This document contains information about an LVAC-TRANSCO-BUS_A circuit including its nominal voltage of 0.415 kV. It describes a 630A MCCB circuit breaker manufactured by Siemens with a thermal trip setting of 100% and fixed magnetic trip. It also contains details about an ABB REF615 relay with a 2000:1 CT ratio set with a normal inverse time-current characteristic, 0.65 pickup setting, and 0.07 time dial setting providing 3x, 5x, and 8x time multiplications. The document appears to be from an ETAP power system modeling case study.

Uploaded by

joshi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
52 views1 page

Case 4

This document contains information about an LVAC-TRANSCO-BUS_A circuit including its nominal voltage of 0.415 kV. It describes a 630A MCCB circuit breaker manufactured by Siemens with a thermal trip setting of 100% and fixed magnetic trip. It also contains details about an ABB REF615 relay with a 2000:1 CT ratio set with a normal inverse time-current characteristic, 0.65 pickup setting, and 0.07 time dial setting providing 3x, 5x, and 8x time multiplications. The document appears to be from an ETAP power system modeling case study.

Uploaded by

joshi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Amps X 100 LVAC-TRANSCO-BUS_A (Nom. kV=0.415, Plot Ref. kV=0.

415)
.5

10

30

50

100

300

500

1K

3K

5K

1K

10K
1K

500

500

300

300

630A MCCB
SIEMENS 3VL630
3VL57631
Size = 630 Amps
Thermal Trip = 100%
Magnetic Trip = Fixed

100

50

30

RP-TRANSCO-LVAC_BS - P
OC1

30

10

ABB
REF615
CT Ratio 2000:1
IEC - Normal Inverse
Pickup = 0.65 (0.3 - 5 xCT Sec)
Time Dial = 0.07
3x = 0.441 s, 5x = 0.3 s, 8x = 0.231 s

10

.5

.5

.3

.3

.1

.1

.05

.05

.03

.03

.01
.5

10

30

50

100

300

500

1K

Amps X 100 LVAC-TRANSCO-BUS_A (Nom. kV=0.415, Plot Ref. kV=0.415)


N7733:ZAKHER
Project:
Location:
Contract:
Engineer:
Filename:

220/33/11kV Zakher Grid


Zakher Area of Al Ain
N7733
JM
C:\ETAP 1250\N7733\N7733.OTI

CASE:4.3
Date:
SN:
Rev:
Fault:
Circuit:

23-01-2016
LARSENTRN2
Base
Phase
LVAC BS,MCCB630A

3K

5K

.01
10K

ETAP Star 12.5.0C

Seconds

Seconds

50

100