new relay terminologies.xiv Preface
Chapter 2 on Relay Construction and Operating Principles has also undergone a
thorough revision.
Chapter 3, a new chapter on Current and Voltage Transformers, describes the
construction and operating principles of various types of current and voltage trans-
formers (transducers) required in protection systems.
Chapter 4, a new chapter on Fault Analysis, discusses the per unit system, sym-
metrical fault analysis, symmetrical components, unsymmetrical fault analysis and
grounding. In order to ensure adequate protection, the student must clearly under-
stand the conditions existing ona power system during faults. These abnormal condi-
tions provide the discriminating means for relay operation. Hence, fault analysis is
very essential for the design of a suitable protection system.
Chapter 5 on Overcurrent Protection is the revised and renumbered Chapter 3
of the first edition. This chapter deals with overcurrent protection detailing electro-
magnetic and static overcurrent relays, directional relays, and overcurrent protective
schemes.
Similarly, Chapter 6 on Distance Protection is the revised and renumbered
Chapter 4 of the first edition. It discusses different types of electromagnetic and static
distance relays, arc resistance and power swings on performance of distance relays,
realization of different types of operating characteristics of distance relays and auto-
reclosing.
Chapter 7 on Pilot Relaying Schemes is the same as Chapter 5 of first edition. It
deals with pilot protection, wire pilot relaying and carrier pilot relaying.
Chapter 8, a new chapter on Differential Protection, discusses construction,
operating principles and performance of various differential relays for differential
protection,
Chapter 9, a new chapter on Rotating Machines Protection, deals with protection
of generators and motors. We developed it by splitting Chapter 6 of the first edi-
tion and adding motor protection. We then used the remaining parts of Chapter 6 to
develop Chapter 10, a new chapter on Transformer and Bus Zone Protection.
Chapter 11, a new chapter on Numerical Protection, discusses the numerical
relay, data acquisition system, numerical relaying algorithms, numerical overcurrent
protection, numerical distance protection and numerical differential protection of
generator and power transformer. Numerical relay, which is the main component of
the numerical protection scheme, is the latest development in the area of protection.
The basis of this topic is numerical (digital) devices, e.g., microprocessors, micro-
controllers, Digital Signal Processors (DSPs), etc., developed because of tremendous
advancement in VLSI and computer hardware technology.
Chapter 12, a new chapter on Microprocessor Based Numerical Protective
Relays, comprises some portions of Chapters 7 and 8 of the first edition and some
new additions. It describes microprocessor-based overcurrent and distance relays and
digital filtering algorithms for removal of de offset from relaying signals and compu-
tation of R and X of a transmission line.
Chapter 13, a new chapter on Artificial Intelligence Based Numerical Protection,
deals with application of Artificial Neural Networks (ANNs) and Fuzzy Logic to
numerical protection of power system.Preface xv
Chapter 14 on Circuit Breakers is the thoroughly revised and renumbered Chapter
9 of the first edition. It covers circuit breakers explaining the principle of circuit
interruption and different types of circuit breakers.
Chapter 15 on Fuses is the same as Chapter 10 of the first edition. It describes the
construction and operating principle of different types of fuses and gives the defini-
tions of different terminologies related to a fuse. Again, Chapter 16 is the same as
Chapter 11 of the first edition, and is on Protection Against Overvoltages. Chapter
17, a new chapter on Modern Trends in Power System Protection, discusses the mod-
ern topics of power system protection such as Gas Insulated Substation (GIS), fre-
quency relays and loadshedding, Field Programmable Gate Arrays (FPGA) based
relays, adaptive protection, integrated protection and control, Supervisory Control
And Data Acquisition (SCADA), travelling wave relay, etc.
Acknowledgements
We owe a special note of thanks to Mr. Harshit Nath who helped us a lot in the prepa-
ration of the manuscript of this edition. We also express our gratitude to Ms. Amrita
Sinha and Ms. Kiran Srivastava for their constructive suggestions and cooperation
during the manuscript-preparation stage of this edition. At this stage, we would also
like to thank the many reviewers who took out time from their busy schedules and
sent us their suggestions, all of which wenta long way in helping us revise the book.
We mention their names below.
Zakir Hussain National Institute of Technology Hamirpur, Himachal
Pradesh
Rakesh Kumar Global Institute of Technology, Greater Noida, Uttar
Pradesh
Sardindu Ghosh National Institute of Technology Rourkela, Orissa
RC Jha Birla Institute of Technology Mesra, Ranchi, Jharkhand
V B Babaria Lalbhai Dalpatbhai College of Engineering, Ahmadabad,
Gujarat
R Senthil Kumar = Bannari Amman Institute of Technology, Sathyamangalam,
Erode, Tamil Nadu
K Lakshmi K S Rangasamy College of Engineering, Tiruchengode,
Tamil Nadu
S P Rajkumar Sri Ramakrishna Engineering College, Coimbatore, Tamil
Nadu
CV K Bhanu Gayatri Vidya Parishad College of Engineering,
Vishakhapatnam, Andhra Pradesh
M Narendra Kumar Guru Nanak Engineering College, Hyderabad, Andhra
Pradesh
S Ram Mohan Rao — College of Engineering, Andhra University, Vishakhapatmam,
Andhra Pradesh
We wish to convey our feelings of indebtedness to our colleagues and students for
the encouragement and useful suggestions they gave us while we were revising thexvi Preface
book. Finally, we state our heartfelt gratitude to our respective families for the love,
patience and inspiration, which they are never short of showering on us.
We welcome constructive criticism and suggestions from all concerned for further
improvement of the future editions of the book. Please feel free to email your views
at the publisher’s website mentioned below.
Badri Ram
DN Vishwakarma
Feedback
We invite comments and suggestions from all the readers. You may e-mail your feed-
back to tmh.elefeedback @ gmail.com (kindly mention the title and author name in
the subject line). Also, please report any piracy of the book spotted by you.' 1.1 NEED FOR PROTECTIVE SYSTEMS '
An electrical power system consists of generators, transformers, transmission and
distribution lines, etc. Short cireuits and other abnormal conditions often occur ona
power system, The heavy current associated with short circuits is likely to cause dam-
age to equipment if suitable protective relays and circuit breakers are not provided for
the protection of each section of the power system. Short circuits are usually called
faults by power engineers. Strictly speaking, the term ‘fault’ simply means a ‘defect’.
Some defects, other than short circuits, are also termed as faults. For example, the
failure of conducting path due to a break in a conductor is a type of fault.
If a fault occurs in an element of a power system, an automatic protective device
is needed to isolate the faulty element as quickly as possible to keep the healthy sec-
tion of the system in normal operation. The fault must be cleared within a fraction of
a second. If a short circuit persists on a system for a longer, it may cause damage to
some important sections of the system. A heavy short circuit current may cause a fire.
It may spread in the system and damage a part of it. The system voltage may reduce
to a low level and individual generators in a power station or groups of generators
in different power stations may lose synchronism. Thus, an uncleared heavy short
circuit may cause the total failure of the system.
A protective system includes circuit breakers, transducers (CTs and VTs), and
protective relays to isolate the faulty section of the power system from the healthy
sections. A circuit breaker can disconnect the faulty element of the system when it
is called upon to do so by the protective relay. Transducers (CTs and VTs) are used
to reduce currents and voltages to lower values and to isolate protective relays from
the high voltages of the power system. The function of a protective relay is to detect
and locate a fault and issue a command to the circuit breaker to disconnect the faulty
element. It is a device which senses abnormal conditions on a power system by con-
stantly monitoring electrical quantities of the systems, which differ under normal and
abnormal conditions. The basic electrical quantities which are likely to change dur-
ing abnormal conditions are current, voltage, phase-angle (direction) and frequency.
Protective relays utilise one or more of these quantities to detect abnormal conditions
on a power system.
Protection is needed not only against short circuits but also against any other
abnormal conditions which may arise on a power system. A few examples of other
abnormal conditions are overspeed of generators and motors, overvoltage, under-2 Power System Protection and Switchgear
frequency, loss of excitation, overheating of stator and rotor of an alternator etc.
Protective relays are also provided to detect such abnormal conditions and issue
alarm signals to alert operators or trip circuit breaker.
A protective relay does not anticipate or prevent the occurrence of a fault, rather
it takes action only after a fault has occurred. However, one exception to this is
the Buchholz relay, a gas actuated relay, which is used for the protection of power
transformers. Sometimes, a slow breakdown of insulation due to a minor arc may
take place in a transformer, resulting in the generation of heat and decomposition of
the transformer’s oil and solid insulation. Such a condition produces a gas which is
collected in a gas chamber of the Buchholz relay. When a specified amount of gas is
accumulated, the Buchholz relay operates an alarm. This gives an early warning of
incipient faults. The transformer is taken out of service for repair before the incipient
fault grows into a serious one. Thus, the occurrence of a major fault is prevented. If
the gas evolves rapidly, the Buchholz relay trips the circuit breaker instantly.
The cost of the protective equipment generally works out to be about 5% of the
total cost of the system.
1.2 NATURE AND CAUSES OF FAULTS
Faults are caused either by insulation failures or by conducting path failures. The
failure of insulation results in short circuits which are very harmful as they may
damage some equipment of the power system. Most of the faults on transmission and
distribution lines are caused by overvoltages due to lightning or switching surges, or
by external conducting objects falling on overhead lines. Overvoltages due to light-
ing or switching surges cause flashover on the surface of insulators resulting in short
circuits, Sometimes, insulators get punctured or break. Sometimes, certain foreign
particles, such as fine cement dust or soot in industrial areas or salt in coastal areas
or any dirt in general accumulates on the surface of string and pin insulators. This
reduces their insulation strength and causes flashovers. Short circuits are also caused
by tree branches or other conducting objects falling on the overhead lines.
Birds also may cause faults on overhead lines if their bodies touch one of the
phases and the earth wire (or the metallic supporting structure which is at earth
potential). If the conductors are broken, there is a failure of the conducting path and
ircuited. If the broken conductor falls to the ground,
it results in a short circuit. Joint failures on cables or overhead lines are also a cause
of failure of the conducting path. The opening of one or two of the three phases
makes the system unbalanced. Unbalanced currents flowing in rotating machines
set up harmonics, thereby heating the machines in short periods of time. Therefore,
unbalancing of the lines is not allowed in the normal operation of a power system.
Other causes of faults on overhead lines are: direct lightning strokes, aircraft, snakes,
ice and snow loading, abnormal loading, storms, earthquakes, creepers, etc. In the
case of cables, transformers, generators and other equipment, the causes of faults are:
the conductor becomes oper
failure of the solid insulation due to aging, heat, moisture or overvoltage, mechanical
damage, accidental contact with earth or earthed screens, flashover due to overvolt-
ages, etc.Introduction 3
Sometimes, circuit breakers may trip due to errors in the switching operation, test-
ing or maintenance work, wrong connections, defects in protective devices, etc.
Certain faults occur due to the poor quality of system components or because
of a faulty system design. Hence, the occurrence of such faults can be reduced by
improving the system design, by using components and materials of good quality and
by better operation and maintenance.
1.3. TYPES OF FAULTS
t
Two broad classifications of faults are
(i) Symmetrical faults
(ii) Unsymmetrical faults
13.1 Symmetrical Faults
A three-phase (3-9) fault is called a symmetrical type of fault. In a 3-6 fault, all the
three phases are short circuited. There may be two situations—all the three phases
may be short circuited to the ground or they may be short-circuited without involving
the ground. A 3-@ short circuit is generally treated as a standard fault to determine
the system fault level.
1.3.2. Unsymmetrical Faults
Single-phase to ground, two-phase to ground, phase-to-phase short circuits; single-
phase open circuit and two-phase open circuit are unsymmetrical types of faults.
Single-phase to Ground (L-G) Fault
A short circuit between any one of the phase conductors and earth is called a sin-
gle phase to ground fault. It may be due to the failure of the insulation between a
phase conductor and the earth, or due to phase conductor breaking and falling to the
ground.
Two-phase to Ground (2L-G) Fault
A short circuit between any two phases and the earth is called a double line to ground
or a two-phase to ground fault.
Phase-to-Phase (L-L) Fault
A short circuit between any two phases is called a line to line or phase-to-phase
fault.
Open-circuited Phases
This type of fault is caused by a break in the conducting path. Such faults occur when
One or more phase conductors break or a cable joint or a joint on the overhead lines
fails. Such situations may also arise when circuit breakers or isolators open but fail
to close one or more phases. Due to the opening of one or two phases, unbalanced
currents flow in the system, thereby heating rotating machines. Protective schemes
must be provided to deal with such abnormal situations.4 Power System Protection and Switchgear
Winding Faults
All types of faults discussed above also occur on the alternator, motor and trans-
former windings. In addition to these types of faults, there is one more type of fault,
namely the short circuiting of turns which occurs on machine windings.
1.3.3. Simultaneous Faults
Two or more faults occurring simultaneously on a system are known as multiple or
simultaneous faults. In simultaneous faults, the same or different types of faults may
occur at the same or different points of the system. An example of two different types
of faults occurring at the same point is a single line to ground fault on one phase and
breaking of the conductor of another phase, both simultaneously present at the same
point. The simultaneous presence of an L-G fault at one point and a second L-G fault
on another phase at some other point is an example of two faults of the same type at
two different points. If these two L-G faults are on the same section of the line, they
are treated as a double line to ground fault. If they occur in different line sections,
it is known as a cross-country earth fault. Cross-country faults are common on sys-
tems grounded through high impedance or Peterson coil but they are rare on solidly
grounded systems.
i 1.4 EFFECTS OF FAULTS i
The most dangerous type of fault is a short circuit as it may have the following effects
on a power system, if it remains uncleared.
()) Heavy short circuit current may cause damage to equipment or any other
element of the system due to overheating and high mechanical forces set up
due to heavy current.
(ii) Ares associated with short circuits may cause fire hazards. Such fires, result-
ing from arcing, may destroy the faulty element of the system. There is also
a possibility of the fire spreading to other parts of the system if the fault is
not isolated quickly.
(iii) There may be reduction in the supply voltage of the healthy feeders, resulting
in the loss of industrial loads.
(iv) Short circuits may cause the unbalancing of supply voltages and currents,
thereby heating rotating machines.
(v) There may be a loss of system stability. Individual generators in a power
station may lose synchronism, resulting in a complete shutdown of the
system. Loss of stability of interconnected systems may also result. Subsys-
tems may maintain supply for their individual zones but load shedding would
have to be resorted in the sub-system which was receiving power from the
other subsystem before the occurrence of the fault.
(vi) The above faults may cause an interruption of supply to consumers, thereby
causing a loss of revenue.
High grade, high speed, reliable protective devices are the essential requirements
of a power system to minimise the effects of faults and other abnormalities.Introduction 5
i 1.5 FAULT STATISTICS i
For the design and application of protective scheme, it is very useful to have an
idea of the frequency of occurrence of faults on various elements of power system.
Usually the power stations are situated far away from the load centres, resulting
in hundreds of kilometers’ length of overhead lines being exposed to atmospheric
conditions. The chances of faults occurring due to storms, falling of external objects
on the lines, flashovers resulting from dirt deposits on insulators, etc., are greater
for overhead lines than for other parts of the power system. Table 1.1 gives an
approximate idea of the fault statistics.
Table 1.1 Percentage Distribution of Faults in Various Elements of a Power
system
Element % of Total Faults
Overhead Lines 50
Underground Cables 9
Transformers 10
Generators
Switchgears 12
CTs, VTs, Relays
Control Equipment, etc. 12
From Table 1.1, it is evident that 50% of the total faults occur on overhead lines.
Hence it is overhead lines that require more attention while planning and designing
protective schemes for a power system.
Table 1.2 shows the frequency of occurrence of different types of faults (mainly
the different types of short circuits) on overhead lines. From the table it is evident that
the frequency of line to ground faults is more than any other type of fault, and hence
the protection against L-G fault requires greater attention in planning and design of
protective schemes for overhead lines.
Table 1.2. Frequency of Occurrence of Different Types of Faults on Overhead Lines
Types of Faults Fault Symbol % of Total Faults
Line to Ground LG 85
Line to Line LL 8
Double Line to Ground 2L-G 5
Three Phase 3-6 2
In the case of cables, 50% of the faults occur in cables and 50% at end junctions.
Cable faults are usually of a permanent nature and hence, automatic reclosures are
not recommended for cables.6 Power System Protection and Switchgear
1.6 EVOLUTION OF PROTECTIVE RELAYS
In the very early days of the power industry, small generators were used to supply
local loads and fuses were the automatic devices to isolate the faulty equipment.
They were effective and their performance was quite satisfactory for small systems.
However, they suffered from the disadvantage of requiring replacement before the
supply could be restored. For important lines, frequent interruption in power supply
is undesirable. This inconvenience was overcome with the introduction of circuit
breakers and protective relays. Attracted armatured-type electromagnetic relays were
first introduced. They were fast, simple and economical. As auxiliary relays their use
will continue even in future, due to their simplicity and low cost. This type of relays
operate through an armature which is attracted to an electromagnet or thought a
plunger drawn into a solenoid. Plunger-type electromagnetic relays formed instanta-
neous units for detecting overcurrent or over-voltage conditions. Attracted armature-
type electromagnetic relays work on both ac and de. Later on, induction-type elec-
tromagnetic relays were developed. These relays use the electromagnetic induction
principle for their operation and hence work on ac only. Since both attracted armature
and induction-type electromagnetic relays operate by mechanical forces generated
on moving parts due to electromagnetic forces created by the input quantities, these
relays were called electromechanical relays. Induction disc-type inverse time-current
relays were developed in the early 1920s to meet the selectivity requirement. They
were used for overcurrent protection. For directional and distance relays, induction-
cup-type units were widely used throughout the world. An induction-cup-type unit
was fast and accurate due to its higher torque/inertia ratio. For greater sensitivity and
accuracy, polarised de relays are being used since 1939.
Attracted armature-type balanced-beam relays provided differential protection,
distance protection as well as low burden overcurrent units. These relays operated
when the magnitude of an operating signal was larger than the magnitude of the
restraining signal. These relays were classified as amplitude comparators.
Single-input induction-type relays provided operations with time delays. Two-
input induction type relays provided directional protection. Two- and three-input
induction-type relays also provided distance protection. The operation of these relays
was dependant on the phase displacement between the applied electrical inputs.
These relays were classified as phase comparators.
In 1947, rectifier bridge-type comparators were developed in Norway and
Germany. Polarised de relays, energised from rectifier bridge comparators, chal-
lenged the position of induction-cup-type relays. They are widely used for the reali-
sation of distance relay characteristics.
Electronic relays using vacuum tubes first appeared in the literature in 1928 and
continued up to 1956. They were not accepted because of their complexity, short life
of vacuum tubes and incorrect operation under transient conditions. But electronic
valves were used in carrier equipment. There was automatic checking of the carrier
channel. An alarm was sounded if any tube became defective, and it was replaced
immediately.Introduction 7
Magnetic amplifiers were also used in protective relays in the past. A magnetic
amplifier consists of a transformer and a separate de winding. As the transformer
action is controlled by the de winding, the device is also known as transductor. This
type of relay is rugged but slow in action. At present, such relays are not used.
Hall crystals were also used to construct phase comparators. Because of their low
output and high-temperature errors, such relays have not been widely adopted except
in Russian countries.
The first transistorised relay was developed in 1949, soon after the innova-
tion of the transistor. Various kinds of static relays using solid-state devices were
developed in the fifties. Multi-input comparators giving quadrilateral characteristics
were developed in the sixties. Static relays possess the advantages of low burden on
the CT and VT, fast operation, absence of mechanical inertia and contact troubles,
long life and less maintenance. As static relays proved to be superior to electrome-
chanical relays, they were used for the protection of important lines, power stations
and sub-stations. But they did not replace electromechanical relays. Static relays were
treated as an addition to the family of relays. In most static relays, the output or slave
relay isa polarised de relay which is an electromechanical relay. This can be replaced
by a thyristor circuit, but it is used because of its low cost. Electromechanical rela
have continued to be used because of their simplicity and low cost. Their mainte-
nance can be done by less qualified personnel, whereas the maintenance and repair
of static relays requires personnel trained in solid-state devices. Static relays using
digital techniques have also been developed.
Static relays appeared to be the technology poised to replace the electromechani-
cal counterparts in the late sixties when researchers ventured into the use of comput-
ers for power system protection. Their attempts and the advances in the Very Large
Scale Integrated (VLSI) technology and software techniques in the seventies led to
the development of microprocessor-based relays that were first offered as commer-
cial devices in 1979. Early designs of these relays used the fundamental approaches
that were previously used in the electromechanical and static relays.
In spite of the developments of complex algorithms for implementing protection
functions, the microprocessor-based relays marketed in the eighties did not incor-
porate them. These relays performed basic functions, took advantage of the hybrid
analog and digital techniques, and offered a good economical solution. At present,
in microprocessor-based relays, different relaying algorithms are used to process the
acquired information. Microprocessor/Microntroller-based relays are called numeri-
cal relays specifically if they calculate the algorithm numerically.
The modern power networks which have grown both in size and complexity
require fast accurate and reliable protective schemes to protect major equipment
and to maintain system stability. Increasing interest is being shown in the use of
on-line digital computers for protection. The concept of numerical protection
employing computers which shows much promise in providing improved perfor-
mance has evolved during the past three decades. In the beginning, the numerical
protection (also known as digital protection) philosophy was to use a large computer
system for the total protection of the power system. This protection system proved
to be very costly and required large space. If a computer is required to perform other8 Power System Protection and Switchgear
control functions in addition to protection, it can prove to be economical. With the
tremendous developments in VLSI and computer hardware technology, microproces-
sors that appeared in the seventies have evolved and made remarkable progress in
recent years, The latest fascinating innovation in the field of computer technology
is the development of microprocessors, microcontrollers, Digital Signal Processors
(DSPs) and Field Programmable Gate Arrays (FPGAs) which are making in-roads in
every activity of mankind. With the development of fast, economical, powerful and
sophisticated microprocessors, microcontrollers, DSPs and FPGAs, there is a grow-
ing tend to develop numerical relays based on these devices.
The conventional relays of electromechanical and static types had no significant
drawbacks in their protection functions, but the additional features offered by micro-
processor technologies encouraged the evolution of relays that introduced many
changes to the power industry. Economics and additionally, functionality were prob-
ably the main factors that forced the power industry to accept and cope with the
changes brought by microprocessor/microcontroller-based numerical relays.
Multifunction numerical relays were introduced in the market in the late eight-
ies. These devices reduced the product and installation costs drastically. This trend
has continued until now and has converted microprocessor/microcontroller based
numerical relays to powerful tools in the modern substations.
The inherent advantage of microprocessor/microcontroller-based protective
schemes, over the existing static relays with one or very limited range of applica-
tions, is their flexibility, The application of microprocessors and microcontrollers to
protective relays also result in the availability of faster, more accurate and reliable
relaying units. A microprocessor or a microcontroller increases the flexibility of a
relay due to its programmable approach. It provides protection at low cost and com-
petes with conventional relays. A number of relaying characteristics can be realised
using the same interface. Using a multiplexer, the microprocessor/microcontroller
can obtain the required input signals for the realisation of a particular relaying char-
acteristic. Different programs can be used for different characteristics. Individual
types and number of relaying units are reduced to a great extent, resulting in a very
compact protective scheme. Field tests have demonstrated their feasibility and some
schemes are under investigation. A number of schemes have been put into service
and their performances have been found to be satisfactory. Microprocessor/micro-
controller-based numerical protective schemes are being widely used in the field.
At present, many trends are emerging. These include common hardware plat-
forms, configuring the software to perform different functions, integrating protection
with substation control and substituting cables carrying voltages and currents with
optical fibre cables carrying signals in the form of polarized light.
On the software side, Artificial Intelligence (Al) techniques, such as Artificial
Neural Networks (ANNs) and Fuzzy Logic Systems have attracted the attention of
researchers and protection engineers and they are being applied to power system
protection. ANN and Fuzzy Logic based intelligent numerical relays for overcurrent
protection, distance protection of transmission lines and differential protection of
transformers and generators are presently under active research and development
stage. Adaptive protection is also being applied to protection practices. RecentIntroduction 9
work in this area includes feedback systems in which relays continuously monitor
the operating state of the power system and automatically reconfigure themselves
for providing optimal protection.
' 1.7__ ZONES OF PROTECTION '
A power system contains generators, transformers, bus bars, transmission and distri-
bution lines, etc, There is a separate protective scheme for each piece of equipment
or element of the power system, such as generator protection, transformer protection,
transmission line protection, bus bar protection, etc. Thus, a power system is divided
into a number of zones for protection. A protective zone covers One or at the most
two elements of a power system. The protective zones are planned in such a way
that the entire power system is collectively covered by them, and thus, no part of the
system is left unprotected. The various protective zones of a typical power system are
shown in Fig. 1.1. Adjacent protective zones must overlap each other, failing which
a fault on the boundary of the zones may not lie in any of the zones (this may be
due to errors in the measurement of actuating quantities, etc.), and hence no circuit
breaker would trip. Thus, the overlapping between the adjacent zones is unavoidable.
If a fault occurs in the overlapping zone in a properly protected scheme, more circuit
breakers than the minimum necessary to isolate the faulty element of the system
would trip. A relatively low extent of overlap reduces the probability of faults in this
region and consequently, tripping of too many breakers does not occur frequently.
HV Switchgear protection
Tete? sensor protection
'— EHV Switchgear protection
EHV Switchgear protection
Fig. 1.1 Zones of protection10 Power System Protection and Switchgear
1.8 PRIMARY AND BACK-UP PROTECTION
It has already been explained that a power system is divided into various zones for
its protection. There is a suitable protective scheme for each zone. If a fault occurs
in a particular zone, it is the duty of the primary relays of that zone to isolate the
faulty element. The primary relay is the first line of defense. If due to any reason, the
primary relay fails to operate, there is a back-up protective scheme to clear the fault
as a second line of defence.
The causes of failures of protective scheme may be due to the failure of various
elements, as mentioned in Table 1.3. The probability of failures is shown against each
item.
The reliability of protective scheme should at least be 95%. With proper design,
installation and maintenance of the relays, circuit breakers, trip mechanisms, ac and
de wiring, etc. a very high degree of reliability can be achieved.
The back-up relays are made independent of those factors which might cause
primary relays to fail. A back-up relay operates after a time delay to give the primary
relay sufficient time to operate, When a back-up relay operates, a larger part of the
power system is disconnected from the power source, but this is unavoidable. As far
as possible, a back-up relay should be placed at a different station. Sometimes, a
local back-up is also used. It should be located in such a way that it does not employ
components (VT, CT, measuring unit, etc.) common with the primary relays which
are to be backed up. There are three types of back-up relays:
(i) Remote back-up
(ii) Relay back-up
(iii) Breaker back-up
Table 1.3 Percentage failure rate of various equipment
Name of Equipment % of Total Failures
Relays 44
Circuit breaker interrupters 14
AC wiring 12
Breaker trip mechanisms 8
Current transformers
DC wiring
VE
Breaker auxiliary switches
Breaker tripcoils
Hs wwwur
DC supply
1.8.1 Remote Back-up
When back-up relays are located at a neighbouring station, they back-up the entire
primary protective scheme which includes the relay, circuit breaker, VT, CT and other
elements, in case of a failure of the primary protective scheme. It is the cheapest andIntroduction 14
the simplest form of back-up protection and is a widely used back-up protection for
transmission lines. It is most desirable because of the fact that it will not fail due to
the factors causing the failure of the primary protection,
1.8.2. Relay Back-up
This is a kind of a local back-up in which an additional relay is provided for back-up
protection. It trips the same circuit breaker if the primary relay fails and this opera-
tion takes place without delay. Though such a back-up is costly, it can be recom-
mended where a remote back-up is not possible. For back-up relays, principles of
operation that are different from those of the primary protection as desirable. They
should be supplied from separate current and potential transformers.
1.8.3 Breaker Back-up
‘This is also a kind of a local back-up. This type of a back-up is necessary for a bus
bar system where a number of circuit breakers are connected to it. When a protec-
tive relay operates in response to a fault but the circuit breaker fails to trip, the fault
is treated as a bus bar fault. In such a situation, it becomes necessary that all other
circuit breakers on that bus bar should trip. After a time-delay, the main relay closes
the contact of a back-up relay which trips all other circuit breakers on the bus if the
proper breaker does not trip within a specified time after its trip coil is energised.
' 1.9 ESSENTIAL QUALITIES OF PROTECTION
The basic requirements of a protective system are as follows:
(i) Selectivity or discrimination
(ii) Reliability
(iii) Sensitivity
(iv) Stability
(v) Fast operation
1.9.1 Selectivity or Discrimination
Selectivity, is the quality of protective relay by which it is able to discriminate
between a fault in the protected section and the normal condition. Also, it should be
able to distinguish whether a fault lies within its zone of protection or outside the
zone. Sometimes, this quality of the relay is also called discrimination. When a fault
occurs on a power system, only the faulty part of the system should be isolated. No
healthy part of the system should be deprived of electric supply and hence should be
left intact. The relay should also be able to discriminate between a fault and transient
conditions like power surges or inrush of a transformer’s magnetising current. The
magnetising current of a large transformer is comparable to a fault current, which
may be 5 to 7 times the full load current. When generators of two interconnected
power plants lose synchronism because of disturbances, heavy currents flow through
the equipment and lines. This condition is like a short circuit. The flow of heavy cur-
rents is known as a power surge. The protective relay should be able to distinguish
between a fault or power surge either by its inherent characteristic or with the help of12 Power System Protection and Switchgear
an auxiliary relay. Thus, we see that a protective relay must be able to discriminate
between those conditions for which instantaneous tripping is required and those for
which no operation or a time-delay operation is required.
1.9.2 Reliability
A protective system must operate reliably when a fault occurs in its zone of protection.
The failure of a protective system may be due to the failure of any one or more ele-
ments of the protective system. Its important elements are the protective relay, circuit
breaker, VT, CT, wiring, battery, etc. To achieve a high degree of reliability, greater
attention should be given to the design, installation, maintenance and testing of the
various elements of the protective system. Robustness and simplicity of the relaying
equipment also contribute to reliability. The contact pressure, the contact material of
the relay, and the prevention of contact contamination are also very important from
the reliability point of view. A typical value of reliability of a protective scheme is
95%.
1.9.3 Sensitivity
A protective relay should operate when the magnitude of the current exceeds the
preset value. This value is called the pick-up current. The relay should not operate
when the current is below its pick-up value. A relay should be sufficiently sensitive
to operate when the operating current just exceeds its pick-up value.
1.9.4 Stability
A protective system should remain stable even when a large current is flowing through
its protective zone due to an external fault, which does not lie in its zone. The con-
cerned circuit breaker is supposed to clear the fault, But the protective system will
not wait indefinitely if the protective scheme of the zone in which fault has occurred
fails to operate. After a preset delay the relay will operate to trip the circuit breaker.
1.9.5 Fast Operation
A protective system should be fast enough to isolate the faulty element of the system
as quickly as possible to minimise damage to the equipment and to maintain the
system stability. For a modern power system, the stability criterion is very important
and hence, the operating time of the protective system should not exceed the criti-
cal clearing time to avoid the loss of synchronism, Other points under consideration
for quick operation are protection of the equipment from burning due to heavy fault
currents, interruption of supply to consumers and the fall in system voltage which
may result in the loss of industrial loads. The operating time of a protective relay is
usually one cycle. Half-cycle relays are also available. For distribution systems the
operating time may be more than one cycle.
t 1.10 PERFORMANCE OF PROTECTIVE RELAYS
When a fault occurs in a particular zone of the power system, the primary relays
of that zone are expected to operate and initiate isolation of the faulty element.
However, back-up relays surrounding that area are also alerted by the fault andIntroduction 13
begin to operate. They do not initiate tripping if the primary relays operate correctly.
Information regarding operation of these back-up relays is not available when they
do not trip. The back-up relay operates, if due to any reason the primary relay fails
to operate. Though several primary relays are employed in many protection sys-
tems, but frequently only one of the relays actually initiates tripping of the circuit
breaker. There may be no direct evidence regarding the other relays being in a correct
operating mode.
The performance of the protective relay is documented by those relays that
provide direct or specific evidence of operation. Relay performance is generally clas-
sified as
(i) Correct operation
(ii) Incorrect operation
(iv) No conclusion
1.10.1 Correct Operation
Correct operation of the relay can be either wanted or unwanted. The correct opera-
tion gives indication about (i) correct operation of atleast one of the primary relays,
(ii) operation of none of the back-up relays to trip for the fault, and (iii) proper isola-
tion of the trouble area in the expected time.
Almost all relay operations are corrected and wanted, i.e., the operation is as per
plan and programme. There are the few cases of the correct but unwanted operation.
If all relays and associated equipment perform correctly when their operation is not
desired or anticipated, it is called “correct but unwanted operation.”
1.10.2 Incorrect Operation
A failure, a malfunction, or an unplanned or unanticipated operation of the protec-
tive system results in incorrect operation of the relay. The incorrect operation of the
relay can cause either incorrect isolation of an unfaulted area, or a failure to isolate
a faulted area, The reasons for incorrect operation can be any one or a combination
of (i) misapplication of relays, (ii) incorrect settings, (iii) personnel errors, and (iv)
equipment malfunctions. Equipment that can cause an incorrect operation includes
CTs, VTS, relays, breakers, cable and wiring, pilot channels, station batteries, etc.
1.10.3. No Conclusion
When one or more relays have or appear to have operated, such as the tripping of the
circuit breaker, but no cause of operation can be found, it is the case of ‘no conclu-
sion’. Neither any evidence of a power system fault or trouble, nor apparent failure
of the equipment, causes and extremely frustrating situation. Thus the cases of no
conclusion involves considerable concern and thorough investigation. It is suspected
that many of the cases of ‘no conclusion’ may be the result of personnel involvement
which is not reported. Modern oscillographs and data-recording equipment which
are being used nowaday in many power systems often provide direct evidence or
clues regarding the problem, as well as indicating possibilities that could not have
occurred,14 Power System Protection and Switchgear
1.11 CLASSIFICATION OF PROTECTIVE RELAYS
Protective relays can be classified in various ways depending on the technology used
for their construction, their speed of operation, their generation of development,
function, etc., and will be discussed in more details in the following chapters.
1.41.1 Classification of Protective Relays Based on Technology
Protective relays can be broadly classified into the following three categories, depend-
ing on the technology they use for their construction and operation.
(i) Electromechanical relays
(ii) Static relays
(iii) Numerical relays
Electromechanical Relays
Electromechanical relays are further classified into two categories, i.e., (i) electro-
magnetic relays, and (ii) thermal relays. Electromagnetic relays work on the princi-
ple of either electromagnetic attraction or electromagnetic induction. Thermal relays
utilise the electrothermal effect of the actuating current for their operation.
First of all, electromagnetic relays working on the principle of electromagnetic
attraction were developed. These relays were called attracted armature-type electro-
magnetic relays. This type of relay operates through an armature which is attracted
to an electromagnet or through a plunger drawn into a solenoid. Plunger type elec-
tromagnetic relays are used for instantaneous units for detecting over current or over-
voltage conditions.
Attracted armature-type electromagnetic relays are the simplest type which
respond to ac as well as de. Initially attracted armature-type relays were called elec-
tromagnetic relays. Later on, induction type electromagnetic relays were developed.
These relays use electromagnetic induction principle for their operation, and hence
work with ac quantities only. Electromagnetic relays contain an electromagnet (or a
permanent magnet) and a moving part. When the actuating quantity exceeds a cer-
tain predetermined value, an operating torque is developed which is applied on the
moving part. This causes the moving part to travel and to finally close a contact to
energise the trip coil of the circuit breaker.
Since both attracted armature and induction type electromagnetic relays oper-
ate by mechanical forces generated on moving parts due to electromagnetic forces
created by the input quantities, these relays were called electromechanical relays.
The term ‘electromechanical relays’ has been used to designate all the electro-
magnetic relays which use cither electromagnetic attraction or electromagnetic
induction principle for their operation and thermal relays which operate as a result of
electrothermic forces created by the input quantities. Sometimes both the terms, L.e.,
electromagnetic relays and electromechanical relays are used in parallel.
Static Relays
Static relays contain electronic circuitry which may include transistors, ICs, diodes
and other electronic components. There is a comparator circuit in the relay, which
compares two or more currents or voltages and gives an output which is applied toIntroduction 15
either a slave relay or a thyristor circuit. The slave relay is an electromagnetic relay
which finally closes the contact. A static relay containing a slave relay is a semi-static
relay. A relay using a thyristor circuit is a wholly static relay. Static relays possess
the advantages of having low burden on the CT and VT, fast operation, absence of
mechanical inertia and contact trouble, long life and less maintenance. Static relays
have proved to be superior to electromechanical relays and they are being used for
the protection of important lines, power stations and sub-stations. Yet they have not
completely replaced electromechanical relays. Static relays are treated as an addi-
tion to the family of relays. Electromechanical relays continue to be in use because
of their simplicity and low cost. Their maintenance can be done by less qualified
personnel, whereas the maintenance and repair of static relays requires personnel
tained in solid state devices.
Numerical Relays
Numerical relays are the latest development in this area, These relays acquire the
sequential samples of the ac quantities in numeric (digital) data form through the
data acquisition system, and process the data numerically using an algorithm to cal-
culate the fault discriminants and make trip decisions. Numerical relays have been
developed because of tremendous advancement in VLSI and computer hardware
technology. They are based on numerical (digital) devices, ¢.g., microprocessors,
microcontrollers, Digital Signal Processors (DSPs), etc. At present microprocessor/
microcontroller-based numerical relays are widely used. These relays use different
relaying algorithms to process the acquired information. Microprocessor/micro-
controller-based relays are called numerical relays specifically if they calculate the
algorithm numerically. The term ‘digital relay’ was originally used to designate a
previous-generation relay with analog measurement circuits and digital coincidence
time measurement (angle measurement) using microprocessors. Now a days the term
‘numerical relay’ is widely used in place of ‘digital relay’. Sometimes, both terms are
used in parallel. Similarly, the term ‘numerical protection’ is widely used in place of
‘digital protection’. Sometimes both these terms are also used in parallel.
The present downward trend in the cost of Very Large Scale Integrated (VLSI)
circuits has encouraged wide application of numerical relays for the protection of
modern complex power networks. Economical, powerful and sophisticated numeri-
cal devices (e.g., microprocessors, microcontrollers, DSPs, etc) are available today
because of tremendous advancement in computer hardware technology. Various effi-
cient and fast relaying algorithms which form a part of the software and are used 10
process the acquired information are also available today. Hence, there is a growing
trend to develop and use numerical relays for the protection of various components
of the modern complex power system. Numerical relaying has become a viable alter-
native to the traditional relaying systems employing electromechanical and static
relays. Intelligent numerical relays using artificial Intelligence techniques such as
Artificial Neural Networks (ANNs) and Fuzzy Logic Systems are presently under
active research and development stage.
The main features of numerical relays are their economy, compactness, flexibility
reliability, self-monitoring and self-checking capability, multiple functions, low bur-
den on instruments transformers and improved performance over conventional relays
of electromechanical and static types.16 Power System Protection and Switchgear
1.11.2 Classification of Protective Relays Based on Speed of Operation
Protective relays can be generally classified by their speed of operation as follows:
(i) Instantaneous relays
(ii) Time-delay relays
(iii) High-speed relays
(iv) Ultra high-speed relays
Instantaneous Relays
In these relays, no intentional time delay is introduced to slow down their response.
These relays operate as soon as a secure decision is made.
Time-delay Relays
In these relays, an intentional time delay is introduced between the relay decision
time and the initiation of the trip action.
High-speed Relays
These relays operate in less than a specified time. The specified time in present prac-
tice is 60 milliseconds (3 cycles on a 50 Hz system).
Ultra High-speed Relays
Though this term is not included in the relay standard but these relays are commonly
considered to operate within 5 milliseconds.
1.11.3 Classification of Protective Relays Based on their
Generation of Development
Relays can be classified into the following categories, depending on generation of
their development.
(i) First-generation relays: Electromechanical relays
(i)
(iii) Third-generation relays: Numerical relays.
‘econd-generation relays: Static relays
1.11.4 Classification of Protective Relays Based on their Function
Protective relays can be classified into the following categories, depending on the
duty they are required to perform:
(i) Overcurrent relays
(ii) Undervoltage relays
(iii) Impedance relays
(iv) Underfrequency relays
(v) Directional relays
These are some important relays. Many other relays specifying their duty they
perform can be put under this type of classification. The duty which a relay performs
is evident from its name. For example, an overcurrent relay operates when the current
exceeds a certain limit, an impedance relay measures the line impedance between
the relay location and the point of fault and operates if the point of fault lies within
the protected section. Directional relays check whether the point of fault lies in the
forward or reverse direction.
The above relays may be electromechanical, static or numerical.Introduction 17
1.11.5 Classification of Protective Relays as Comparators
Protective relays are basically comparators which must be able to carry out addition,
subtraction, multiplication or division of some scalar or some phasor quantities and
make comparisons of the input quantities as desired. Based upon this principle, the
protective relays can be classified as comparators into the following categories.
(i) Single-input comparator
(ii) Dual-input comparator
(iii) Multi-input comparator
Single-input Comparator
These relays have only one input signal and are also known as level detectors. Such
relays continuously monitor one electrical quantity and compare it with certain con-
stant quantity, i.e., a reference or a base quantity which may be the pull of a spring
or gravitational force. An example of this type of relay is an over current relay which
measures the current of a circuit and compares it with a certain preset value of the
reference or base quantities. Though these relays are simple in construction and oper-
ation, they have several drawbacks such as (i) they are non-directional, (ii) they are
not reliable because their action depends upon a single quantity, and (iii) they fail to
attain the desired reliability.
Dual-input Comparator
These relays have two input signals. Such relays measure one quantity and compare
it with another quantity. The typical examples of such type of relays are distance
relays and differential relays. The distance relay measures the current entering the
circuit and compares it in magnitude or in phase angle with the local bus voltage. The
differential relay measures the current entering the circuit and compares it with the
current leaving the circuit at the other end. Dual-input comparators are of two types,
i.e., amplitude comparator and phase comparator. The amplitude comparator com-
pares only the amplitude of the two input signals irrespective of phase angle between
them, whereas the phase comparator compares only the phase angle between the two
input signals irrespective of their magnitudes. There is duality between amplitude
and phase comparators, i.e., an amplitude comparator can be converted to a phase
comparator and vice-versa if the input quantities to the comparator are modified. The
modified input quantities are the sum and difference of the original two input quanti-
ties, These relays have several advantages and wide applications.
Multi-input Comparator
Multi-input comparators have more than two input signals and are used for the
relaisation of special characteristics other than straight lines or circle. These compar-
ators are also of two types, ie., (i) multi-input phase comparator, and (ii) multi-input
amplitude comparator. Multi-input phase comparator is used for realisation of
quadrilateral characteristic whereas multi-input amplitude comparator is used for
realisation of conic characteristics such as elliptical or hyperbolic characteristics.18 Power System Protection and Switchgear
1.12 COMPONENTS OF A PROTECTION SYSTEM
A protection system consists of ct CB Line
many other subsystems which con- Bus bar .
tribute to the detection and removal
of faults. As shown in Fig. 1.2, the pee
main subsystems of the protection tI —_
system are the transducers, relays, Typecolt |,
circuit breakers and trip circuit con- | Inport
taining trip coil and battery. Relay |__|)
The transducers, i.e., the current Battery
and voltage transformers (CTs and
VTs) are used to reduce currents
and voltages to standard lower values and to isolate protective relays from the high
voltages of the power system. They constitute a major component of the protection
system, and are discussed in detail in Chapter 3. Protective relays detect and locate
the fault and issue a command to the circuit breaker (CB) to disconnect the faulty
element. When a fault occurs in the protected circuit (i.e., the line in this case), the
relay connected to the CT and VT actuates and closes its contacts to complete the
trip circuit. Current flows from the battery in the trip circuit. As the trip coil of the
circuit breaker is energized, the circuit breaker operating mechanism is actuated and
it operates for the opening operation to disconnect the faulty element.
Fig. 1.2. Components of aprotection system
A circuit breaker is a mechanical switching device capable of making, carrying
and breaking currents under normal circuit conditions and also making, carrying fora
specified time, and automatically breaking currents under specified abnormal circuit
condition such as those of short circuits, i.e., faults. It is used to isolate the faulty part
of the power system under abnormal conditions. A protective relay detects abnormal
conditions and sends a tripping signal to the circuit breaker. A circuit breaker has two
contacts—a fixed contact and a moving contact. Under normal conditions, these two
contacts remain in closed position. When the circuit breaker is required to isolate
the faulty part, the moving contact moves to interrupt the circuit. On the separation
of the contacts, the flow of current is interrupted, resulting in the formation of an
are between the contacts. The medium in which circuit interruption is performed is
designated by a suitable prefix, such as oil circuit breaker, air-break circuit breaker, air
blast circuit breaker, sulphure hexafluoride circuit breaker, vacuum circuit breaker.
Since the primary function of a protection system is to remoye a fault, the abil-
ity to trip a circuit breaker through a relay must not be compromised during a fault,
when the ac voltage available at the substation may not be of sufficient magnitude.
In case of a close-in three-phase fault, the ac voltage at the substation can be zero.
Therefore the tripping power, as well as the power required by the relays cannot
be obtained from the ac system, and is usually provided by the station battery. The
battery which is permanently connected through a charger to the station ac service
floats on the charger during normal steady-state conditions. The charger is of a
sufficient VA capacity to provide all steady-state loads powered by the battery. The
battery should also be rated to maintain adequate de power for 8-12 hours following
a station blackout. For better reliability EHV stations have duplicate batteries, cachIntroduction 19
feeding from its charger, and connected to its own complement of relays. Since the
severe transients produced by the electromechanical relays on the battery loads dur-
ing their operation may cause maloperation of other sensitive relays in the substation,
or may even damage them, it is common practice, as far as practicable, to separate
electromechanical and static equipment by connecting them to different batteries.
1.13 CLASSIFICATION OF PROTECTIVE SCHEMES
A protective scheme is used to protect an equipment or a section of the line. It
includes one or more relays of the same or different types. The following are the
most common protective schemes which are usually used for the protection of a
modern power system,
(i) Overcurrent protection
(ii) Distance protection
(iii) Carrier-current protection
(iv) Differential protection
1.13.1 Overcurrent Protection
This scheme of protection is used for the protection of distribution lines, large
motors, equipment, ete. It includes one or more overcurrent relays, An overcurrent
relay operates when the current exceeds its pick-up value.
1.13.2 Distance Protection
Distance protection is used for the protection of transmission or sub-transmission
lines; usually 33 kV, 66 kV and 132 kV lines. It includes a number of distance relays
of the same or different types. A distance relay measures the distance between the
relay location and the point of fault in terms of impedance, reactance, etc. The relay
operates if the point of fault lies within the protected section of the line. There are
various kinds of distance relays. The important types are impedance, reactance and
mho type. An impedance relay measure the line impedance between the fault point
and relay location; a reactance relay measures reactance, and a mho relay measures
acomponent of admittance.
1.13.3. Carrier-Current Protection
This scheme of protection is used for the protection of EHV and UHV lines, gener-
ally 132 kV and above. A carrier signal in the range of 50-500 ke/s is generated for
the purpose. A transmitter and receiver are installed at each end of a transmission line
to be protected. Information regarding the direction of the fault current is transmitted
from one end of the line section to the other. Depending on the information, relays
placed at each end trip if the fault lies within their protected section. Relays do not
trip in case of external faults. The relays are of distance type and their tripping opera-
tion is controlled by the carrier signal.
113.4 Differential Protection
This scheme of protection is used for the protection of generators, transformers,
motors of very large size, bus zones, etc. CTs are placed on both sides of each20 Power System Protection and Switchgear
winding of a machine. The outputs of their secondaries are applied to the relay coils.
The relay compares the current entering a machine winding and leaving the same.
Under normal conditions or during any external fault, the current entering the wind-
ing is equal to the current leaving the winding. But in the case of an internal fault
on the winding, these are not equal. This difference in the current actuates the relay.
Thus, the relay operates for internal faults and remains inoperative under normal
conditions or during external faults. In case of bus zone protection, CTs are placed
on the both sides of the bus bar.
I 1.14 AUTOMATIC RECLOSING 1
About 90% of faults on overhead lines are of transient nature. Transient faults are
caused by lightning or external bodies falling on the lines. Such faults are always
associated with arcs. If the line is disconnected from the system for a short time,
the are is extinguished and the fault disappears. Immediately after this, the circuit
breaker can be reclosed automatically to restore the supply.
Most faults on EHV lines are caused by lightning. Flashover across insulators
takes place due to overvoltages caused by lightning and exists fora short time. Hence,
only on instantaneous reclosure is used in the case of EHV lines. There is no need
for more than one reclosure for such a situation. For EHV lines, one reclosure in 12
cycles is recommended. A fast reclosure is desired from the stability point of view.
More details have been given in Ch. 6.
On lines up 33 kV, most faults are caused by external objects such as tree branches,
etc. falling on the overhead lines. This is due to the fact that the support height is less
than that of the trees. The external objects may not be burnt clear at the first reclosure
and may require additional reclosures. Usually three reclosures at 15-120 seconds’
intervals are made to clear the fault. Statistical reports show that over 80% faults
are cleared after the first reclosure, 10% require the second reclosure and 2% need
the third reclosure, while the remaining 8% are permanent faults. If the fault is not
cleared after 3 reclosures, it indicates that the fault is of permanent nature. Automatic
reclosure are not used on cables as the breakdown of insulation in cables causes a
permanent fault.
1.15 CURRENT TRANSFORMERS (CTs)
t FOR PROTECTION 1
Current transformers (CTs) are used to obtain reduced current signals from the power
systems for the purpose of measurement, control and protection. They reduce the
heavy currents of the power system to lower values that are suitable for the opera-
tion of relays and other instruments connected to their secondary windings. Besides
reducing the current levels, CTs also isolate the relays and instruments circuits
from the primary circuit which is a high voltage power circuit and allow the use of
standardized current ratings for relays and meters, The current ratings of the second-
ary windings of the CTs have been standardized so that a degree of interchange-
ability among relays and meters of different manufacturers can be achieved. Since
the standard current ratings of the secondary windings of the CTs are 5 or 1 ampereIntroduction 21
the protective relays also have the same current rating. The current transformers are
designed to withstand fault currents (which may be as high as 50 times the full load
current) for a few seconds. Protective relays require reasonably accurate reproduc-
tion of the normal and abnormal conditions in the power system for correct sens-
ing and operation. Hence the current transformers should be able to provide current
signals to the relays which are faithful reproductions of the primary currents. The
measure of a current transformer performance is its ability to accurately reproduce
the primary current in secondary.
The requirements of CTs used for relaying are quite different from those of meter-
ing (CTs for measuring instruments). CTs used for instrumentation are required to be
accurate over the normal working range of currents, whereas CTs used for relaying
are required to give a correct ratio up to several times the rated primary current. The
CTs used for metering may have very significant errors during fault conditions, when
the currents may be several times their normal value for a very short time. Since
metering functions are not required during faults, this is not significant. CTs used
for relaying are designed to have small errors during fault conditions, whereas their
performance during normal steady state condition, when the relay is not required to
operate, may not be as accurate.
The accuracy of a current transformer is expressed in terms of the departure of its
ratio form its true ratio. This is called the ratio error, and is expressed as:
NI,~ 1,
Percent error = || « 100
where, N=Nominal CT ratio
__ Rated primary current
~ Rated secondary current
Number of secondary turns
© Number of primary tums
1, = Secondary current, and
1, = Primary current
The ratio error of a CT depends on its exciting current.
Current transformers are of electromagnetic, opto-electronic and Rogowski coil
types. The electromagnetic type CTs which are magnetically coupled, multi-winding
transformers can be classified into two categories: toroidal or bar primary CTs and
wound primary CTs. Toroidal or bar-primary-type CTs, donot contain a primary
winding and instead a straight conductor, (wire) which is a part of the power system
and carries the current, acts as the primary. The conductor (wire) that carries the cur-
rents is encircled by a ring-type iron core on which the secondary winding is wound
over the entire periphery. Wound-type CTs consist of a primary winding of fewer
turns wound on the iron core and inserted in series with the conductor that carries the
measured-current.
An opto-electronic or optical CT uses two light beams travelling through an opti-
cal fiber to measure the magnetic field around a current-carrying conductor, which22 Power System Protection and Switchgear
gives a measure of the current flowing in the conductor. The phase displacement
between the two beams is proportional to the level of current in the conductor.
The Rogowski Coil (RC) is a helical coil of wire with the lead from one end
returning through the centre of the coil to the other end, so that both are at the same
end of the coil. The whole assembly is then wrapped around the straight conduc-
tor whose current is to be measured. Since the voltage that is induced in the coil is
proportional to the rate of change (derivative) of current in the conductor, the output
of the Rogowski coil is usually connected to an electrical (or electronic) integrator
circuit to provide an output signal that is proportional to the current.
Current transformers are described in detail in Chapter 3.
1.16 VOLTAGE TRANSFORMERS (VTs)
Voltage transformers (VTs) were previously known as potential transformers (PTs).
They are used to reduce the power system voltages to lower values and to provide
isolation between the high-voltage power network and the relays and other instru-
ments connected to their secondaries. The voltage ratings of the secondary windings
of the VTs have been standardized, so that a degree of interchangeability among
relays and meters of different manufacturers can be achieved, The secondary wind-
ings of the voltage transformers are rated at 110 V line to line. Therefore, the voltage
ratings of the voltage (pressure) coils of protective relays and measuring instruments
(meters) are also 110 V line to line. The voltage transformers should be able to pro-
vide voltage signals to the relays (and meters) which are faithful reproductions of the
primary voltages.
The accuracy of voltage transformers is expressed in terms of the departure of its
ratio from its true ratio.
The percentage ratio error is given by
KV,-V,)
Percent ratio error = x 100
v,
where, K = Nominal voltage ratio
Rated primary voltage
Rated secondary voltage
Number of primary turns
~ Number of secondary turns
V,
Secondary voltage, and
V, = Primary voltage
Ideally a VT should produce a secondary voltage which is exactly proportional and
in phase opposition to the primary voltage. But, in practice, this cannot be achieved
owing to the voltage drops in the primary and secondary windings due to magnitude
and power factor of the secondary burden. Thus, ratio and phase angle errors are
introduced.Introduction 23
There are three types of voltage transformers:
(i) electromagnetic type, (ii) capacitor type, and (iii) opto-electronic type. The electro
magnetic type of VT is similar to a conventional wound type transformer with addi-
tional feature to minimise errors. This type of VT is conveniently used for voltages
up to 132 KV. Capacitor-type voltage transformer has a capacitance voltage divider
and is used at higher system voltages, i.e., 132 KV and above. This type of voltage
transformer is also known as Coupling Capacitor Voltage Transformer (CCV). In
an opto-electronic VT, a circular polarized light beam traveling through a fibre optic
up the column is used to determine the voltage difference between the conductor
and the ground. This type of voltage transformer is also known as electronic voltage
transformer.
The voltage transformers (VTs) are described in detail in Chapter 3.
1.17. BASIC RELAY TERMINOLOGY
I
Relay: A relay i
indirectly controlled (opened or closed) and is governed by a change in the same or
another electrical circuit.
an automatic device by means of which an electrical circuit is
Protective relay: A protective relay is an automatic device which detects an abnor-
mal condition in an electrical circuit and causes a circuit breaker to isolate the faulty
clement of the system. In some cases it may give an alarm or visible indication to
alert operator.
Operating force or torque: A force or torque which tends to close the contacts of
the relay.
Restraining force or torque: A force or torque which opposes the operating force/
torque.
Actuating quantity: An electrical quantity (current, voltage, etc) to which relay
responds.
Pick-up (level): The threshold value of the actuating quantity (current, voltage, etc.)
above which the relay operates.
Reset on drop-out (level): The threshold value of the actuating quantity (current,
voltage, etc.) below which the relay is de-energised and returns to its normal position
or state. Consider a situation where a relay has closed its contacts and the actuating
current is still flowing. Now, due to some reason, the abnormal condition is over and
the current starts decreasing. At some maximum value of the current the contacts will
start opening. This condition is called reset or drop-out. The maximum value of the
actuating quantity below which contacts are opened is called the reset or drop-out
value.
Operating time: Ii is the time which elapses from the instant at which the actuating
quantity exceeds the relays pick-up value to the instant at which the relay closes its
contacts.
Reset time: [t is the time which elapses from the moment the actuating quantity falls
below its reset value to the instant when the relay comes back to its normal (initial)
position.24 Power System Protection and Switchgear
Setting: The value of the actuating quantity at which the relay is set to operate.
Seal-in relay: This is a kind of an auxiliary relay. It is energised by the contacts of
the main relay. Its contacts are placed in parallel with those of the main relay and is
designed to relieve the contacts of the main relay from their current carrying duty. It
remains in the circuit until the circuit breaker trips. The seal-in contacts are usually
heavier than those of the main relay.
Reinforcing relay: This is a kind of an auxiliary relay. It is energised from the con-
tacts of the main relay. Its contacts are placed in parallel with those of the main relay
and it is also designed to relieve the main relay contacts from their current carrying
duty, The difference between a reinforcing relay and a seal-in relay is that the latter
is designed to remain in the circuit till the circuit breaker operates. But this is not
so with the reinforcing relay. The reinforcing relay is used to hold a signal from the
initiating relay (main relay) for a longer period. As the contacts of the main relay are
not robust, they are closed for a short time.
Back-up relay: A back-up relay operates after a slight delay, if the main relay fails
to operate.
Back-up protection: The back-up protection is designed to clear the fault if the
primary protection fails. It acts as a second line of defence.
Primary protection: If a fault occurs, itis the duty of the primary protective scheme
to clear the fault. It acts as a first line of defence. If it fails, the back-up protection
clears the fault.
Measuring relay: It is the main protective relay of the protective scheme, to which
energising quantities are applied. It performs measurements to detect abnormal con-
ditions in the system to be protected.
Auxiliary relays: Auxiliary relays assist protective relays. They repeat the opera-
tions of protective relays, control switches, etc. They relieve the protective relays of
duties like tripping, time lag, sounding and alarm, etc. They may be instantaneous or
may have a time delay.
Electromagnetic relay: A relay which operates on the electromagnetic principle,
ie., an electromagnet attracts magnetic moving parts (e.g.,) plunger type moving
iron type, attracted armature type). Such a relay operates principally by action of an
electromagnetic element which is energized by the input quantity.
Electromachanical relay: An electrical relay in which the designed response is
developed by the relative movement of mechanical elements under the action of a
current in the input circuit. Such relay operates by physical movement of mechanical
parts resulting from electromagnetic or electrothermic forces created by the input
quantities.
Electrodynamic relay: A relay which has two or more coils and- operates due to
interaction of fluxes produced by the individual coils
Ferrodynamic relay: A relay in which the electrodynamic action is reinforced by
pieces of ferromagnetic material placed in the path of magnetic lines of force.
Static relays: These are solid state relays and employ semiconductor diodes, tran-
sistors, thyristors, logic gates, ICs, etc. The measuring circuit is a static circuit and
there are no moving parts. In some static relays, a slave relay which is a de potarised
relay is used as the tripping device.Introduction 25
Analog relay: An analog relay is that in which the measured quantities are con-
verted into lower voltage but similar signals, which are then combined or compared
directly to reference values in level detectors to produce the desired output.
Digital relay: A digital relay is that in which the measured ac quantities are manipu-
lated in analog form and subsequently converted into either square-wave voltages or
digital form. Logic circuits or microprocessors compare either the phase relation-
ships of the square waves or the magnitudes of the quantities in digital form to make
atrip decision.
Numerical relay: A numerical relay is that in which the measured ac quanti-
ties are sequentially sampled and converted into numerical (digital) data form. A
microprocessor or a microcontroller processes the data numerically (i.e., performs
mathematical and/or logical operations on the data) using an algorithm to calculate
the fault discriminants and make trip decisions.
Microprocessor-based relay: A microprocessor is used to perform all functions
of a relay, It measures electrical quantities, makes comparisons, performs computa-
tions, and sends tripping signals. It can realise all sorts of relaying characteristics,
even irregular curves which cannot be reslised by electromechanical or static relays
easily.
Microcontroller-based relay: A microcontroller is used for performing all the
function of the relay. It measures the electrical quantities by acquiring them in digital
form through a data acquisition system, makes comparisons, processes the digital
data to calculate the fault discriminants and make trip decisions. It can realise all
sorts of relaying characteristics.
DSP-based relay: A Digital Signal Processor (DSP) is used to perform all the func-
tions of a relay.
FPGA-based relay: A Field Programmable Gate Array (FPGA) is used to perform
all the functions of a relay. It acquires the signals, processes them to calculate the
fault discriminants and make trip decisions.
ANN-based relay: An Artificial Neural Network (ANN) is used for processing the
relaying signals (current and voltage signals) and making trip decisions.
Overcurrent relay: A relay which operates when the actuating current exceeds a
certain preset value (its pick-up value).
Undervoltage relay: A relay which operates when the system voltage falls below a
certain preset value.
Directional or reverse power relay: A directional relay is able to detect whether
the point of fault lies in the forward or reverse direction with respect to the relay loca-
tion. It is able to sense the direction of power flow, i.e. whether the power is flowing
in the normal direction or the reverse direction.
Polarised relay: A relay whose operation depends on the direction of current or
voltage.
Flag or target: Flag i:
operated or not.
Time-lag relay: A time-lag relay operates after a certain preset time lag. The time
lag may be due to its inherent design feature or may be due to the presence of a time-
a device which gives visual indication whether a relay has26 Power System Protection and Switchgear
delay component. Such relays are used in protection schemes as a means of time
discrimination. They are frequently used in control and alarm schemes.
Instantaneous relay: An instantaneous relay has no intentional time delay in its
operation. It operates in 0.1 second. Sometimes the terms high set or high speed
relays are also used for the relays which have operating times less than 0.1 second.
Inverse time relay: A relay in which the operating time is inversely proportional to
the magnitude of the operating current.
Definite time relay: A relay in which the operating time is independent of the mag-
nitude of the actuating current.
San inverse
Inverse Definite Minimum Time (IDMT) Relay: A relay which gi
time characteristic at lower values of the operating current and definite time char:
teristic at higher values of the operating current.
Induction relay: A relay which operates on the principle of induction.
Examples are induction disc relays, induction cup relays etc.
Moving coil relay: This type of a relay has a permanent magnet and a moving coil.
It is also called a permanent magnet d.c. moving coil relay. The actuating current
flows in the moving coil.
Moving iron relay: This is a de polarised, moving iron type relay. There is an elec-
tromagnet, permanent magnet and a moving armature in its construction.
Printed disc relay: This relay operates on the principle of a dynamometer. There is
a permanent magnet or an electromagnet and a printed disc. Direct current is fed to
the printed circuit of the disc.
Thermal relay: This relay utilises the electrothermal effect of the actuating current
for its operation.
Distance relay: A relay which measures impedance or a component of the imped-
ance at the relay location is known as a distance relay. It is used for the protection ofa
transmission line. As the impedance of a line is proportional to the length of the line,
arelay which measures impedance or its component is called a distance relay.
Impedance relay: A relay which measures impedance at the relay location is called
an impedance relay. It is a kind of a distance relay.
Modifie pedance relay: [tis an impedance relay having shifted characteris
The voltage coil includes some current biasing.
Reactance relay: A relay which measures reactance at the relay location is called a
reactance relay. It is a kind of a distance relay.
MHO relay (admittance or angle admittance): This is a kind of a distance relay.
It measures a particular component of the impedance, i.e. where dis the
Z
cos (@— 6)"
power factor angle and @ is the design angle to shift MHO characteristic on the R-X
diagram. Its characteristic on the R-X diagram is a circle passing through the origin.
It is a directional relay. It is also known as an admittance or angle admittance relay.
Conduction relay: This is a MHO relay whose diameter (passing through the ori-
gin) lies on the R-ayIntroduction 27
Offset MHO characteristic: In an offset MHO relay, the MHO characteristic is
shifted on the R-X diagram to include the origin.
Angle impedance relay (ohm relay): The characteristic of this relay on the R-X
diagram is a straight line passing at an angle and cutting both the axes. It is a kind of
a distance relay and is also called an Ohm relay.
Flliptical relay: The characteristic of an elliptical relay on the R-X diagram is an
ellipse. This is also a kind of a distance relay.
Quadrilateral relay: The characteristic of a quadrilateral relay on the R-X diagram
is a quadrilateral. This too is a kind of a distance relay.
Frequency sensitive relay: This is a relay which operates at a predetermined value
of the system frequency. It may be an under-frequency relay or an over-frequency
relay. An under-frequency relay operates when the system frequency falls below
a certain value. An oyer-frequency relay will operate when the system frequency
exceeds a certain preset value of the frequency.
Differential relay: A relay which operate in response to the difference of two actu-
ating quantities.
Earth fault relay: A relay used for the protection of an element of a power system
against earth faults is known as an earth fault relay.
Phase fault relay: A relay used for the protection of an element of a power system
against phase faults is called a phase fault relay.
Negative sequence relay: A relay for which the actuating quantity is the negative
sequence current. When the negative sequence current exceeds a certain value, the
relay operates. This type of a relay is used to protect electrical machines against
overheating due to unbalanced currents.
Zero sequence relay: A relay for which the actuating quantity is the zero sequence
current. This type of a relay is used for earth fault protection.
Starting relay or fault detector: This is a relay which detects abnormal conditions
and initiates the operation of other elements of the protective scheme.
Notching relay: A relay which switches in response to a specific number of applied
impulses is called a notching relay,
Regulating relay: A regulating relay is activated when an operating parameter devi-
ates from predetermined limits. This relay functions through supplementary equip-
ment to restore the quantity to the prescribed limits.
Monitoring relay: A monitoring relay verifies conditions on the power system or in
the protection system. This relay includes fault detectors, alarm units, channel-mon-
itoring relays, synchronism verification, and network phasing. Power system condi-
tions that do not involve opening circuit breakers during faults can be monitored by
monitoring (verification) relays.
Synchronizing (or synchronism check) relay: This relay assures that proper con-
ditions exist for interconnecting two sections of power system.
Biased relay: A relay in which the characteristics are modified by the introduction
of some quantity other than the actuating quantity, and which is usually in opposition
to the actuating quantity. The setting of this relay is modified by additional windings
the amount of bias being dependent upon conditions in the protected circuit.28 Power System Protection and Switchgear
Primary relay: A relay which is directly connected to the protected circuit without
interposing instrument transformers or shunt.
Secondary relay: A relay connected to the protected circuit through current and
voltage transformers.
Sequential relay: A relay which instantaneously transfers its contact position from
a particular combination of ‘off’ and ‘on’ position to another combination, every time
it picks up or drops off, according to a predetermined programme which may or may
not be adjustable and repetitive
Indicating relay: A measuring or auxiliary relay which displays a signal on
energisation
Reclosing relay: This relay establishes a closing sequence for a circuit breaker fol-
lowing wipping by protective relays.
Supervisory relay: A measuring relay or a combination of measuring and auxiliary
relays in a unit with a definite purpose of supervision.
Change over relay: An auxiliary relay with two positions either of which cannot
be designated as ‘on’ and ‘off’ but which transfers the contact circuits from one con-
nection to the other.
‘Two-step relay: A relay with two sets of contacts, one of them operates at a cer-
tain value of the characteristic quantity and the other after a further change of the
quantity.
Current unbalance relay: This relay operates when the currents in a polyphase
system are unbalanced by a predetermined amount.
Voltage unbalanced relay: This relay operates when the voltages in a poly phase
system are unbalanced by a predetermined amount.
Ferraris relay: This relay moves by the interaction of the magnetic field of a coil
and the currents induced in a metal body (disc or cup)
Protective zone: A power system is divided into a number of zones from the pro-
tection point of view. Each element of the power system has a separate protective
scheme for its protection. The elements which come under a protective scheme are
said to be in the zone of protection of that particular scheme. Similarly, a protective
relay has its own zone of protection.
Reach: This term is mostly used in connection with distance relays. A distance relay
operates when the impedance (or a component of the impedance) as seen by the relay
is less than a preset value. This preset impedance (or a component of impedance) or
corresponding distance is called the reach of the relay. In other words, it is the maxi-
mum length of the line up to which the relay can protect.
Overreach: Sometimes a relay may operate even when a fault point is beyond its
present reach (ice. its protected length).
Underreach: Sometimes a relay may fail to operate even when the fault point is
within its reach, but it is at the far end of the protected line. This phenomenon is
called underreach.
Selectivity or discrimination: It is the ability of a relay to discriminate between
faulty conditions and normal conditions (or between a fault within the protected
section and outside the protected section). In other words, it is the quality of theIntroduction 29
protective system by which it distinguishes between those conditions for which it
should operate and those for which it should not.
Reliability: A protective relay must operate reliably when a fault occurs. The reli-
ability of a protective relay should be very high, a typical value being 95%.
Sensitivity: A protective relay should be sensitive enough to operate when the mag-
nitude of the actuating quantity exceeds its pick-up value.
Stability: This is the ability of the protective system to remain inoperative under all
load conditions, and also in case of external faults. The relay should remain stable
when a heavy current due to an external fault is flowing through it.
Fast operation: A protective relay should be fast enough to cause the isolation of
the faulty section as quickly as possible to minimise the damage and to maintain the
stability.
Burden: The power consumed by the relay circuitry at the rated current is known
as its burden.
Blocking: The prevention of tripping of the relay is called blocking. It may be due
to the operation of an additional relay or due to its own characteristic.
Energizing quantity: The electrical quantity, i.e., either current or voltage, which
alone or in combination with other electrical quantities, must be applied to the relay
for its functioning.
Characteristic quantity: A quantity, the value of which characterizes the operation
of the relay for example, current for an overcurrent relay, voltage for a voltage relay,
phase angle for a directional relay, time for an independent time delay relay, imped-
ance for an impedance relay, frequency for a frequency relay.
Characteristic angle: The angle between the phasors representing two of the ener-
gizing quantities applied to a relay and used for the declaration of the performance
of the relay.
System Impedance Ratio (SIR): The ratio of the power system source impedance
to the impedance of the protected zone.
Characteristic Impedance Ratio (CIR): The maximum value of the system imped-
ance ratio up to which the relay performance remains within the prescribed limits of
accuracy.
Power swing: Oscillation between groups of synchronous machines caused by an
abrupt change in load conditions.
Through fault current: The current flowing through a protected zone to a fault
beyond that zone.
Unit system of protection: A unit system of protection is one which is able to detect
and respond to faults occurring only within its own zone of protection. It is said
to have absolute discrimination. Its zone of protection is well defined. It does not
respond to the faults occurring beyond its own zone of protection. Examples of unit
protection are differential protection of alternators, transformers or bus bars, frame
leakage protection, pilot wire and carrier current protection.
Non-unit system of protection: A non-unit system of protection does not have
absolute discrimination (selectivity). It has dependent or relative discrimination.
The discrimination is obtained by time grading, current grading or a combination of30 Power System Protection and Switchgear
current and time grading of the relays of several zones. In this situation, all relays
may respond to a given fault. Examples of non-unit system of protection are dis-
tance protection and time graded, current graded or both time and current graded
protection.
Restricted earth fault protection: This is an English term which may be misunder-
stood in other countries. It is used in the context of transformer or alternator. It refers
to the differential protection of transformers or alternators against ground faults. It is
called restricted because its zone of protection is restricted only to the winding of the
alternator or transformer. The scheme responds to the faults occurring within its zone
of protection. It does not respond to faults beyond its zone of protection.
Unrestricted protection: A protection system which has no clearly defined zone of
operation and which achieves selective operation only by time grading.
Protective gear or equipment: It includes transducers (CTs and VTs), protective
relays, circuit breakers and ancillary equipment to be used ina protective system.
Protective system: It is a combination of Protective gear equipment to
secure isolation of the faulty element under predetermined conditions, usually
abnormal or to give an alarm signal or both,
Protective scheme: A protective scheme may consist of several protective systems.
It is designed to protect one or more elements of a power system.
Residual current: It is the algebraic sum of all currents in a multiphase
system. It is denoted by /,,,. In a 3-phase system J, = 1, + Ig + Io
‘Transducers or instrument transformers: Current and voltage transformers (CTs
and VTs) are collectively known as transducers or instrument transformers. They are
used to reduce currents and voltages to standard lower values and to isolate protective
relays and measuring instruments from the high voltages of the power system.
Switchgear: It is a general term covering switching and interrupting devices and
their combination with associated control, metering, protective and regulating
devices, also assemblies of these devices with associated inter-connections, accesso-
ries, enclosures and supporting structures used primarily in connection with genera-
tion, transmission, distribution, and conversion of electric power.
Circuit breaker: It is a mechanical switching device capable of making, carrying
and breaking currents under normal circuit conditions and also making, carrying fora
specified time, and automatically breaking currents under specified abnormal circuit
conditions such as those of short circuit. The medium in which circuit interruption
is performed may be designated by suitable prefix, such as, oil-circuit breaker, air-
blast circuit breaker, air-break circuit breaker, sulphur hexafluoride circuit breaker,
vacuum circuit breaker, etc.
Adaptive relaying: Adaptive relaying is defined as the protection system whose
settings can be changed automatically so that it is attuned to the prevailing power
system conditions.
Pilot wire: An auxiliary conductor used in connection with remote measuring
devices or for operating apparatus at a distant point.
Pilot protection: A form of line protection that uses a communication channel as a
means to compare electrical conditions at the terminals of a line.Introduction 31
Pilot wire protection: Pilot protection in which a metallic circuit is used for the
communicating means between relays at the circuit terminals.
EXERCISES
10.
ll.
14.
15.
16.
17.
. Explain the nature and causes of faults. Discuss the consequences of faults
‘on a power system.
What are the different types of faults? Which type of fault is most
dangerous?
Discuss briefly the role of protective relays in a modern power system.
What do you understand by a zone of protection? Discuss various zones of
protection for a modern power system.
. Explain what you understand by primary and back-up protection. What is
the role of back-up protection? What are the various methods of providing
back-up protection?
Explain what you understand by pick-up and reset value of the actuating
quantity.
Discuss what you understand by selectivity and stability of protective relay.
Discuss the essential qualities of a protective relay.
How is the relay performance classified? What indication the correct opera-
tion of the relay gives? What do you mean by “correct but unwanted opera-
tion”?
What do you understand by incorrect operation of the protective relay? What
are the reasons of incorrect operation?
Discuss the classification of protective relays based on their speed of opera-
tion.
2. Differentiate between a digital relay and a numerical relay.
3. What is a numerical relay? Discuss its advantages over conventional relays
of electromechanical and static types. How can an intelligent numerical relay
be developed.
What are the various components of a protection system? Briefly describe
their functions with the help of an schematic diagram.
Differentiate between a protective system and a protective scheme.
What do you understand by adaptive relaying? How can a relay be made
adaptive?
Briefly describe the following types of relay.
(i) Monitoring relay (ii) Regulating relay (iii) Auxiliary relay (iv) Synchroniz-
ing relay, and (v) Biased relay.Relay Construction and
Operating Principles
' 2.1 INTRODUCTION '
The proper operation of the power system requires an efficient, reliable and fast-
acting protection scheme, which basically consists of protective relays and switching
devices. A protective relay, acting as a brain behind the whole system, senses the
fault, locates it, and sends a command to appropriate circuit breaker to i
late only
the faulty section, thus keeping the rest of the healthy system functional. It detects
abnormal conditions on a power system by constantly monitoring the electrical quan-
tities of the system, which are different under normal and abnormal (fault) conditions.
The basic electrical quantities which are likely to change during abnormal conditions
are current, voltage, phase angle (direction) and frequency. Protective relays utilize
one or more of these quantities to detect abnormal conditions on a power system.
The basic relay circuit is illustrated in Fig. 2.1. There are two ways in which the
circuit breaker trip coil is energized. In one method, the station battery is used 10
supply the current in the trip coil after the relay contacts are closed by the operation
of the relay. In the second method, as soon as the relay operates, the CT secondary
current flows through the trip coil and energizes it. This method does not require a
station battery and it is used for the protection of feeders.
Bus bar
3-6 Line [
Station battery ‘oon Laua 4
e007 VT,
(OD)
CB- Circuit breaker
CT- Current transiormer
VT- Voltage transformer
CC- Current coil of the
relay
VC- Voltage coil of the
relay
Fig. 2.1 Relay connectionRelay Construction and Operating Principles 33
Protective relays are broadly classified into the following three categories
depending on the technologies they use for their construction and operation.
(i) Electromechanical relays
(ii) Static relays
(iii) Numerical relays
There are various types of protective relays in each category, depending on the
operating principle and application.
I 2.2. ELECTROMECHANICAL RELAYS 1
Electromechanical relays operate by mechanical forces generated on moving parts
due to electromagnetic or electrothermic forces created by the input quantities. The
mechanical force results in physical movement of the moving part which closes the
contacts of the relay for its operation. The operation of the contact arrangement is
used for relaying the operated condition to the desired circuit in order to achieve
the required function. Since the mechanical force is generated due to the flow of an
electric current, the term ‘electromechanical relay” is used.
Most electromechanical relays use either electromagnetic attraction or electro-
magnetic induction principle for their operation. Such relays are called electromag-
netic relays. Depending on the principle of operation, the electromagnetic relays
are of two types, i.e., (i) attracted armature relays, and (ii) induction relays. Some
electromechanical relays also use electrothermic principle for their operation and
are based upon the forces created by expansion of metals caused by temperature rise
due to flow of current. Such relays are called thermal relays. Most of the present day
electromechanical relays are of either induction disc type or induction cup type.
The following are the principal types of electromechanical relays:
1. Electromagnetic relays
(i) Attracted armature relays, and
(ii) Induction relays
2. Thermal relays
2.2.1 Attracted Armature Relays
Attracted armature relays are the simplest type which respond to ac as well as de.
These relays operate through an armature which is attracted to an electromagnet
or through a plunger which is drawn into a solenoid. All these relays use the same
electromagnetic attraction principle for their operation. The electromagnetic force
exerted on the moving element, i.c., the armature or plunger, is proportional to the
square of the flux in the air gap or the square of the current. In de relays this force
is constant. In case of ac relays, the total electromagnetic force pulsates at double
the frequency. The motion of the moving element is controlled by an opposing force
generally due to gravity or a spring.
The following are the different types of construction of attracted armature relays.
(i) Hinged armature type
(ii) Plunger type34 Power System Protection and Switchgear
(iii) Balanced beam type
(iv) Moving-coil type
(v) Polarised moving-iron type
(vi) Reed type
Hinged Armature-Type Relays
Figure 2.2(a) shows a hinged armature-type construction. The coil is energised by
an operating quantity proportional to the system current or voltage. The operating
quantity produces a magnetic flux which in turn produces an electromagnetic force.
The electromagnetic force is proportional to the square of the flux in the air gap or
the square of the current. The attractive force increases as the armature approaches
the pole of the electromagnet. This type of a relay is used for the protection of small
machines, equipment, etc. It is also used for auxiliary relays, such as indicating flags,
slave relays, alarm relays, annunciators, semaphores, etc.
ees
To trip circuit To trip circuit
Electromagnet
I
7 Coll | Gi
/
Armature R rmature
heal
(a) (b)
Fig. 2.2 (a) Hinged armature-type relay (b) Modified hinged armature-type relay
The actuating quantity of the relay may be either ac or de. In de relay, the electro-
magnetic force of attraction is constant. In the case of ac relays, sinusoidal current
flows through the coil and hence the force of attraction is given by
F=KP=K Una max ~ !max
sin of)? = ; K (Bog. — Egg C08 201)
From the above expression, it is evident that the electromagnetic force consists
of two components. One component is constant and is equal to 2 K Pe The other
component is time dependent and pulsates at double the frequency of the applied ac
quantity. Its magnitude is % K P,,, cos 2et. The total force is a double frequency
pulsating force. This may cause the armature to vibrate at double the frequency.
Consequently, the relay produces a humming sound and becomes noisy. This
difficulty can be overcome by making the pole of the electromagnet of shaded
construction. Alternatively, the electromagnet may be provided with two coils. One
coil is energised with the actuating quantity. The other coil gets its supply through a
phase shifting circuit.Relay Construction and Operating Principles 35
The restraining force is provided by a spring. The reset to pick-up ratio for
attracted armature type relays is 0.5 to 0.9. For this type of a relay, the ratio for
ac relays is higher as compared to de relays. The VA burden is low, which is
0.08 W at pick-up for the relay with one contact, 0.2 W for the relay with four
contacts. The relay is an instantaneous relay. The operating speed is very high. Fora
modern relay, the operation time is about 5 ms. It is faster than the induction disc and
cup type relays. Attracted armature relays are compact, robust and reliable. They are
aifected by transients as they are fast and operate on both de and ac. The fault current
contains a dc component in the beginning for a few cycles. Due to the presence of de
transient, the relay may operate though the steady state value of the fault current may
be less than its pick-up. A modified construction as shown in Fig. 2.2(b) reduces the
effect of de transients.
Plunger-Type Relays
Figure 2.3 shows a plunger-type relay.
In this type of a relay, there is a solenoid Solenoid
and an iron plunger which moves in and
out of the solenoid to make and break the Plunger
contact. The movement of the plunger Fcontacts
is controlled by a spring. This type of
construction has however become obsolete + Spring
as it draws more current.
Fig. 2.3 Plunger-type relay
Balanced Beam Relays eo) Manseriypersiay
Figure 2.4 shows a balanced beam relay which is also a kind of attracted armature
type relay. As its name indicates, it consists of a beam carrying two electromagnets
at its ends. One gives operating torque while the other retraining torque. The beam
is supported at the middle and it remains horizontal under normal conditions. When
the operating torque exceeds the restraining torque, an armature fitted at one end of
the beam is pulled and its contacts are closed. Though now obsolete, this type of a
relay was popular in the past for constructing impedance and differential relays. It
has been superseded by rectifier bridge comparators and permanent magnet moving
coil relays. The beam type relay is robust and fast in operation, usually requiring only
I cycle, but is not accurate as it is affected by de transients.
Armature Control spring
/ i
Z
rea aconacts
Pivote
I, 1,
Iz Operating current
J; Restraining current
Fig. 2.4 Balanced beam relay36 Power System Protection and Switchgear
Moving Coil Relays
Figure 2.5 shows a permanent magnet mov-
ing coil relay. It is also called a polarised de
moving coil relay. It responds to only de actu- contest’
ating quantities. It can be used with ac actuat- if msg
ing quantities in conjunction with rectifiers. contact
f
Fixed
Moving coil relays are most sensitivity type
electromagnetic relays. Modern relays have a
sensitivity of 0.1 mW. These relays are cost- 4
lier than induction cup or moving iron type perrranent
relays. The VA burden of moving coil relays magnet
is very small. These are used as slave relays
with rectifier bridge comparators.
There are two types of moving coil relays: rotary moving coil and axially moving
coil type. The rotary moving coil type is similar to a moving coil indicating instru-
ment. Figure 2.5 shows a rotary moving coil type construction. The components are: a
permanent magnet, a coil wound on a non-magnetic former, an iron core, a phosphor
bronze spiral spring to provide resetting torque, jewelled bearing, spindle, etc. The
moving coil assembly carries an arm which closes the contact. Damping is provided
by an aluminum former. The operating time is about 2 cycles. A copper former can
be used for heavier damping and slower operation. The operating torque is produced
owing to the interaction between the field of the permanent magnet and that of the
coil. The operating torque is proprtional to the current carried by the coil. The torque
exerted by the spring is proportional to deflection. The relay has an inverse operating
time/current characteristic.
Fig. 2.5 Rotating moving coil relays
Figure 2.6 shows an axially moving coil | -———___ arp csi
type construction. As this type has only one 4
air gap, it is more sensitive than the rotary ee
moving coil relay. It is faster than the es | Berke
rotary moving coil relay because of light SEE circuit
parts. An operating time of the order of
30 msec can be obtained. Sensitivities as
low as 0.1 mW can be obtained. Its coils
are wound ona cylindrical former which is
suspended horizontally. The coil has only
axial movement. The relay has an inverse operating time/current characteristic. The
axially moving coil relay is a delicate relay and since the contact gap is small, it has
to be handled carefully.
Fig. 2.6 Axial moving coil relay
Polarised Moving Iron Relays
Figure 2.7 shows a typical polarised moving iron relay. There are different types of
constructions of this type (see Ref. 1). The construction shown in the figure is a flux
shifting attracted armature type construction. Polarisation increases the sensitivity
of the relay. A permanent magnet is used for polarisation. The permanent magnet
produces flux in addition to the main flux. It is a de polarised relay, meant to beRelay Construction and Operating Principles 37
used with de only. However, it can be To tip ~~
used with ac with rectifiers. Modern — *ireuit
relays have sensitivities in the range of
0.03 to ImW, depending on their con-
struction. Using transistor amplifiers,
arelay’s sensitivity can be increased to
1 UW for pick-up. It is used as a slave N 3 Ee
relay with rectifier bridge comparators
As its current carrying coil is stationary, Fig. 2.7 Polarised moving iron relay
it is more robust than the moving coil type de polarised relay. Its operating time is
2 msec to 15 msec depending upon the type of construction. An ordinary attracted
armature type relay is not sensitive to the polarity of the actuating quantity whereas a
de polarised relay will only operate when the input is of the correct polarity.
Reed Relays
A reed relay consists of a coil and nickel-iron strips Coil
: Seal
(reeds) sealed in a closed glass capsule, as shown
(eed : ooccoc0¢000000000
in Fig. 2.8. The coil surrounds the reed contact. gugoneoosssccueeS:
When the coil is energised, a magnetic field is
produced which causes the reeds to come together
and close the contact. Reed relays are very reliable
and are maintenance free. As far as their construc-
uid : Reed Contact
tion is concerned, they are electromagnetic relays. opening
But from the service point of view, they serve as
static relays. They are used for control and other
purposes.
They can also be used as a protective relays. They are quite suitable to be used
as slave relays. Their input requirement is | W to 3 W and they have speed of 1 or
2 msec. They are completely bounce free and are more suitable for normally-closed
applications. Heavy duty reed relays can close contacts carrying 2 kW at 30 A maxi-
mum current or at a maximum of 300 V de supply. The voltage withstand capacity
for the insulation between the coil and contacts is about 2 kV. The open contacts can
withstand 500 V to 1 kV.
Fig. 2.8 Reed relay
2.2.2 Induction Relays
Induction relays use electromagnetic induction principle for their operation. Their
principle of operation is same as that of a single-phase induction motor. Hence they
can be used for ac currents only. Two types of construction of these Relays are fairly
standard: one with an induction disc and the other with an induction cup. In both
types of relays, the moving element (disc or cup) is equivalent to the rotor of the
induction motor. There is one contrast from the induction motor, i.e., the iron associ-
ated with the rotor in the relay is stationary. The moving clement acts as a carrier of
rotor currents, whereas the magnetic circuit is completed through stationary magnetic
elements. Two sources of alternating magnetic flux in which the moving element
may turn are required for the operation of induction-type relays. In order to produce
an operating torque, the two fluxes must have a phase difference between them.38 Power System Protection and Switchgear
Induction Disc Relay
There are two types of construction of induction disc relays, namely the shaded pole
type, as shown in Fig. 2.9; and watt hour meter type, as shown in Fig. 2.10.
Figure 2.9(a) shows a simple theoretical figure, whereas Fig. 2.9(b) shows the
construction which is actually used in practice. The rotating disc is made of alu-
minium. In the shaded pole type construction, a C-shaped electromagnet is used. One
half of each pole of the electromagnet is surrounded by a copper band know as the
shading ring. The shaded portion of the pole produces a flux which is displaced in
space and time with respect to the flux produced by the unshaded portion of the pole.
Thus two alternating fluxes displaced in space and time cut the disc and produce
eddy currents in it. Torques are produced by the interaction of each flux with the eddy
current produced by the other flux. The resultant torque causes the disc to rotate.
Shading
ring
joe (OP N Brake
i ieee magnet
4
(a) Simple construction
Plug setting | {51 $F a
(PS) Brake
| magnet
(b) Construction in practice
Fig. 2.9 Shaded pole type induction disc relay
In wattmetric type of construction, two electromagnets are used: upper and lower
one. Each magnet produces an alternating flux which cuts the disc. To obtain a phase
displacement between two fluxes produced by upper and lower electromagnets, their
coils may be energised by two different sources. If they are energised by the same
ances and reactances of the two circuits are made different so that
there will be sufficient phase difference between the two fluxes.
source, the resi
Induction disc type construction is robust and reliable. It is used for overcurrent
protection, Disc type units gives an inverse time current characteristic and are slowRelay Construction and Operating Principles 39
compared to the induction cup and attracted armature type relays. The induction disc
type is used for slow-speed relays. Its operating time is adjustable and is employed
where a time-delay is required. Its reset/pick-up ratio is high, above 95% because its
operation does not involve any change in the air gap. The VA burden depends on its
application, and is generally of the order of 2.5 VA. The torque is proportional to the
square of the actuating current if single actuating quantity is used.
SE og ots 9
1
Relay
coil
MM
Secondary
coil
|
——— N nee iy bs 5 To trip circuit
Fig. 2.10 Wattmetric type induction-disc relay
A spring is used to supply the resetting torque. A permanent magnet is employed
to produce eddy current braking to the disc. The magnets should remain stable with
age so that its accuracy will not be affected. Magnets of high coercive force are used
for the purpose. The braking torque is proportional to the speed of the disc. When
the operating current exceeds pick-up value, driving torque is produced and the disc
accelerates to a speed where the braking torque balances the driving torque. The disc
rotates at a speed proportional to the driving torque.
It rotates at a constant speed for a given current. The disc inertia should be as
small as possible, so that it should stop rotating as soon as the fault current disap-
pears when circuit breaker operates at any other location or fault current is for a short
moment (i.e. transient in nature). After the cessation of the fault current, the disc will
travel to some distance due to inertia. This distance should be minimum. It is called
the over-run of the disc. A brake magnet is used to minimise over-run. The over-run
is usually not more than 2 cycles on the interruption of a current which is 20 times
the current setting.
At a current below pick-up value, the disc remains stationary by the tension of
the contro! spring acting against the normal direction of disc rotation. The disc rests40 Power System Protection and Switchgear
against a backstop. The position of the backstop is adjustable and therefore, the dis-
tance by which the moving contact of the relay travels before it closes contacts, can
be varied. The distance of travel is adjusted for the time setting of the relay.
The rotor (disc) carries an arm which is attached to its spindle. The spindle is
supported by jewelled bearings. The arm bridges the relay contacts. In earlier
constructions, there were two contacts which were bridged when the relay operated.
In modern units however, there is a single contact with a flexible lead-in.
Current Setting
In disc type units, there are a number of tapping provided on coil to select the desired
pick-up value of the current. These tapping are shown in Fig. 2.10. This will be
discussed in the next chapter.
Time Setting
The distance which the disc travels before it closes the relay contact can be adjusted
by adjusting the position of the backstop. If the backstop is advanced in the normal
direction of rotation, the distance of travel is reduced, resulting in a shorter operating
time of the relay. More details on time-setting will be discussed in the next chapter.
Printed Disc Relay
Figure 2.11 shows the construction of a printed disc inverse time relay. Its operating
principle is the same as that of a dynamometer type instrument.
Torque oh S\
%—___—_]
Fig. 2.11 Printed disc inverse time relay
GE
There is a permanent magnet to produce a magnetic field. The current from the
CT is fed to the printed disc through a rectifier. When a current carrying conductor is
placed in a magnetic field, a force is developed, thereby a torque is exerted on it. On
this very principle, torque is produced in a printed disc relay.
Figure 2.12 shows the construction of a printed disc extremely inverse time relay
(Pt = K relay). To obtain Pr = K characteristic, an electromagnet and a printed dise
are used. The electromagnet is energised from the CT through a rectifier.
Printed disc relays give a much more accurate time characteristic. They are also
very efficient. A printed disc relay is 50 to100 times more efficient than the inductionRelay Construction and Operating Principles 41
disc type. The maximum efficiency that an induction disc relay can have is only
about 0.05%, which is extremely poor. Characteristics other than inverse time-
current characteristic can be obtained by including a non-linear network in between
the printed circuit of the disc and the rectified current input.
Fig. 2.12 Printed disc extremely inverse time relay
Induction Cup Relay
Figure 2.13 shows an induction cup relay.
A stationary iron core is placed inside the
rotating cup to decrease the air gap with-
out increasing inertia. The spindle of the
cup carries an arm which closes contacts.
A spring is employed to provide a reset-
ting torque. When two actuating quantities
are applied, one may produce an operat-
ing torque while the other may produce
restraining torque. Brake magnets are not
used with induction cup type relays. It
operates on the same principle as that of an induction motor. It employs a 4 or 8-pole
structure.
Rotor
Stationary
core
Fig. 2.13. Induction cup relay
The rotor is a hollow cylinder (inverted cup). Two pairs of coils, as shown in the
figure, produce a rotating field which induces current in the rotor. A torque is pro-
duced due to the interaction between the rotating flux and the induced current, which
causes rotation. The inertia of the cup is much less than that of a disc. The magnetic
system is more efficient and hence the magnetic leakage in the magnetic circuit is
minimum. This type of a magnetic system also reduces the resistance of the induced
current path in the rotor. Due to the low weight of the rotor and efficient magnetic
tem its torque per VA is about three times that of an induction disc type construc-
tion. Thus, its VA burden is greatly reduced. It possesses high sensitivity, high speed42 Power System Protection and Switchgear
and produces a steady non-vibrating torque. Its parasitic torques due to current or
voltage alone are small. Its operating time is to the order of 0.01 second. Thus with
its high torque/inertia ratio, it is quite suitable for higher speeds of operation.
Magnetic saturation can be avoided by proper design and the relay can be made to
have its characteristics linear and accurate over a wide range with very high reset to
pick-up ratio. The pick-up and reset values are close together. Thus this type is best
suited where normal and abnormal conditions are very close together. It is inherently
self compensating for dc transients. In other words, it is less sensitive to dc transients.
The other system transients as well as transients associated with CTs and relay cir-
cuits can also be minimised by proper design. However, the magnitude of the torque
is affected by the variation in the system frequency. Induction cup type relays were
widely used for distance and directional relays. Later, however, they were replaced
by bridge rectifier type static relays.
Theory of Induction Relay Torque
Fluxes @, and @, are produced in a disc type construction by shading technique. In
watt-metric type construction, @, is produced by the upper magnet and @, by the
lower magnet. A voltage is induced in a coil wound on the lower magnet by trans-
former action. The current flowing in this coil produces flux @5. In case of the cup
type construction, @, and @, are produced by pairs of coils, as shown in Fig. 2.13. The
theory given below is true for both disc type and cup type induction relays. Figure
2.14 shows how force is produced in a rotor which is cut by @; and @). These fluxes
are alternating quantities and can be expressed as follows.
9; = Mm Sin oF 2 = Pry, Sin (@t + A)
where @ is the phase difference between 6,
and 95. The flux @, leads $, by 0.
Voltages induced in the rotor are:
a9,
Clade
& Dj, COS OF
do,
ey
“dt Fig. 2.14 Torque produced in an
%& Po, COS (WI + O) induction relay
As the path of eddy currents in the rotor has negligible self-inductance, with negli-
gible error it may be assumed that the induced eddy currents in the rotor are in phase
with their voltages.
i, © O_ COS Ot
iy © Gym COS (Cot + 0)
The current produced by the flux interacts with other flux and vice versa. The
forces produced are:
Fre ob
Gy», SiN OF yy, COS (Ct + B)
%€ Dim Grn, COS (WF + 6) - sin wrRelay Construction and Operating Principles 43
Fre bi
ce ds, Sin (@t + B) + @,,,, COS Ot
% Bim Pr Sin (@t + @) + cos cot
As these forces are in opposition, the resultant force is
F=(F,-F;)
c by, 92, [Sin (@t + A) cos @t— cos (@t + 8) - sin of]
Pim Prm Sin O
‘The suffix m is usually dropped and the expression is written in the form of
F = K6, @, sin @. In this expression, @, and @, are rms values.
If the same current produces @, and @, the force produced is given by
F=KPsin@
where @ is the angle between @, and @). If two actuating currants M and N produce
@, and ¢,, the force produced is
F = KMN sin @
2.2.3. Thermal Relays
These relays utilise the electro-thermal effect of the actuating current for their opera-
tion. They are widely used for the protection of small motors against overloading and
unbalanced currents. The thermal element is a bimetallic strip, usually wound into a
spiral to obtain a greater length, resulting in a greater sensitivity. A bimetallic element
consists of two metal strips of different coefficients of thermal expansion, joined
together. When it heats up one strip expands more than the other. This results in the
bending of the bimetallic strip. The thermal element can be heated directly by passing
the actuating current through the strip, but usually a heater coil is employed. When the
bimetallic element heats up, it bends and deflects, thereby closing the relay contacts.
For the ambient temperature compensation, a dummy bimetallic clement shielded
from the heater coil and designed to oppose the bending of the main bimetallic strip
is employed. When the strip is in a spiral form, the unequal expansions of the two
metals causes the unwinding of the spiral, which results in the closure of the contacts.
Fig. 2.15(a) shows a simple arrangement to indicate the operating principle. Figure
2.15(b) shows a spiral form. Unimetallic strips are also used as thermal elements in
ahair-pin like shape, as shown in Fig, 2.15(c). When the strip gets heated it expands
and closes the contac
For the protection of 3-phase motors, three bimetallic strips are used. They are
energised by currents from the three phases. Their contacts are arranged in such a
way that if any one of the spirals moves differently from the other, due to an unbal-
ance exceeding |2%, their contacts meet and cause the circuit breakers to trip. These
spirals also protect the motor against overloading.
Thermocouples and resistance temperature detectors are also used in protection.
In the protection of a large generator, such elements are placed in the stator slots.
The element forms an arm of a balancing bridge. In normal condition, the bridge is
balanced. When the temperature exceeds a certain limit, the bridge becomes unbal-
anced. The out-of-balance current energises a relay which trips a circuit breaker. This
will be discussed in detail in the chapter dealing with protection of machines.44 Power System Protection and Switchgear
To trip
5 irouit » To trip
J 5 eireuit
TELE Bimetallic
| —
strip
Pee coi
(a) (b)
To trip
_ [eat
i
Heating —_Unimetallic
element strip
(o)
Fig. 2.15 (a) Bimetallic thermal relay (b) Bimetallic spiral type thermal relay
(c) Unimetallic thermal relay
2.2.4 Auxiliary Relay, Auxiliary Switch and Flag
A protective relay is assisted by auxiliary relays for a number of important opera-
tions. A protective relay performs the task of measurement and under the required
condition, it closes its contacts. It is relieved of other duties such as tripping, time
lag, breaking of trip circuit current, giving alarm, showing flags etc. These duties are
performed by auxiliary relays. Auxiliary relays repeat the operations of protective
relays, control switches, etc. Repeat contact and auxiliary switches are also used to
assist protective relays. The reasons for employing auxiliary relays, repeat contactors
and auxiliary switches are:
(i) Protective relay contacts are delicate and light in weight. They are not capable
of carrying large amount of current for a long period.
(ii) The protective relays do not have enough contacts to perform all duties re-
quired in a protective scheme.
The commonly used auxiliary relays have been described below.
Seal-in Relay
A seal-in relay is an auxiliary relay which is employed to protect the contacts of
a protective relay. Once the protective relay closes its contacts, the seal-in relay is
energized. Its contacts bypass the contacts of the protective relay, close and seal the
circuit while the tripping current flows. It may also give an indication by showing a
flag (target), It is an instantaneous relay, operates on attracted armature principle.
Time-lag Relays
Time-lag relays operate after a preset time-lag. They are used in protection schemes
as a means of time discrimination, for example, time graded schemes which will beRelay Construction and Operating Principles 45
discussed in Chapter 5. They are also used in control and alarm circuits to allow time
for the required sequence of operations to take place. The principle of producing time
delays will be discussed later (see sec. 2.2.6).
Alarm Relays
An alarm relay gives both an audible and a visual indication. At a substation, it is
sufficient to provide a trip alarm and one non-trip alarm, which is common to the
whole substation. In the control room of a generating station, the trip alarm and non-
trip alarm should be separate for each primary circuit. There is an arrangement for
alarm cancellation by pressing a button. The alarm circuit is interrupted on pushing
this button, When the relay is de-energised, the initiating contact of the cancellation
mechanism is reset so that it can receive another alarm.
Repeat Contactors
A repeat contactor repeats the operation of a protective relay. It is sometimes needed
because a protective relay may not have a sufficient number of contacts. It may also
be required to take over the operation from the initiating relay if the contacts of
the latter are not designed for carrying current for long periods. Its most important
requirements are that it should be fast and absolutely reliable. It should also be robust
and compact. It is usually mounted in the same case as the relay for which it is
required to repeat the operation.
Repeat contactors operate on the attracted armature principle. It may be connected
either in series or in parallel with the relay. It contains a number of contacts which
are placed in parallel. However, having more than three contacts in parallel is usually
not pratical.
Flag or Target
When a relay operates, a flag is indicated to show its operation. When on a relay
panel there are several relays, it is the flag that indicates, the relay that has operated.
This helps the operator to know the cause of the tripping of the circuit breaker. Iti
also called the target or indicator. Its coil is connected in series with the trip coil of
the circuit breaker, as shown in Fig. 2.16. The resetting of a flag indicator is usually
manual. There is a button or knob outside the relay case to reset the flag indicator. A
flag indicator may either be electrical or mechanical. In a mechanical flag indicator,
the movement of the armature of the relay pushes a small shutter to expose the flag.
In an electrically operated flag indicator there is a solenoid which is energised when
relay contacts are closed. Electrical flags being more reliable are preferred.
Auxiliary Switch
An auxiliary switch is connected in series with the trip-coil circuit, as shown in
Fig. 2.16. It is mechanically interlocked with the operating mechanism of the circuit
breaker so that the auxiliary switch opens when the circuit breaker opens. The open-
ing of the auxiliary switch prevents unnecessary drainage of the battery.
When the trip-coil of the circuit breaker is energised, it actuates a mechanism of
the circuit breaker, which causes the operating force to come into action to open the
circuit breaker.46 Power System Protection and Switchgear
2.2.5 Connections for Seal-in Relay, Auxiliary Switch and
Circuit Breaker Trip-Coil
Figure 2.16(a) shows the connection fora seal-in relay, circuit breaker trip-coil and
auxiliary switch. In order to protect the contacts of the protective relay, a seal-in
relay is employed. Its contacts bypass the contacts of the protective relay and seal the
circuit closed, while the tripping current flows. Some relays employ a simple hold-
ing coil in series with the relay contacts, as shown in Fig. 2.16(b). The holding coil
is wound on a small soft iron core which acts on a small armature on the moving-
contacts assembly to hold the contacts tightly closed, once they have established the
flow of current through the trip coil. The holding coils are used to protect the relay
contacts against damage which may be caused due to the make and break action of
the contacts
+ +
Sealin== == Protective-relay Protective-relay
relay —— contact contact
contact Flag Fleg
Seal-.in relay coil Holding coil
Circuit breaker Circuit breaker
trip coil trip coil
Circuit breaker {, Circuit breaker
auxiliary switch fF auxiliary switch
~00000 92009 90000 —|
(a) (b)
2.16 Circuit breaker trip coil circuit (a) With seal-in relay (b) With holding coil
2.2.6 Techniques to Produce Time-delays
Sometimes, a protective relay is required to operate after a preset time delay.
Intentional time delays are necessary for such relays. The intentional time delay may
be caused by inherent design features of the relay or by a delay producing component
of the relay. Sometimes, a starting relay or instantaneous relay is used in conjunction
with a timing relay to perform certain operations after a preset time. A time-lag relay
(timing relay) is an auxiliary relay designed to operate after a preset time-delay.
Mechanical Time-delay
The time delay may be produced by mechanical, electrical or electronic components.
Oil dashpots, pneumatic damping, toothed gears, cams, mercury switches, etc. are
some examples of mechanical devices which are used to produce a time delay. In an
oil dashpot, there is a mechanically operated plunger. Oil flowing through an orifice
in the cylinder retards the relay movement. The pneumatic timer contains a metal
chamber, a diaphragm and solenoid. These mechanical devices are crude devices
and do not produce accurate delays. The mercury switch, however, gives an accurate
delay. The mercury tube has two sections. One section contains mercury and the
other section contains contacts. The tube is tilted so that mercury flows from oneRelay Construction and Operating Principles 47
section to the other and bridges the contacts. The flow of mercury is impeded by a
construction between the two sections of the tube. The time setting is fixed by the
design of the tube. It is not possible to have a range of time settings on a particular
mercury switch. Toothed gears or cams are also used to produce time delay.
Thermal Time-delay
Thermal devices employing expansion of bimetal strip or spiral, unimetal (brass)
strips, etc. are also used to produce time-delay.
Electrical Time-delay
Time delay can be produced by employing a short-circuiting ring around a solenoid
pole; a circuit containing reactance, capacitance or non-linear resistance; a resonant
circuit, etc.
Short-circuiting Ring
A short-circuiting copper band is fitted around the pole piece of an attracted arma-
ture hinged-type relay. This arrangement provides eddy current path for damping. To
obtain a time-delay on pick-up, the band is placed at the armature end of the core. By
this technique, a delay of about 0.1 s can be produced in pick-up with a large arma-
ture gap, and a stiff restraining spring. To obtain a delayed reset, the band is placed at
the frame end of the solenoid. A delay up to 0.5 s in drop out can be obtained with a
short lever arm and a light spring load. Time-delay can also be produced by employ-
ing a copper tube inside the coil.
Capacitance
A capacitor which is connected in parallel with the relay coil is changed through a
resistor, as shown in Fig. 2.17(a). A longer time-delay is obtained by this technique.
A delay of up to 0.5 s can be obtained on pick-up with a capacitor of reasonable size.
For ac applications, a rectifier should be included.
Resonant Circuit
A resonant circuit, as shown in Fig. 2.17(b) can be employed to produce a delay of
up to 3 cycles.
SS x
fo trip circuit z To trip circuit
(a) (b)
Fig. 2.17 (a) Capacitor charge delay (b) Resonance build-up delay48 Power System Protection and Switchgear
Ballistic Resistance
This technique is based on the principle of Ta hip circuit
delaying the build-up of operating voltage. This
includes thermistors or filament lamps. Figure
2.17(c) shows a metal filament lamp connected
across the relay coil. A resistance is also placed
in the circuit as shown in the figure. The hot
resistance of the lamp filament is 10 times its
cold resistance. The relay coil is short-circuited
by the lamp, thereby keeping the magnetic ¥
flux to zero for a short time until the filament
becomes incandescent. é
Alternatively, a thermistor or a carbon fila- Fig. 217. (c) Lamp filament
ment can be placed in series with the relay coil. heating delay
The thermistor resistance being high at room
temperature limits the coil current. As the current drawn by the relay coil heats the
thermistor, its resistance decreases until the relay current becomes sufficient for
pick-up.
ac. or d.c.
Synchronous Motor
A synchronous motor, geared to a reduced speed can be also used on ac to produce
more precise, long time delays.
Electronic Time Delay
Longer time delays are obtained with R-C circuits. R-C circuits are also used with
electromagnetic relays, as shown in Fig. 2.17(a). Longer time delays can be obtained
with R-C circuits when used with electronic relays rather than with electromagnetic
relays. This is due to the face that a smaller current is needed with electronic relays,
which in turn takes longer time to charge the capacitor.
Figure 2.18 shows a time-delay circuit employing a transistor. A constant de volt-
age is applied to an R-C network to charge the capaci- tor C through resistor R. When
the voltage of capacitor C reaches a suitable
value, the transis- tor starts conducting. A realy
is placed in the collector circuit. This relay oper-
ates when the transistor starts conducting. The
time delay depends on the value of the capacitor
and the magnitude of the charging current. As Relay
the charging current is small in a transistor cir- [—w—€
cuit, a delay of several minutes can be obtained
with a capacitor of only few microfarads. Delays
of several hours can be obtained with tantalum
capacitors of a few hundred microfarads.
Fig. 2.18 Static time delay circuit
Counter
For obtaining even more accurate time-delays, electronic counters are used. A crystal
oscillator or some suitable electronic circuitry is employed to generate a train of high
frequency pulses. Counters are used as frequency dividers. A number of countersRelay Construction and Operating Principles 49
may be connected in cascade and different time-lags may be obtained from different
stages of the cascaded counters.
2.2.7. Bearings
The pivot and jewel bearing is commonly used for precision relays. Spring-mounted
jewels are used in modern relays. The design is such that shocks are taken on a shoul-
der and not on a jewel.
For high sensitivity and low friction, a single ball bearing between two cup-shaped
sapphire jewels is used.
Mulii-ball bearings provide friction as low as the jewel bearings and have greater
resistance to shock. They arealso capable of combining side-thrust and end-thrust ina
single bearing. Miniature bearings less than 1.6 mm in diameter are now available.
Knife-edge bearings, pin bearings or resilient strips are used in hinged armature
relays.
2.2.8 Backstops
When the moving part of the relay is stationary, it rests against a backstop. The mate-
rial of a backstop should be chosen carefully so that it should not be sticky. To avoid
magnetic adherence, the material should be non-metallic. The molecular adherence
can be overcome using a hard surface rounded to a large radius. Smooth backstops
made of agate or nylon are used.
2.2.9 Contacts
The reliability of protective relays depends on their contact performance. The follow-
ing are the requirement of good contacts.
(i) Low contact resistance
(ii) High contact pressure
(iii) Freedom from corrosion
(iv) Bounce free
(v) Self-clearing action
(vi) Freedom from sparking
(vii) Dust proof
Silver is the most commonly used material for relay contacts. It has the lowest
resistance. Copper is not used because of its higher resistance. Silver cadmium oxide
is used where high currents are to be handled. It has low resistance like silver but
does not weld or become sticky. An alloy consisting of 67% gold, 26% silver and 7%
platinum is used for small currents and very light contact pressure. Non-corroding
materials like gold, palladium or rhodium can be used for sensitive relays where the
contact pressure needs to be very low. These materials are not recommended for
protective relays where high contact pressure is required.
The most reliable relay contact are cylindrical contacts at right angles, as they give
the optimum high pressure, bounce-proof contacts, hard smooth contact surfaces and
dust proof relay cases minimise the maintenance of protective relays.50 Power System Protection and Switchgear
On silver contacts silver oxide does not form readily. Even when formed, its
thickness does not exceed 10 A and hence can easily be moved aside by high pres-
sure or wiping action. Humid sulphurous and high temperature atmosphere causes
corrosion. In polluted atmospheres where coal fires are used, silver sulphide is formed
readily, especially in the presence of heat and humidity. It is not breakable like oxides
but it is soft and thus can be squeezed aside by high pressure. A thin petrolatum coat-
ing can reduce corrosion of contacts without increasing their resistance. It is helpful
in polluted atmospheres.
A dust-proof casing is usually used for modern relays. A filter is provided at the
back to trap any dust and to allow the relay to breathe. A relay with such a casing is
quite suitable for a dusty or otherwise dirty atmosphere. In a relay with poor ventila-
tion, particularly in a sealed relay, high resistance polymers may appear on contacts.
This is due to organic emanations from the coil insulation material. All insulating
materials, except teflon give off organic vapour to a certain degree. Phenolic resin
gives off organic vapours more than others. Polyester and epoxide varnishes now
available have good performance and are quite satisfactory for coil insulation. Relay
casings with good ventilation and having dust filters minimise the collection of high
resistance polymers on the contacts. Encapsulated contacts as in the case of reed
relays provide the best solution to the problem. Alternatively, the relay coil can also
be encapsulated.
An electromechanical relay used with comparators is usually of a small rating.
When such relays control auxiliary relays and timing units, they are to be protected
with spark quenching circuits. A series resistor and capacitor connected across the
contacts is a simple spark quenching circuit.
2.3. STATIC RELAYS
In a static relay, the comparison or measurement of electrical quantities is performed
by a static circuit which gives an output signal for the tripping of a circuit breaker.
Most of the present day static relays include a de polarised relay as a slave relay, The
slave relay is an output device and does not perform the function of comparison or
measurement. It simply closes contacts. It is used because of its low cost. In a fully
static relay, a thyristor is used in place of the electromagnetic slave relay. The elec-
tromechanical relay used as a slave relay provides a number of output contacts at low
cost. Electromagnetic multicontact tripping arrangements are much simpler than an
equivalent group of thyristor circuits.
A static relay (or solid state relay) employs semiconductor diodes, transistors,
zener diodes, thyristors, logic gates, etc. as its components. Now-a-days, integrated
circuits are being used in place of transistors. They are more reliable and compact.
Earlier, induction cup units were widely used for distance and directional relays.
Later these were replaced by rectifier bridge type static relays which employed de
polarised relays as slave relays. Where overcurrent relays are needed, induction disc
relays are in universal use throughout the world. But ultimately static relays will
supersede all electromagnetic relays, except the attracted armature relays and de
polarised relays as these relays can control many circuit at low costs.Relay Construction and Operating Principles 51
2.3.1. Merits and Demerits of Static Relays
The advantages of static relays over electromechanical relays are as follows.
(i) Low burden on CTs and VTs. The static relays consume less power and in
most of the cases they draw power from the auxiliary de supply
(ii) Fast response
(iii) Long life
(iv) High resistance to shock and vibration
(v) Less maintenance due to the absence of moving parts and bearings
(vi) Frequent operations cause no deterioration
(vii) Quick resetting and absence of overshoot
(viii) Compact size
(ix) Greater sensitivity as amplification can be provided easily
(x) Complex relaying characteristics can easily be obtained
(xi) Logic circuits can be used for complex protective schemes
The logic circuit may take decisions to operate under certain conditions and not to
operate under other conditions.
The demerits of static relays are as follows:
(i) Static relays are temperature sensitive. Their characteristics may vary with the
variation of temperature. Temperature compensation can be made by using
thermistors and by using digital techniques for measurements, ete.
(ii) Static relays are sensitive to voltage transients. The semiconductor components
may get damaged due to voltage spikes. Filters and shielding can be used for
their protection against voltage spikes.
(iii) Static relays need an auxiliary power supply. This can however be easily sup-
plied by a battery or a stabilized power supply.
2.3.2 Comparators
When faults occur on a system, the magnitude of voltage and current and phase
angle between voltage and current may change. These quantities during faulty con-
ditions are different from those under healthy conditions. The static relay circuitry
is designed to recognise the changes and to distinguish between healthy and faulty
conditions. Either magnitudes of voltage/current (or corresponding derived quanti-
ties) are compared or phase angle between voltage and current (or corresponding
derived quantities) are measured by the static relay circuitry and a trip signal is sent
to the circuit breaker when a fault occurs. The part of the circuitry which compares
the two actuating quantities either in amplitude or phase is known as the comparator.
There are two types of comparators—amplitude comparator and phase comparator.
Amplitude Comparator
An amplitude comparator compares the magnitudes of two input quantities, irrespec-
tive of the angle between them. One of the input quantities is an operating quantity
and the other a restraining quantity. When the amplitude of the operating quantity
exceeds the amplitude of the restraining quantity, the relay sends a tripping signal.
The actual circuits for comparators will be discussed in subsequent chapters.52 Power System Protection and Switchgear
Phase Comparator
A phase comparator compares two input quantities in phase angle, irrespective of
their magnitudes and operates if the phase angle between them is < 90°.
2.3.3. Duality between Amplitude and Phase Comparators
An amplitude comparator can be converted to a phase comparator and vice versa if
the input quantities to the comparator are modified. The modified input quantities
are the sum and difference of the original two input quantities. To understand this
fact, consider the operation of an amplitude comparator which has two input signals
M and N as shown in Fig. 2.19(a). It operates when |MI> INI. Now change the input
quantities to (M + N) and (M — N) as shown in Fig. 2.19(b). As its circuit is designed
for amplitude comparison, now with the changed input, it will operate when IM + M
> IM — MI. This condition will be satisfied only when the phase angle between M and
Nis less than 90°. This has been illustrated with the phasor diagram shown in Fig.
2.20. Itmeans that the comparator with the modified inputs has now become a phase
comparator for the original input signals M and N.
Mu (M+N)
it Output o——+| Output
Inputs Amplitude “a Inputs Amplitude pl
comparator comparator
N (M-N)
Operates when IM + NI>IM- NI
Operates when IM! > INI This condition is satisfied when 9 < 90°
(a) (b)
Fig. 2.19 (a) Amplitude comparator (b) Amplitude comparator used for
phase comparison
M-N M Man M-N M M+N
~~ S 6
\
-N @>90° N -N = 90° N
Comparison: (M +N) <(M-N) Comparison: (M+ N) = (M- N)
@) (b)
-N 9< 90° N
Comparison: (M+ N) > (M~ N)
Fig. 2.20 Phasor diagram for amplitude comparator used for phase comparisonRelay Construction and Operating Principles 53
Similarly, consider a phase comparator shown in Fig. 2.21(a). It compares the
phases of input signals M and N. If the phase angle between M and N, i.e. angle @ is
less than 90°, the comparator operates. Now change the input, signals to (M + N) and
(M - N), as in Fig. 2.21(b). With these changed inputs the comparator will operate
when phase angle between (M + N) and (M — N), i.e. angle J is less than 90°. This
condition will be satisfied only when [MI> INL. In other words, the phase comparator
with changed inputs has now become an amplitude comparator for the original input
signals M and N. This has been illustrated with phasor diagrams as shown in Fig.
2.22.
M (M+N)
Input | __ Phase Output Ingar | Phase Output
input comparator nput comparator =
N (M—N)
Operates when 4 < 90°
Operates when 9 < 90° This condition is satisfied when IMI > INI
(a) (b)
Fig. 2.21 (a) Phase comparator (b) Phase comparator used for amplitude comparison
Figure 2.20 shows three phasor diagrams for an amplitude comparator. The phase
angle between the original inputs Mand Nis ¢. Now the inputs to the amplitude com-
parator are changed to (M + N) and (M — N) and its behaviour is examined with the
help of three phasor diagrams. The three phasor diagrams are with phase angle (i)
greater than 90°, (ii) equal to 90° and (iii) less than 90°, respectively. When 9 is less
than 90°, IM + NI become greater than |M — Mand the relay operates with the modi-
fied inputs. When @ is equal to 90° or greater than 90°, the relay does not operate.
The phasor diagrams show that IM + NI becomes greater than IM — Nl only when @
is less than 90°. This will be true irrespective of the magnitude of M and N, In other
words, this will be true whether [MI = INI or IMI > IMI or IMI < INI. The figures have
been drawn with IM] = IMI. The reader can draw phasor diagrams with IMI < IMI or
IMI > INI. The results will remain the same. This shows that with changed inputs, the
amplitude comparator is converted to a phase comparator for the original inputs.
Figure 2.22 shows three phasor diagrams for a phase comparator. The original
inputs are M and N. Now the inputs of the phase comparators are changed to (M+ N)
and (M — N), and its behavior is examined with the help of three phasor diagrams
drawn for (i) IMI < IMI, (ii) IMI = INI and (iii) IMI > INI. The angle between (M + NV)
and (M — N) is A. The angle A becomes less than 90° only when |MI > IMI. As the
comparator under consideration is a phase comparator, the relay will tip. But for the
original inputs M and N, the comparator behaves as an amplitude comparator. This
will be true irrespective of the phase angle @ between M and N. The figure has been
drawn with @ less than 90°. The reader can check it by drawing phasors with @ = 90°
or @> 90°. The result will remain the same.
2.3.4 Types of Amplitude Comparators
As the ratio of the instantaneous values of sinusoidal inputs varies during the cycle,
instantaneous comparison of two inputs is not possible unless at least one of the54 Power System Protection and Switchgear
N we
N
M 90° Comparision: 4 > 90°
(a) (b)
M-N_ M M+N
a
{Y]
-N
M>N
Comparison: / < 90°
(c)
Fig. 2.22 Phase comparator used for amplitude comparison
signals is rectified. There are various techniques to achieve instantaneous compari-
son. In some techniques both inputs are rectified, while in some methods, only one of
the inputs is rectified. When only one input signal is rectified, the rectified quantity
is compared with the value of the other input at a particular moment of the cycle.
Besides instantaneous (or direct) comparison, the integrating technique is also used.
The amplitude comparison can be done in a number of different ways. The follow-
ing are some important methods which will be described to illustrate the principle.
(i) Circulating current type rectifier bridge comparators
(ii) Phase splitting type comparators
(iii) Sampling comparators.
Rectifier Bridge Type Amplitude Comparator
The rectifier bridge type comparators are widely used for the realisation of overcur-
rent and distance relay characteristics. The operating and restraining quantities are
rectified and then applied to a slave relay or thyristor circuit. Figure 2.23(a) shown a
rectifier bridge type amplitude comparator. There are two full wave rectifiers, one for
the operating quantity and the other for the restraining quantity. The outputs of these
bridges are applied to a de polarised relay. When the operating quantity exceeds the
restraining quantity, the relay operates. Figure 2.23(b) shows a rectifier bridge type
amplitude comparator with the thyristor circuit as an output device.
To get more accurate results the bridge rectifier can be replaced by a precision
rectifier employing an operational amplifier. The circuit for the precision rectifier has
been discussed while describing microprocessor based relays.Relay Construction and Operating Principles 55
Sensitive polarised relay
Se | Te
90°. Thus, the phase comparator circuit is designed
to trip signal when y exceeds 90°.aa
You have either reached a page that is unavailable for viewing or reached your viewing limit for this
book.aa
You have either reached a page that is unavailable for viewing or reached your viewing limit for this
book.Relay Construction and Operating Principles 59
Figure 2.27(d) and (e) show the outputs of the AND gate and the integrator,
respectively. This situation is for y = 90° and is the limiting condition. The relay
may be set to operate at y= 90°.
rae Sine to
e square wave
converter a
Inputs I h te aN
PiaNe> | Imssiai' | "| detector [7
~ Sine to
e square wave Coincidence
converter detector
(a)
‘
(b) v
Operate
’
() reset
Output of
coincidence
(d) ~* Detector at
the boundary
Operate
reset
(e) Output of
integrator
(f)
k—10 ms—> = Opandie
~ Reset
@ 2a ~~ |
Fig. 2.27 _ Integrating type phase comparator
Figure 2.27(f) and (g) show the outputs of the AND gate and the integrator, respec-
tively, for y< 90°. For this condition, the relay does not operate.
+Veg
mene
|
To thyristor
Input
Fig. 2.28 Integrating circuitaa
You have either reached a page that is unavailable for viewing or reached your viewing limit for this
book.aa
You have either reached a page that is unavailable for viewing or reached your viewing limit for this
book.aa
You have either reached a page that is unavailable for viewing or reached your viewing limit for this
book.Relay Construction and Operating Principles 63
2.5 COMPARISON BETWEEN ELECTROMECHANICAL
RELAYS AND NUMERICAL RELAYS
Sr.No. Feature Electromechanical Relay Numerical Relay
1. Size Bigger Compact
2. Characteristics Fixed Selectable
3. Flexibility No flexibility Flexibility due to
programmability.
4. Communication feature Not available Available
5. Blocking feature Not available Available
6. Self-supervision Not available Available
7. Adaptability Not adaptable Adaptable to changing
system condition.
8. Multiple-functions Not possible Possible
9. Accuracy + 5% or more + 2%
10. Speed of operation Slow Fast
11. Burden on Transducers Very high Extremely low
(CTs and VTs)
12. Consistancy of Deteriorate No effect on calibration even
calibration with time after use of 20-25 years
13. Setting Through plug Software based settings.
setting in fix steps.
14. Memory feature No memory of any Several memory features
type is available. are available.
15. Maintenance Cumbersome and — Maintenance free relays
frequent mainte-
nance required.
16. Output relay programming Not available Available
17. Accessibility of relay Not possible Remote accessibility is
from remote place available
18. Status of service values Not available Available
19. Safety of personnel Not adequate due Adequate safety is provided.
to non-accessibility
at remote location.
20. Spares requirement There is need to Universal designs minimise
stock several items the spares requirement.
as spare.
21. Upward connectivity Not possible Possible
for a present or future
system such as SCADA,
EMS etc.aa
You have either reached a page that is unavailable for viewing or reached your viewing limit for this
book.aa
You have either reached a page that is unavailable for viewing or reached your viewing limit for this
book.aa
You have either reached a page that is unavailable for viewing or reached your viewing limit for this
book.Current and Voltage Transformers 67
voltage tends to collapse. The fault current is abnormal and may be 20 to 50 times the
full-load current. It may have de offset in addition to ac component. The fault current
for a CT secondary of 5A rating could be 100 to 250 A. Therefore, the CT secondary
having a continuous current rating of 5A should have short-time current rating of
100 to 250 A, so that the same is not damaged. Since the ac component in the fault
current is of paramount importance for the relays, the protective CT should correctly
reproduce it on the secondary side in spite of the de offset in the primary winding.
Hence the de offset should also be considered while designing the protective CT. The
protective CT should not saturate upto 20 to 50 times full-load current.
3.2.2. Core Material of CTs
Figure 3.1 shows the magnetisation Characteristics of (a) cold-rolled grain-oriented
silicon steel (3%), (b) hot-rolled silicon steel (4%) and (c) nickel-iron (77% Ni, 14%
Fe). It is seen that the nickel-iron core has the qualities of highest permeability, low
exciting current, low errors and saturation at a relatively low flux density. Measuring
CTs are required to give a high accuracy for all load currents up to 125% of the rated
current. Nickel-iron gives a good accuracy up to 5 times the rated current and hence,
it is quite a suitable core material for CTs used for meters and instruments. The
excessive currents being fed to instruments and meters are prevented during faults on
power system due to almost absolute saturation at relatively low flux density.
Cold-rolled grain-oriented silicon steel (3%), which has a high permeability, high
saturation level, reasonably small exciting current and low errors is used for the core
of the CTs used for protective relays. Such core material has reasonably good accu-
racy up to 10-15 times the rated current, but when we consider currents that are five
times under the rated current, the core material made from nickel-iron alloy fares
batter.
+— Cold-rolled silicon steel
a
/ Hot-rolled silicon steel
ae
L — High-nickel steel
0 1 2 3
Exciting Force (Atiem) —>
&
Flux density B,,,, (Wb/m*)
°
&
Fig. 3.1 Magnetisation characteristics of CT cores
Hot-rolled silicon steel has the lowest permeability. So it is not suitable for CTs.
In order to achieve the desired characteristics, composite cores made of laminations
of two or more materials are also used in CTs.aa
You have either reached a page that is unavailable for viewing or reached your viewing limit for this
book.aa
You have either reached a page that is unavailable for viewing or reached your viewing limit for this
book.aa
You have either reached a page that is unavailable for viewing or reached your viewing limit for this
book.Current and Voltage Transformers 71
(xiv) Rated primary saturation current The maximum value of primary current
at which the required accuracy is maintained
(xy) Rated saturation factor The ratio of rated primary saturation current to rated
primary current.
3.2.5 Theory of Current Transformers
Conventional electromagnetic current transformers (CTs) are single primary and
single secondary magnetically coupled transformers. Hence, their performance can
be analysed from and equivalent circuit commonly used in the analysis of transform-
ers. The equivalent circuit of CT as viewed from secondary side is shown in Fig. 3.3.
It is convenient to put the exiting shunt circuit on the secondary side and to refer all
quantities to that side, so that / denotes the primary current referred to the secondary
side. The exciting current J, is deducted from /, to excite the core and induce voltage
E, which circulates current /,.
Fig. 3.3 Equivalent circuit of CT as viewed from secondary side
An ideal (perfect) transformer shown in Fig. 3.3 is to provide the necessary ratio
change, it has no loss or impedance. All the quantities are referred to the secondary
side. In an ideal CT, the primary ampere-turns (AT) is exactly equal in magnitude
to the secondary AT and is in precise phase opposition to it. But in practical (actual)
CTs errors are introduced both in magnitude and in phase angle. These errors are
known as ratio error and phase angle error. The exciting current Jy is the main source
of these errors. Practical CTs do not reproduce the primary currents exactly in mag-
nitude and phase due to these errors.
The errors of practical CTs can best be considered through the study of the phasor
diagram shown in Fig. 3.4
In the equivalent circuit of Fig. 3.3 and phasor diagram of Fig. 3.4,
N= Nominal (rated) transformation ratio or Nominal (rated) CT ratio
_ Rated primary current _ Number of secondary turns
~ Rated secondary current Number of primary turns
R,, X, = Primary resistance and leakage reactance respectively.
R, and X, = secondary resistance and leakage reactance
R, and X;, = Primary resistance and leakage reactance as referred to the
secondary sideaa
You have either reached a page that is unavailable for viewing or reached your viewing limit for this
book.aa
You have either reached a page that is unavailable for viewing or reached your viewing limit for this
book.aa
You have either reached a page that is unavailable for viewing or reached your viewing limit for this
book.Current and Voltage Transformers 75
Ratio Error (Current Error)
The actual transformation ratio (N,) is not equal to the rated (nominal) transforma-
tion ratio (N) since the primary current is contributed by the exciting current. The
error introduced due to this difference in CT ratios is termed as ratio error or current
error. The ratio error in percentage is expressed as
Nominal ratio — Actual ratio
Per cent ratio error = ————_——_——————— x 100
Actual ratio
=x 100
N-1/l,
or Per cent ratio error = ——— x 100
7M,
or Per cent ratio error = —>— x 100 (3.14)
B
Where N = Nominal (rated) ratio
Rated primary current
~ Rated secondary current
Number of secondary turns
Number of primary turns
N,, = Actual ratio
I, = Primary Current
1, = Secondary current
1, can be calculated by using Equation (3.7) and N, by using Equation (3.9) or
(B.10)
The ratio error is largely dependant upon the value of the iron-loss component I,
of the exciting current.
The ratio error is considered to be positive when the actual ratio of the CT is less
than the nominal ratio, i.e., when the secondary current, for a given primary current,
is high.
Phase-Angle Error
For a perfect (ideal) current transformer, the phase difference between the primary
and reversed secondary phasors is zero. But for an actual transformer, there is always
a difference in phase between the two phasors due to the fact that primary current has
to supply the components of the exciting current. The phase difference between the
primary current phasor and the reversed secondary current phasor is termed as the
‘phase-angle error’ of the CT. For sinusoidal current, it is said to be positive when the
reversed secondary current phasor leads the primary current phasor. The phase angle
error Bcan be calculated by using Equation (3.12) or (3.13).
The phase-angle error is largely dependant upon the value of the magnetizing
component /,, of the exciting current.aa
You have either reached a page that is unavailable for viewing or reached your viewing limit for this
book.aa
You have either reached a page that is unavailable for viewing or reached your viewing limit for this
book.aa
You have either reached a page that is unavailable for viewing or reached your viewing limit for this
book.Current and Voltage Transformers 79
ZL
--( Ne (3.21)
For the transient component of i,, and integrating from f= 0 to r= ©
R,
tel ‘ dt
0
i
On = (x) Dies
1
a
D
ZL, x,
_ [2s tom) [Ap 7)
= | eS Z| (3.22)
Therefore, the component of the core flux due to the transient component of the
fault current is X,/R, times the component of the core flux due to the steady-state
component of the fault current. Considering the worst case of a fault near a large
power station, X,/R, could be as high as 30, corresponding to a primary-circuit time
constant of L,/Rp =0.1 s, or about 5 cycles.
Assuming that the two fluxes can be added numerically (the worst case), the total
core flux is equal to the steady-state component multiplied by the factor
(*) nfl,
14{[—)e14
=14+2,
R R, e
a 7
where 7, is the primary circuit time-constant in cycles. The flux waveforms are
shown in Fig. 3.6
Total flux.
Transient component
Flux ——>
Steady-state component
1 2 3 4 5
Cycles ——»
Fig. 3.6 CT core fluxes during transient period
The value of XJR, increa with the system voltage because of the increased
spacing of the conductors. The component of the core flux due to transient de off-
set Current increases X,/R, times the flux due to the symmetrical (steady-state) acaa
You have either reached a page that is unavailable for viewing or reached your viewing limit for this
book.aa
You have either reached a page that is unavailable for viewing or reached your viewing limit for this
book.aa
You have either reached a page that is unavailable for viewing or reached your viewing limit for this
book.Current and Voltage Transformers 83
Fig. 3.8 (a) Left polarized beam
(b) Right polarized beam
Opto-electronic CTs generate two jin- oe i
early polarized light beams by sending light /
|
then to a polarization splitter, and finally
to an optical phase modulator. The two lin-
to a polarizing retaining optical fiber that (a) (b)
takes them to the “sensing head”. A circular
larly polarized beam and the other to a right
circularly polarized beam, as shown in Fig
The circular polarized beams travel around the phase conductor many times.
While encircling the conductor, the magnetic field induced by the current flow-
beams due to the Faraday effect. As a result of this, one beam is accelerated and the
other beam is decelerated. After having gone around the conductor many times, the
result, the right polarized beam becomes a left polarized beam and the left polarized
beam becomes a right polarized beam. The beams travel back around the conductor
ated beam and further decelerates the decelerated beam. The polarizer changes the
circular polarizations to linear polarization.
decelerated. In this case, the returning beams are in phase as shown in Fig, 3.9(a).
When there is a current in the conductor, the acceleration of one beam and decelera-
Fig. 3.9(b).
The two light beams are finally routed to the optical detector where the electron-
light beams is proportional to current in the conductor. An analog or digital signal
representing the current is provided by the electronics to the end user.
currents with significant de offsets without any type of saturation, as is understood
with conventional electromag-
through a waveguide to a linear polarizer, )
\
early polarized light beams are then applied ae
polarizer converts one beam to a left circu-
3.8(a) and (b).
ing in the conductor creates a differential optical phase shift between the two light
beams are reflected by a mirror. The reflection changes the polarization, and as a
towards the polarizer. The travel on the return path further accelerates the acceler-
When there is no current in the conductor, the beams are neither accelerated nor
tion of the other beam manifests in a phase shift between the two beams as shown in
ics de-modulate them to determine the phase shift. The phase shift between the two
Opto-electronic CTs provide a reliable method of measuring very high fault
netic CTs.
3.2.13. Rogowski Coil
A Rogowski Coil, named after
Walter Rogowski, is an. ‘air-
cored’ toroidal coil of wire
used for measuring alternating
current (ac) or high frequency
current pulses. It is the mod-
(a) (b)
ern current sensor. It consists Fig. 3-9 (a) Beams in phase (b) Acceration of one
BE A ORUGALSCBUNGE WHS With beam and deceleration of the other beam